Installation and Operation Manual for RPI M50A
8 Settings
69
Installation and Operation Manual for RPI M50A
8.11 Max. Power (Maximum feed-in power)
Overview
This function should be set only when requested by country regulations, authorities or your grid
operator.
With this function you can limit the maximum active power to be fed into the grid.
Accessing the menu
Main menu > Install Settings > Max. Power
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1.
When the default information is displayed, press any button to open the
main menu. Otherwise, repeatedly press the button
ESC
until the main
menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the buttons
and
to select
Install Settings
.
To confi rm your selection, press the button
ENT
.
3.
The menu is protected by password 5555. Use the buttons
and
to set each digit.
To confi rm a digit, press the button
ENT
.
AC Connection: 3P4W
EPO: Normal Close
Anti-islanding: ON
Max. Power: 50000VA
Return to Factory
4.
Use the buttons
and
to select
Max. Power
. The current setting
is displayed behind the menu entry.
5.
To start editing the parameter value, press the button
ENT
.
6.
To change the parameter value, use the buttons
and
.
To confi rm your selection, press the button
ENT
.
To cancel the action, press the button
ESC
.
Confi gurable Parameters
Parameter
Description
Value range
Max. Power
Limits the maximum power to be fed into the grid.
0 .. 55000 VA
Default: according to the coun-
try regulations