Clock Box PRO Installation and Operations Manual V1.1
LAB-110218
31
Monitoring System
Receiving a signal from the building monitoring system or alarm system
The Clock Box PRO provides a connection that allows a building monitoring system or alarm system to send a
signal to the Clock Box PRO to power down the range.
In the Clock Box PRO control box, there is a six-position plug for the monitoring system. The last three wires
are black, white, and green/yellow. The black and white wires control a relay coil that is powered by the signal sent
from the building monitoring system or alarm system. The optional relay voltages (sent with the Clock Box PRO) are
120 VAC, 24 VDC, and 12 VDC. Define the needed voltage and install the relay accordingly (See below). If an
additional voltage is required, please contact Denlar Service.
To connect the wires, the black is the Hot or positive, the white is the neutral, and the green/yellow is for
ground. The installer
’
s connector is a push-to-connect for solid or terminated ferruled wires.
To select the relay, there is a bag with three (3x) different relays in it. The coil voltage for the relays are
marked on the top of the relay. Identify the correct relay required.
Insert the relay into the K4 relay socket. To do this, press the Relay Retaining Clip down. Insert the required K4
Relay into the K4 Relay Socket. Press the top of the Relay down to engage the K4 Relay
.
Summary of Contents for ClockBox Pro
Page 1: ...Clock Box PRO Installation and Operations Manual V1 1...
Page 10: ...Clock Box PRO Installation and Operations Manual V1 1 LAB 110218 10 Device Flow Chart...
Page 27: ...Clock Box PRO Installation and Operations Manual V1 1 LAB 110218 27...
Page 34: ...Clock Box PRO Installation and Operations Manual V1 1 LAB 110218 34 Clock Box PRO Schematic...
Page 35: ...Clock Box PRO Installation and Operations Manual V1 1 LAB 110218 35 Clock Box PRO Datasheet...
Page 36: ...Clock Box PRO Installation and Operations Manual V1 1 LAB 110218 36 Gas Disconnect Datasheet...