41
95-8714
6.3
ATEX Standards:
EN 60079-29-4: 2010
Performance Approved for Methane, Butane, and Propane.
EN 60079-0: 2012 +A11:2013
EN 60079-1: 2014
EN 60079-7: 2015
EN 60079-28:2007
EN 60529:1991+A1:2000
EN 50270: 2015
EN 50271: 2010
CE:
Conforms to:
Low Voltage Directive: 2014/35/EU,
EMC Directive: 2014/30/EU,
ATEX Directive: 2014/34/EU, WEEE 2002/96/EC.
ACCURACY (PER EN 60079-29-4)
±5% of full scale gas concentration or ±10% of applied gas concentration, whichever is greater.
RESPONSE TIME
T90:
2 seconds (2.5 LFL-meters applied).
Note: Add 1 second to response time for EQP compatible models
ALIGNMENT
Misalignment will cause the manufacturer stated accuracy limits to increase, but remain within the
limits of EN 60079-29-4.
Accessories with the following part numbers are approved for use with the LS2000:
011773-001
Short Range Aperture Kit
012287-002
LS2000 Alignment Tool
009246-003
Gas Test Cell, Methane, ISO*
009246-004
Gas Test Cell, Methane, IEC
009246-005
Gas Test Cell, Propane, ISO
009246-006
Gas Test Cell, Propane, IEC
009246-007
Gas Test Cell, Butane, ISO
009246-008
Gas Test Cell, Butane, IEC
012673-001
System Test Film (set of 5 films)
012312-001
Transmitter Brow
012300-001
Receiver Brow
012660-001
Mounting and Alignment Bracket
103922-001
HART Handheld Communicator
011824-001
LS2000 Inspector Software
102740-002
Calibration Magnet
*ISO = NFPA 497
IEC = IEC 60079-20-1