INSTALLATION AND CLEARANCES
FOR VENT-FREE OpERATION
WARNING: Maintain the
minimum clearances. If you
can, provide greater clearances
from floor, ceiling and adjoining
wall.
MINIMUM FIREpLACE CLEARANCE TO
COMBUSTIBLE MATERIALS
Log Size
Side Wall
Ceiling
4"
16"
4"
LOG SIzING REQUIREMENTS
Minimum Firebox Size
Log
Front
Rear
Size Height Depth Width Width*
4"
17"
14"
8"
1"
*Measured at 14" Depth
Carefully follow the instructions below. This will
ensure safe installation into a masonry, UL127-
listed manufactured fireplace or certified vent-free
firebox.
Minimum Clearances For Side
Combustible Material, Side Wall and
Ceiling
A. Clearances from the side of the fireplace
cabinet to any combustible material and wall
should follow diagram in Figure 4.
Example:
The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3
1
/
2
" from the wall. This combus
-
tible material must be 4" from the side of the
fireplace cabinet (see Figure 4).
Note:
When installing your gas logs into
a manufactured firebox, follow firebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the fireplace
opening to the ceiling should not be less than
42".
INSTALLATION
Continued
Figure 4 - Minimum Clearance for
Combustible to Wall
*Minimum 16" from Side Wall
*
Example
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney flue damper open.
If running heater with damper
open, noncombustible material
above fireplace opening is not
needed. Go to
Installing Damper
Clamp Accessory for Vented
Operation
, page 12.
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note:
If using a mantel, proceed to If Using
Mantel. If not using a mantel, follow the informa
-
tion below.
You must have noncombustible material(s) above
the fireplace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least 1/2
inch thick. With sheet metal, you must have non
-
combustible material behind it. Noncombustible
material must extend at least 8" up. If noncombus
-
tible material is less than 12", you must install the
fireplace hood accessory. See Figure 5, page 10,
at right for minimum clearances.
IMPORTANT:
If you cannot meet these minimum
clearances, you must operate heater with chimney
flue damper open. Go to
Installing Damper Clamp
Accessory for Vented Operation
, page 12.