Delta Terminal Panels Series Instruction Sheet Download Page 1

http://www.delta.com.tw/industrialautomation/

                             

 

2006-0 7-18

5011617503-2 GE3

       

 

 

TP02G-AS1 

Terminal Panels Series 

Instruction Sheet 

 

1  

WARNING 

Please read this manual thoroughly before using the TP02G. 

DANGER! DC input power must be OFF before any maintenance. Do not connect or remove wires and 

connectors while power up to the circuit. Only qualified technicians are allowed to do the maintenance. 

The display panel of the TP02G is waterproof. But please keep away grease, corrosive liquids or sharp 

objects from contacting the TP02G. 

DANGER! The TP02G requires 24VDC input power. The 24VDC input power should not be connected to 

the RS-485 communication port.    The unit may be destroyed and can’t be repaired if the input power is 

improperly applied. Please confirm the input power wiring is correct before power up.   

DANGER! An electrical charge will remain on the DC-link capacitors for 1 minute after power has been 

removed.    This residual power may be hazardous and the TP02G should not be worked on until this 

charge has dissipated. To prevent personal injury, do not conduct any wiring or investigation on the TP02G 

until 1 minute after power off. Do not touch any terminals while power is applied to the TP02. 

CAUTION! Always ground the TP02G using the grounding terminal.    This will not only act as a safety, but 

also help filter electrical noise.    The grounding method must comply with the laws of the country where the 

unit is to be installed. 

CAUTION! If you turn the fixed support that is packaged together with TP02G too tight, TP02G may be 

damaged.  

2  

INTRODUCTION 

2.1 Model 

Explanation

 

 

Nameplate 

MODEL :

POWER INPUT : 

TP02GAS1W6050004

VX.XX

TP02G-AS1

24Vdc  3W

DELTA ELECTRONICS, INC                                   MADE IN XXXXXXX

Production model

Power input spec.

Barcode and 
serial number

Version

 

Note: The words of “MADE IN XXXXX” will be different due to the manufacturing location. 

 

Model Explanation

 

 

Serial Number Explanation

 

TP 02 G

AS 1

  

    -  

  

Reserved
Reserved

T:  Text mode
G: Graphic mode

LCD Spec.

Series name

 

TP02GAS 1 W 6 05 0004

      

     

  

Production serial number

Production weeks

Production year(2006)

Production plant(W:Wuijang)

Version

Production model

 

2.2 Outline

 

LCM
Display Area

RS-232 Indication LED

RS-485 Indication LED

Escape/Exit

Alarm Indication LED

Function  Keys

Arrow Keys

Enter Key

 

Back Panel 

RS-232

Extension port

 

5-PIN terminals: Wire gauge: 12-24 AWG / Torque: 4.5 lb.-inch

 

2.3 Dimensions 

 

Front Panel 

 

Unit: mm[inch] 

 

Right Side Diagram 

 

Unit: mm[inch]

 

 

Back side 

 

 

Vertical View 

 

Unit: mm[inch]

 

 

Mounting Panel Dimension 

Thickness Range 0.5~9mm

135~136.5[5.31~5.37]

85

[3.35]

 

Unit: mm[inch]

 

Installation Method

 

One easy way is insert TP02G to the opening hole of panel and tight up the screws. However, if a firm mounting 

TP02G to the panel is needed, please use the fixed support accessory which is packed together with TP02G, then 

infix the fixed support in the back and tight up the screws.   

  If you turn the screw exceeds torque: 4-5(kg-cm), TP02G may be damaged. 

(Note

the flat surface should be a Type 4 “Indoor Use Only” enclosure or equivalent.) 

Please leave sufficient space (more than 50mm) around the unit for heat dissipation. 

Thickness:
0.5~9.0mm

 

 

 

Panel Function Explanation 

Panel Component

 

Explanation 

Alarm Indication LED 

Status 1: When power is on, the LED will blink slowly for three times.   

Status 2: When there is an abnormal situation, the LED will blink quickly along with 

an alarm sound.   

RS-232 Indication LED 

(Yellow) 

Will blink when transmitting program and communicating by using RS-232. 

RS-485 Indication LED 

(Green) 

Will blink when communicating by using RS-485. 

Esc (Escape/Exit) 

Used to cancel an incorrect input, or to Exit a programming step.   

Arrow Keys 

UP/Pg Up: Used to increase the value or move screen up one page. 

Pg Dn/DOWN: Used to decrease the value or move screen down one page.   

Left: Left direction key. (move curser to left) 

Right: Right direction key. (move cursor to right)   

Enter key 

Used to input a value or accept a programming instruction. 

Function Keys

 

F0/0: used as a constant 0, or user can define it as function F0. 

F1/1: used as a constant 1, or user can define it as function F1. 

F2/2: used as a constant 2, or user can define it as function F2. 

F3/3: used as a constant 3, or user can define it as function F3. 

F4/4: used as a constant 4, or user can define it as function F4. 

F5/5: used as a constant 5, or user can define it as function F5. 

F6/6: used as a constant 6, or user can define it as function F6. 

F7/7: used as a constant 7, or user can define it as function F7. 

F8/8: used as a constant 8, or user can define it as function F8. 

F9/9: used as a constant 9, or user can define it as function F9. 

 

3

SPECIFICATION 

Electrical Specification   

Item 

TP02G-AS1 

Function Key / Digital Key 

F0/0~F9/9, ESC, ENTER and ARROW keys   

External Input Power 

24V (3W Max.) 

Memory Capacity 

256K Byte 

CPU 

Hitachi HD64F3064F 

RAM of System 

32K Byte 

Communication Interface 

Com1: RS-232 and Com2: RS-485 

Waterproof Class of Front Panel 

IP65/NEMA4 

Environment Condition 

0~50

, relative humidity 20-90% RH

non-condensing

 

Storage Temperature of Hardware 

-20~60 

°

Reviews: