  Pipe  Cap  Tee
 Nipple    Joint

Installation Items Needed

Before installing heater, make sure you have 

the items listed below.

•  external regulator (supplied by installer)
•  piping (check local codes)
•  sealant (resistant to propane/LP gas)
•  equipment shutoff valve *
•  test gauge connection *
•  sediment trap
•  tee joint
•  pipe wrench
•  approved  flexible  gas  line  with  gas  con

-

nector  (if  allowed  by  local  codes)  (not 
provided) 

* A  CSA  design-certified  equipment  shutoff 

valve with 1/8" NPT tap is an acceptable al-
ternative to test gauge connection. Purchase 

the optional CSA design-certified equipment 

shutoff valve from your dealer.

For  propane/LP  units,  the  installer  must 

supply  an  external  regulator.  The  external 
regulator will reduce incoming gas pressure. 
You must reduce incoming gas pressure to 
between 11" and 14" of water. If you do not re-

duce incoming gas pressure, heater regulator 

damage could occur. Install external regulator 
with the vent pointing down as shown in Figure 
13.  Pointing  the  vent  down  protects  it  from 

freezing rain or sleet.

  CAUTION:  Use  only  new, 

black  iron  or  steel  pipe.  In-

ternally-tinned copper tubing 

may be used in certain areas. 

Check  your  local  codes.  Use 

pipe of 1/2" diameter or greater 

to  allow  proper  gas  volume  to 

heater. If pipe is too small, undue 

loss of volume will occur.

Installation must include an equipment shutoff 

valve, union and plugged 1/8" NPT tap. Locate 

NPT tap within reach for test gauge hook up. 
NPT tap must be upstream from heater (see 
Figure 14).

IMPORTANT:

 Install equipment shutoff valve 

in  an  accessible  location.  The  equipment 
shutoff valve is for turning on or shutting off 
the gas to the appliance.

Propane/LP 
Supply Tank

External 
Regulator 
with Vent 
Pointing 
Down

Figure 13 - External Regulator With Vent 

Pointing Down

INSTALLATION

Continued

Check  your  building  codes  for  any  special 
requirements for locating equipment shutoff 

valve to fireplaces.

Apply pipe joint sealant lightly to male NPT 
threads. This will prevent excess sealant from 
going into pipe. Excess sealant in pipe could 
result in clogged heater valves.

  WARNING:  Use  pipe  joint 

sealant that is resistant to liquid 

petroleum (LP) gas. 

*  Purchase the optional CSA design-certified 

equipment shutoff valve from your dealer.

**Minimum inlet pressure for purpose of input 

adjustment. 

Figure 14 - Gas Connection (Remote-

Ready Models Only)

Gas 

Control 

3" Minimum

Sediment Trap

CSA Design-Certified 

Equipment Shutoff Valve 
With 1/8" NPT Tap*

Approved Flexible 

Gas Hose (if 

allowed by local 
codes)

pROpANE/Lp

 

From External 

Regulator

(11" W.C.** 

to 14" W.C. 

Pressure)

NATURAL

 

From Gas 

Meter

(5" W.C.** 

to 10.5" 

W.C. 

Pressure)

Summary of Contents for EC18NR

Page 1: ...your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be...

Page 2: ...eat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven tilation section on page 6...

Page 3: ...chemicals known to the state of California to cause cancer or birth defects or other reproductive harm IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble op erate or se...

Page 4: ...bstructions across openings of fireplace 8 To prevent the creation of soot follow the instructions in Cleaning and Maintenance page 27 9 Before using furniture polish wax carpet cleaner or similar pro...

Page 5: ...ady Models Only wall switch hand held ON OFF remote wall thermostat hand held thermostat remote See Accessories page 38 The wall thermostat or hand held thermostat may not be used where vented decorat...

Page 6: ...home energy efficient your home needs to breathe Fresh air must enter your home All fuel burning ap pliances need fresh air for proper combustion and ventilation Exhaust fans fireplaces clothes dryer...

Page 7: ...maximum Btu Hr the space can support 3 Add the Btu Hr of all fuel burning appliances in the space Vent free fireplace ___________ Btu Hr Gas water heater ___________ Btu Hr Gas furnace ___________ Bt...

Page 8: ...nnecting the two spaces see options 1 and 2 Figure 2 You can also remove door into adjoining room see option 3 Figure 2 Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Combustion and Ven...

Page 9: ...Important Vent free heaters add moisture to the air Although this is beneficial installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture See Air for C...

Page 10: ...e Wall Example Minimum Noncombustible Material Clearances If Not Using Mantel Note If using a mantel proceed to If Using Mantel If not using a mantel follow these instructions You must have noncombust...

Page 11: ...nderside of Mantel Hood GA6050 GA6052 or GA6053 Top of Fireplace Opening Underside of Mantel Shelf Mantel Shelf Hearth 5 Min Combustible Material Figure 9 Minimum Fireplace Clearances Above Combustibl...

Page 12: ...ure 10 The damper clamp will keep damper open Installation instructions are included with clamp accessory See chart below for minimum permanent flue opening you must provide Attach damper clamp so th...

Page 13: ...n mortar joint of bricks 4 Remove heater base from fireplace 5 Drill holes at marked locations using 3 16 drill bit 6 Attach base through holes in front panel of base to fireplace floor using masonry...

Page 14: ...ameter or greater to allow proper gas volume to heater Ifpipeistoosmall undue loss of volume will occur Installation must include an equipment shutoff valve union and plugged 1 8 NPT tap Locate NPT ta...

Page 15: ...lve control valve and equip ment shutoff valve from gas supply piping system Pressures in excess of 1 2 psig will damage heater regulator 2 Cap off open end of gas pipe where equip ment shutoff valve...

Page 16: ...in center of log see Figure 18 2 VCG and EC Models Snap switch as sembly into place 3 Attach wires to control valve as shown in Figure 19 Gas Meter Figure 17 Checking Gas Joints Natural Gas Only Cont...

Page 17: ...Bracket Electronic Ignitor On Base Assembly Push Button Clips Pads 9 Volt Battery Battery Clip Terminal Wires Switch Control Valve 11 If logs were removed from heater for install remote accessory repl...

Page 18: ...s Only use logs supplied with heater 1 Place rear log 1 on base assembly as shown in Figure 23 Log will fit over right end of burner and rest in middle of U burner 2 Place middle log 2 in front of U b...

Page 19: ...Separate pieces of ember material and place on surface of flat burner just behind horizontal ports as shown in Figure 27 Ceramat Ember placement Add embers to front flat burner Gently remove embers f...

Page 20: ...re 30 Installing Log 7 7 9 Add lava rock and small decorative logs around base of heater if desired DO NOT place rock or additional logs on front burner or on logs Placing any material on unit other t...

Page 21: ...arts page 32 4 Figure 34 Installing Log 4 5 Figure 35 Installing Log 5 6 7 Figure 36 Installing Logs 6 and 7 Installation Continued 8 Figure 37 Installing Log 8 Rib 2 Place left bottom log 2 onto base...

Page 22: ...t ports and 2 pieces to back ports Additional glowing effect can be achieved by fraying edges of ember material WARNING Do not operate unit without ember material cor rectly in place as shown in Fig u...

Page 23: ...stem and any gas control which has been under water LIGHTING INSTRUCTIONS WARNING If fireplace has glass doors never operate this heater with glass doors closed If you op erateheaterwithdoorsclosed he...

Page 24: ...Note You may be running this heater for the first time after hooking up to gas supply If so the control knob may need to be pressed in for 30 seconds or more This will allow air to bleed from the gas...

Page 25: ...n now turn burner on and off with hand held remote control unit IMPORTANT Do not leave selector switch in the REMOTE or ON position when pilot is not lit This will drain the battery On Off Series Mode...

Page 26: ...y receives sig nals from the hand held remote to control the room temperature If the hand held remote is misplaced obstructed or for any reason cannot transmit to the receiver the receiver will shut o...

Page 27: ...holder for dust and dirt see Figure 47 3 Blow air through the ports slots and holes in the burner 4 Check injector holder located at end of burner tube again Remove any large particles of dust dirt li...

Page 28: ...gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Overlap ember material 1 4 see page 19 1 Reconnect ignitor cable...

Page 29: ...d in 30 seconds 3 Wait one minute for safety interlock system to reset Repeat ignition operation 4 Fully open equipment shut off valve 5 A Contact local natural or propane LP gas company B Clean ODS p...

Page 30: ...te burners until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum installa tion clearances see pages 9 through 11 4 Clean burners see Clean i...

Page 31: ...d 1 Gas leak See Warning statement at top of page 2 Control valve or gas control defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at top of page 1 Hand held...

Page 32: ...iable Control Models VGC18 N P R VGC24 N P R VGC30 N P R EC18 N P R EC24 N P R EC30 N P R VCC18 N P R VCC24 N P R and VCC30 N P R 29 1 30 27 35 30 34 23 29 3 2 29 4 5 10 11 23 21 22 20 14 13 16 15 17...

Page 33: ...18582 02CK 18 ASM Pan Burner 1 120259 01CK 24 30 ASM Pan Burner 1 13 119218 01 Burner Inlet Tube 1 14 111819 07 Elbow Orifice Front 1 111819 11 Elbow Orifice Front 1 111819 10 Elbow Orifice Front 1 15...

Page 34: ...Models VGC18 N P R VGC24 N P R VGC30 N P R EC18 N P R EC24 N P R AND EC30 N P R This list contains replaceable parts used in your heater When ordering parts follow the instructions listed under Replac...

Page 35: ...1 9 121079 01 121079 01 121079 01 Switch Log 1 Parts Log Sets for Models VCC18 N P R VCC24 N P R and VCC30 N P R This list contains replaceable parts used in your heater When ordering parts follow the...

Page 36: ...let Gas Pressure in of water Max 14 W C Min 11 W C For purpose of input adjustment VGC EC VCC 24NR Rating Variable 28 000 39 000 Btu Hr Type Gas Natural Ignition Electronic Manifold Pressure 3 4 W C I...

Page 37: ...acement part s call DESA Heating LLC at 1 866 672 6040 for referral information A list of authorized dealers can be found by visiting www desatech com When calling DESA Heating LLC have ready model an...

Page 38: ...MT1 For all models The desired comfort setting can be selected on the wall thermostat and the log heater will automatically cycle from pilot to the heat setting selected WALL MOUNT ON OFF SWITCH GWMS2...

Page 39: ...___________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 40: ...proved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use origin...

Reviews: