DAEnetIP4
SNMP Five Channel Relay Module
- User's Manual
08 Aug 2017
-10-
5. Installation
5.1.
Connect
This device must be installed by qualified personnel;
This device must not be installed directly outdoors;
Installation consists of mounting the device, connecting to an IP network,
connecting the I/O, providing power and configuring via a web browser.
5.2.
Power supply requirements
Figure 9.
Location of
DAEnetIP4 Five Relay Module
power jack
The whole module has the following current consumption:
140mA
at 24V DC (and all relays are ON)
210mA
at 12V DC (and all relays are ON)
It is recommended the supply source for
DAEnetIP4 Five Relay Module
to be
with the following parameters:
Supply voltage: 12V or 24V DC (depending on the selected model);
Current: minimum 210mA;
It must be stabilized and filtered;