ELECTROVAP® KIT MC
20
3.4
STEAM OUTLET
1.
Preferably use a flexible steam hose that is resistant to a temperature of 100°C.
NB: when new hoses are installed, a smell of burnt plastic may be smelt during the first running of the
steam humidifier. This is normal and will eventually diminish.
2.
Steam hose selection:
Model
KIT MC
5 à 15
KIT MC
20 à 30
KIT MC
40 à 60
Number of steam outputs
1
1
2
Diameter steam output hose [mm]
Ø 25-40
Ø 40-25
Ø 40-25
3.
KIT MC humidifiers can operate with a pressure (P) higher than the atmospheric pressure in the
ducts, but under the following conditions:
•
If P is less than 150 mm WC or 1470 Pa.
•
If P is greater than 150 mm WC (1470 Pa), options are available up to 700 mm WC (6860 Pa).
4.
For the installation of the steam hose, depending on your environment, please respect the
recommendations below and use the appropriate tangential hose clamps.
•
Flexible steam hose length 3 m max.
•
Stainless steel or copper pipe with a slightly larger diameter, grounded. Use a flexible steam hose
cuff to connect the humidifier to the steam distribution pipe. The length of the pipe must be
thermally insulated and should not exceed 6 m.
Always have a slope in the same direction (up or down); the steam hose must
be free of kinks and sags to allow for gravity drainage of condensate.
Make sure that the steam hose is not leaky. Failure to follow these
instructions can lead to serious malfunctions.
Radius of the diameter steam pipe:
•
Ø 25
-
250mm minimum
•
Ø 40
-
400mm minimum
Ø 300 mm min./
12’’ min.
Fig. B 3-4.
Additional drip leg when steam distribution
below humidifier
Fig. A 3-4.
Standard installation
Summary of Contents for ElectroVap KIT MC 15
Page 1: ...ElectroVap HUMIDIFIERS KIT MC Series Instruction Operation Manual ...
Page 2: ...ELECTROVAP KIT MC 2 ...
Page 32: ...ELECTROVAP KIT MC 32 KITMC 8 à 20 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Page 33: ...ELECTROVAP KIT MC 33 KITMC 30 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Page 34: ...ELECTROVAP KIT MC 34 KITMC 40 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Page 35: ...ELECTROVAP KIT MC 35 KITMC 50 60 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Page 46: ...ELECTROVAP KIT MC 46 ...
Page 47: ...ELECTROVAP KIT MC 47 ...