background image

www.desatech.com

113084-01A

6

Unusually Tight Construction

The air that leaks around doors and windows may
provide enough fresh air for combustion and ven-
tilation. However, in buildings of unusually tight
construction, you must provide additional fresh air.

Unusually tight construction is defined as
construction where:
a. walls and ceilings exposed to the out-

side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6 x 10

-11

 kg per pa-sec-m

2

)

or less with openings gasketed or
sealed and

b. weather stripping has been added on

openable windows and doors and

c. caulking or sealants are applied to ar-

eas such as joints around window and
door frames, between sole plates and
floors, between wall-ceiling joints, be-
tween wall panels, at penetrations for
plumbing, electrical, and gas lines, and
at other openings.

If your home meets all of these three crite-
ria, you must provide additional fresh air.
See 

Ventilation Air From Outdoors, page 7.

If your home does not meet all of the three
criteria above, proceed to 

Determining

Fresh-Air Flow For Fireplace Location,
column 2.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA
54
 defines a confined space as a space whose vol-
ume is less than 50 cubic feet per 1,000 Btu per
hour (4.8 m

3

 per kw) of the aggregate input rating

of all appliances installed in that space and an un-
confined space as a space whose volume is not less
than 50 cubic feet per 1,000 Btu per hour (4.8 m

3

per kw) of the aggregate input rating of all appli-
ances installed in that space. Rooms communicat-
ing directly with the space in which the appliances
are installed*, through openings not furnished with
doors, are considered a part of the unconfined space.

* Adjoining rooms are communicating only if there
are doorless passageways or ventilation grills be-
tween them.

AIR FOR COMBUSTION

AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION

Determining if You Have a Confined or
Unconfined Space

Use this work sheet to determine if you have a
confined or unconfined space.

Space: 

Includes the room in which you will install

fireplace plus any adjoining rooms with doorless pas-
sageways or ventilation grills between the rooms.

1.

Determine the volume of the space (length x
width x height).

Length x Width x Height =__________cu. ft.
(volume of space)

Example: 

Space size 20 ft. (length) x 16 ft.

(width) x 8 ft. (ceiling height) = 2560 cu. ft. (vol-
ume of space)

If additional ventilation to adjoining room is sup-
plied with grills or openings, add the volume of
these rooms to the total volume of the space.

2.

Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) x 20 =

51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in
the space.

Vent-free fireplace

__________ Btu/Hr

Gas water heater*

__________ Btu/Hr

Gas furnace

__________ Btu/Hr

Vented gas heater

__________ Btu/Hr

Gas fireplace logs

__________ Btu/Hr

Other gas appliances* + __________ Btu/Hr

Total                            = __________ Btu/Hr

* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors
and vents to the outdoors.

Example:

Gas water heater

______________ Btu/Hr

Vent-free fireplace ______________ Btu/Hr

Total

______________ Btu/Hr

4.

Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.

________ Btu/Hr (maximum the space can support)

________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space
can support)

70,000 Btu/Hr (actual amount of
Btu/Hr used)

The space in the above example is a confined space
because the actual Btu/Hr used is more than the maxi-
mum Btu/Hr the space can support. You must pro-
vide additional fresh air. Your options are as follows:

40,000

+ 30,000

= 70,000

Summary of Contents for SVYD18NRA Series

Page 1: ...not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instruction...

Page 2: ...ust be provided Refer to Air for Combustion and Ventilation section on page 5 of this manual This appliance may be installed in an aftermarket permanently located manufactured mobile home where not pr...

Page 3: ...and proper operation of this heater WARNING Any change to this heater or its controls can be dangerous WARNING Do not allow fans to blow directly into the heater Avoidanydraftsthatalterburner flame p...

Page 4: ...r has an Oxy gen Depletion Sensing ODS safety shutoff system The ODS shuts down the heater if not enough fresh air is available See Air for Com bustion and Ventilation pages 5 through 7 If heater keep...

Page 5: ...ction unless provisions are provided foradequatecombustionandven tilation air Read the following in structions to insure proper fresh air for this and other fuel burning appliances in your home Today...

Page 6: ...hem AIR FOR COMBUSTION AND VENTILATION Continued DETERMINING FRESH AIR FLOW FOR HEATER LOCATION Determining if You Have a Confined or Unconfined Space Use this work sheet to determine if you have a co...

Page 7: ...on the wall connecting the two spaces see options 1 and 2 Figure 2 You can also remove door into adjoining room see option 3 Figure 2 Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Section 5 3...

Page 8: ...rs add moisture to the air Although this is beneficial installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture See Air for Combustion and Ventilation...

Page 9: ...tove body on back to attach bottom components to stove body see Fig ure 5 Rest stove on drop cloth or blanket to avoid scratching stove edges 6 Remove remaining pallet wood attached to bot tom of stov...

Page 10: ...an to stove with two 2 M6 x 1 25mm bolts Use a flat washer and lock washer with each bolt Tighten bolts into threaded holes on stove body see Figures 7 and 9 Use an adjustable wrench or a 10mm socket...

Page 11: ...d washers 6 Place freestanding stove in desired position in room Be sure to maintain clearances to combustibles as outlined on page 8 CAUTION After installation and periodically thereafter check to en...

Page 12: ...ironorsteelpipe Internally tinned copper tubing may be used in certain areas Check your local codes Use pipe of 1 2 diameter or greater to allow proper gas volume to heater If pipe is too small undue...

Page 13: ...t Pressures In Excess Of 1 2 PSIG 3 5 kPa 1 Disconnect appliance with its appliance main gas valve control valve and equipment shutoff valve from gas supply piping system Pressures in excess of 1 2 ps...

Page 14: ...ilot which must be lighted by hand When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because so...

Page 15: ...30 seconds release control knob If control knob does not pop out when re leased contact a qualified service person or gas supplier for repairs Note If pilot goes out repeat steps 4 through 8 9 Slightl...

Page 16: ...old the control button again until burner turns off see Figure 23 TO LOCK press both buttons on hand held re mote control until light stops flashing Hand held remote control is now locked If the fire...

Page 17: ...nd held remote in the MANU or AUTO mode to prevent inadvertent opera tion i e children operating the hand held re mote control etc The keypad is locked in ei ther on or off Press the POWER and LOCK bu...

Page 18: ...n You can use a vacuum cleaner in the blow position If using compressed air in a can please follow the directions on the can If you don t follow directions on the can you could damagethepilotassembly...

Page 19: ...ressure B Dirty or partially clogged ODS pilot 5 Thermocouple connection loose at control valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if...

Page 20: ...y 2 Clean burner see Cleaning and Maintenance page 18 or replace burner orifice 1 Clean burner see Cleaning and Maintenance page 18 or replace burner orifice 2 Replace damaged burner 3 Replace gas con...

Page 21: ...paint paint remover cigarette smoke cements and glues new carpet or textiles etc create fumes These fumes may mix with combustion air and create odors These odors will disappear over time POSSIBLE CA...

Page 22: ...ech com 113084 01A 22 ILLUSTRATED PARTS BREAKDOWN MODELS SVYD18PRA AND SVYD18NRA O F F P I L O T O N H I L O H I L O O F F P I L O T O N 17 17 18 19 24 15 14 16 13 12 12 11 22 23 20 10 9 21 4 8 5 3 2...

Page 23: ...1 02 103781 01 Gas Control Valve 1 11 103345 02 103345 02 Lower Bracket 1 12 M11084 38 M11084 38 Screw 8 x 38 7 13 104383 02CK 104383 02CK Painted Base Assy 1 14 098271 10 098271 10 Ignitor Cable 1 15...

Page 24: ...A 24 2 5 5 5 5 8 7 4 6 7 1 7 2 4 9 7 3 3 1R 1C 1L 10 9 10 ILLUSTRATED PARTS BREAKDOWN Oxford VCIS Series and PVCIS Series Victor Hearth VH A Series Indicates Color Suffix Designation Oxford Stove Body...

Page 25: ...Nuts 1 Per Unit 1 7 3 Bottom Floor Bolts M6 x 1 25mm Long With Flat Washer And Lock Washer 4 Per Unit 1 7 4 Leg Bolts M8 x 1 25 20mm Long With Flat Washer And Lock Washer 4 Per Unit 1 8 104178 01 Bac...

Page 26: ...bers of your heater how heater was malfunctioning type of gas used propane LP or natural gas purchase date Usually we will ask you to return the part to the factory PARTS NOT UNDER WARRANTY Contact au...

Page 27: ...cted on the wall thermostat and the log heater will automatically cycle from pilot to the heat setting selected WALL MOUNT ON OFF SWITCH GWMS2 Not Shown For remote ready models Allows the gas log heat...

Page 28: ...a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a d...

Reviews: