8 Settings
Installation and Operation Manual for RPI M50A
58
Installation and Operation Manual for RPI M50A
58
8.6 Inverter ID
Overview
With this function you can set an ID for the inverter. The inverter ID is used to identify the inverter in a RS485
connection. The inverter ID is also used in monitoring systems.
►
Set a different inverter ID for each inverter in the PV plant. Otherwise, the inverters cannot be
correctly identifi ed.
►
On the last inverter in the RS485 connection, switch on the RS485 termination resistor. For a
description, see
“6.7 Connecting communication port I (optional)”, p. 45
.
Accessing the menu
Main menu > Install Settings > Inverter ID
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1.
When the default information is displayed, press any button to open the
main menu. Otherwise, repeatedly press the button
ESC
until the main
menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the buttons
and
to select
Install Settings
.
To confi rm your selection, press the button
ENT
.
3.
The menu is protected by password 5555. Use the buttons
and
to set each digit.
To confi rm a digit, press the button
ENT
.
Grid Settings
Country
Insulation
Inverter ID: 001
4.
Use the buttons
and
to select
Inverter ID
. The currently set
inverter ID is displayed behind the menu entry.
To confi rm your selection, press the button
ENT
.
ID=001
Setting ID:
5.
Use the buttons
and
to set the inverter ID.
To confi rm your setting, press the button
ENT
.
Confi gurable Parameters
Parameter
Description
Value range
Setting ID
Sets the inverter ID that is needed
to identify the inverter when a PV
plant contains multiple inverters.
001 .. 254