User Manual DEV 5072
Copyright DEV Systemtechnik GmbH 2016-2017
29
5.4.4.2
Control Tab with UPS
If the UPS functionality is activated (please refer to chapter 5.4.6.3.1) and if on the
left side of the Control Tab the structuring entry "
UPS
" is selected, the
corresponding panel appears on the right side.
The status shown in in the following screenshot is supposed to reflect the normal
condition of the properly configured and operating power system:
the power supply modules of the DEV 5072 are working normally, i.e. the
attached load is supplied by the power supply modules,
the latest battery test returned the status "Battery OK",
the output voltage ("V") equals the battery voltage ("V
Bat
"), the batteries are
charged to a 100%, i.e. the voltage setpoint of the power supply modules is
adjusted to the battery voltage, and there is neither charging nor discharging,
and the communication with the Battery Management Controller (BMC) is
working properly, thus the "System Status" is "Ready".