53
95-8714
6.3
ONBOARD HART INTERFACE
The on-board HART interface is functional on the EQP LS2000, however, it should
not
be used to select
the gas type, alarm levels, or the beam block delay time because the LON will overwrite these values.
All EQP device configuration should be performed using the S
3
program.
MULTI-COLORED LED
Operation of the status indicating LED is identical to all other LS2000 versions.
REMOTE CALIBRATION OPTION
Operation of the remote calibration option is identical to all other LS2000 versions.
ANALOG OUTPUT
A 4–20 mA analog current output is not available with EQP LS2000.
RS-485 COMMUNICATION
RS-485 Modbus RTU communication is available with EQP LS2000.
CALIBRATION ROUTINE
The calibration procedure for the EQP LS2000 (zero calibration) is identical to all other LS2000
versions. Zero calibration can also be initiated by S
3
.
NOTE
For complete information regarding installation, configuration or operation of the Eagle
Quantum Premier system, refer to form 95-8533 (Eagle Quantum Premier hardware manual) or
form 95-8560 (Safety System Software manual).
Table G-2—
LS2000 Static
Alarm Logic (Thresholds Programmed Using S
3
Configuration Software)
Field Device
LS2000
Fire
Alarm
High Gas
Alarm
Low Gas
Alarm
Trouble
Supervisory
High Alarm
X
Low Alarm
X