VIBRO KIT
TECHNICAL REFERENCE MANUAL
●
Enable motor and start Ramp cycling by holding RUN_SW for 1 sec. Number of cycles remaining
is now shown in bold font. Arrow is also shown in bold and shows the current step of ramp cycle.
Parameters are updated live during runtime to show progress. Editing of parameters is disabled.
●
Disable motor and stop Ramp cycling by pressing RUN_SW. Display returns to non-bold font and
initial parameters are shown. Editing of parameters is enabled.
●
When the number of cycles to be done is reached, Ramp is automatically stopped and motor
disabled.
●
To exit Ramp mode, hold ENC_SW for 1sec while Ramp is not cycling.
6.3 Analog in mode
●
Connect external voltage source to Control Input.
●
Optionally set Acceleration rate (ACCEL) if input voltage is expected to be rising too quickly,
which would cause the motor to accelerate too quickly, leading to input current limiter tripping.
●
Enable motor by holding RUN_SW for 1sec. ON is displayed.
●
Input voltage is scaled 1:1 to motor output voltage.
●
Regardless of input voltage, motor voltage is limited to max. 6,00V.
●
Disable motor by pressing RUN_SW shortly. OFF is displayed.
●
To exit Analog In mode, disable motor first, then hold ENC_SW for 1sec.
6.4 PWM in mode
●
Connect external PWM source to Control Input. Allowed voltage levels range is from 3V TTL to
36V.
●
Optionally set Acceleration rate (ACCEL) if input duty cycle is expected to be changing too
quickly, which would cause the motor accelerate too quickly, leading to input current limiter
tripping.
●
Enable motor by holding RUN_SW for 1sec. ON is displayed.
●
Duty cycle is measured, maximum PWM frequency is 5kHz. Duty cycle values 0%...100% are
scaled to motor voltage 0,00 … 10,00V.
●
Regardless of input duty cycle, motor voltage is limited to max. 6,00V.
●
Disable motor by pressing RUN_SW shortly. OFF is displayed.
●
To exit PWM In mode, disable motor first, then hold ENC_SW for 1sec.
VIBRO KIT V20-1