8 Settings
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
84
8.4.2 Insulation
These parameters are set according to the
requirements of the selected country. Changing
these parameter settings can invalidate the type
approval of the unit. Change this setting only after
consultation with Delta customer service.
Overview
This function allows you to set the insulation mode and insulation resistance.
Setting options
Parameter
Description
Setting range
Mode
The insulation mode.
ON
Plus grounding
Minus grounding
OFF
Resistance
Insulation resistance
150 kΩ | 250 kΩ | 1100 kΩ
Menu item path
Main Menu > Install Settings > Insulation
Calling up the menu
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1.
If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Install Settings
entry.
and then press the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
This function is protected with password 5555.
Use the
and
buttons to set the individual numerals.
Press the
ENT
button to confirm a number.
Grid Settings
Country
Insulation
Inverter ID: 001
4.
Use the
and
buttons to select the
Insulation
entry and then press the
ENT
button.
Resistance: 1100 kΩ
Mode: ON
5.
Use the
and
buttons to select the
Mode
entry and then press the
ENT
button.
The currently set value is displayed after the entry.
Plus grounded
Minus grounded
OFF
ON
6.
Use the
and
buttons to select a mode and then press the
ENT
button.