37
Low
Mid
High
The maximum operating speed of the ventilation equipment linked to UNOnext
will be limited by the hardware DIP SWITCH on UNOnext; see the UNOnext
installation manual.
Filter status
See Table 8.
Filter reset
After the device filter is replaced, you can click to reset the filter life.
Note: It is recommended that the filters of all connected devices of a single
UNOnext be replaced at the same time.
Central Lock
status
Shows whether Central Lock is enabled
Enabled
Deactivated
When the Central Lock is enabled, UNOnext cannot accept physical button or app
commands.
The control items have AutoMode: Turbo, Smart, ManualMode: 6 buttons for low,
mid, and high speeds, and off. See the description in Table 17 for details.
Table 17
Descriptions of UNOnext Control Panel control items
Options
Description
AutoMode
Set UNOnext to AutoMode, and there will be two modes to choose from: Turbo
and Smart.
Turbo: If any sensor value exceeds the limit, it will run at full speed. The display
mode is (N) Turbo.
Smart: The wind speed is dynamically adjusted according to the value and
thresholds. The display mode is (N) Smart.
ManualMode
There are three speeds to choose from: low, mid, and high. The display mode is
(C) Manual.
But the actual upper speed limit will be determined by the hardware DIP SWITCH
on UNOnext.
Off
Turn off the ventilation equipment.
To-All
Check this option, the [AutoMode], [ManualMode], and [Off] command will be
sent to all UNOnext.
Note: When the control plan is enabled, control here will only be effective for 1 hour.