Hardware ports, switches and LEDs PROFIBUS DP
Deutschmann Automation GmbH & Co. KG
30
Fieldbus-Gateway UNIGATE
®
CX C4Map - PROFIBUS V. 1.0
28.9.20
9.1.1.2
Connector supply voltage and DEBUG-interface
Pin assignment X2 (4-pole screw-plug connector, on the bottom side, at the back)
Pin No.
Name
Function
1
UB (Out)
10..33 V supply voltage / DC
2
0 V (Out)
0 V supply voltage / DC
3
Rx-Debug
Receive signal Debug
4
Tx-Debug
Transmit signal Debug
Attention:
The ground for the DEBUG interface is pin 2, 0V (Pwr).
9.1.1.3
PROFIBUS DP-connector
The plug (labeled: PROFIBUS) for the connection to PROFIBUS is available on the front side of
the device.
Pin assignment (9-pole D-SUB, socket)
Pin No.
Name
Function
1
Shield
2
3
B
Not inverting input-/output-signalfrom PROFIBUS
4
CNTR-P
Control signal / repeater
5
M5
DGND-data reference potential
6
P5
5 V supply voltage
7
8
A
Inverting input-/output-signal from PROFIBUS
9
9.1.1.4
Power supply
The device must be powered with 10-33 VDC, The voltage supply is made through the 4-pole
screw-plug connector at the device’s bottom side.
Please note that the devices of the series UNIGATE
®
should not be operated with AC voltage.
9.2 LEDs
The Gateway UNIGATE
®
CL - PROFIBUS features 9 LEDs with the following significance:
LED (Bus) Power
green
Supply voltage PROFIBUS
LED Bus
red
PROFIBUS error
LED (Bus) State
red/green
Interface state PROFIBUS
LED Power
green
Supply voltage serial interface
LED State
red/green
User-defined / general Gateway error
LEDs 1 / 2 / 4 / 8 (Error No. / Select ID) green
User-defined / general Gateway error
9.2.1
LED "(Bus) Power"
This LED is connected directly to the electrically isolated supply voltage of the PROFIBUS-side.
9.2.2
LED “Bus“
This LED is directly controlled by the PROFIBUS ASIC and goes out in the state "DATA
EXCHANGE".
Summary of Contents for UNIGATE CX C4Map