PMT Panel Mount Power Supply 

4.2V 252W 1 Phase / PMT-4V350W1A

□ 

 

TECHNICAL DATASHEET

 

 

 

  

All parameters are specified at 25°C ambient unless otherwise indicated.

 

  

www.DeltaPSU.com (October 2014, Rev. 02)

  

 

3

 

Environment 

 

Surrounding Air Temperature

 

Operating  -20°C to +70°C

 

 

Storage  -40°C to +85°C

 

Power De-rating

 

  >

 50

°C de-rate power by 4% / °C, 

> 60°C de-rate power by 1% / °C 
< 100Vac de-rate power by 3% / V, 

< 200Vac de-rate power by 1.5% / V 

Operating Humidity

 

  5 to 95% RH (Non-Condensing)

 

Operating Altitude

 

  0 to 5,000 Meters

 

Shock Test (Non-Operating)

 

  IEC 60068-2-27, Half Sine: 50G for a duration of 11ms, 

3 times per direction,18 times in total

 

Vibration 

Operating 

IEC 60068-2-6, Sine Wave: 10Hz to 150Hz @ 25m/S² 

(2.5G peak); 90 min per axis for all X, Y, Z direction 

 

Non-Operating 

IEC 60068-2-6, Random: 5Hz to 500Hz @ 2.09Grms 

peak; 20 min per axis for all X, Y, Z direction 

Pollution Degree 

  2 

 

 

Protections 

 

Overvoltage

 

< 4.83

~

7.00V, SELV Output, Latch Mode

 

Overload / Overcurrent

 

> 105~135% of rated load current, Hiccup Mode,  

Non-Latching (Auto-Recovery) 

Over Temperature

 

Hiccup Mode, Non-Latching 

(Auto-Recovery when the fault is removed) 

Short Circuit

 

Hiccup Mode, Non-Latching 

(Auto-Recovery when the fault is removed)

 

Protection Against Shock

 

Class I with PE* connection

 

*PE: Primary Earth 

 

 

Reliability Data 

 

MTBF 

> 700,000 hrs. as per Telcordia SR-332 

I/P: 100Vac, O/P: 100% load, Ta: 35°C

 

Expected Cap Life Time

 

 

10 years (115Vac & 230Vac, 50% load @ 40°C)

 

 

 

Safety Standards / Directives 

 

Electrical Safety

 

  UL/cUL recognized to UL 60950-1 and CSA C22.2 

No. 60950-1, CB scheme to IEC 60950-1

 

Material and Parts

 

  RoHS Directive 2011/65/EU Compliant

 

Galvanic Isolation

 

Input to Output  3.0KVac

 

 

Input to Ground  1.5KVac

 

 

Output to Ground  0.5KVac

 

 

 

 

 

 

 

Summary of Contents for PMT-4V350W1A Series

Page 1: ...nominal output voltage of 4 2V with a wide operating temperature range from 20 C to 70 C and can withstand shock and vibration in accordance to IEC 60068 2 27 and IEC 60068 2 6 respectively In addition to features like overvoltage and overload protections Delta s PMT series of panel mount power supplies is unlike many other brands in the same price level The PMT series is designed for cost competi...

Page 2: ...gs Characteristics Nominal Output Voltage 4 2Vdc Output Voltage Tolerance 3 initial set point tolerance from factory Output Voltage Adjustment Range 3 78 4 70Vdc Output Current 60 0A Output Power 252W Line Regulation 0 5 typ Load Regulation 2 5 typ PARD 20MHz 150mVpp Rise Time 50ms nominal input 100 load Start up Time 1000ms nominal input 100 load Hold up Time 16ms 115Vac 20ms 230Vac Dynamic Respo...

Page 3: ... Operating IEC 60068 2 6 Random 5Hz to 500Hz 2 09Grms peak 20 min per axis for all X Y Z direction Pollution Degree 2 Protections Overvoltage 4 83 7 00V SELV Output Latch Mode Overload Overcurrent 105 135 of rated load current Hiccup Mode Non Latching Auto Recovery Over Temperature Hiccup Mode Non Latching Auto Recovery when the fault is removed Short Circuit Hiccup Mode Non Latching Auto Recovery...

Page 4: ...l Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A 1 2kV Surge IEC 61000 4 5 Level 3 Criteria A 1 Common Mode 2 2kV Differential Mode 3 1kV Conducted IEC 61000 4 6 Level 3 Criteria A 1 150kHz 80MHz 10Vrms Power Frequency Magnetic Fields IEC 61000 4 8 Criteria A 1 10A Meter Voltage Dips IEC 61000 4 11 100 dip 1 cycle 20ms Self Recoverable Low Energy Pulse Test Ring Wave IEC 61000 4 12 Level 3 ...

Page 5: ...ecified at 25 C ambient unless otherwise indicated www DeltaPSU com October 2014 Rev 02 5 Block Diagram Device Description 1 Input Output terminal block connector 2 DC voltage adjustment potentiometer 3 DC OK control LED Green 4 AC selectable switch PMT 4V350W1AM Terminal Block PMT 4V350W1AN Front Face ...

Page 6: ... 4 2V 252W 1 Phase PMT 4V350W1A TECHNICAL DATASHEET All parameters are specified at 25 C ambient unless otherwise indicated www DeltaPSU com October 2014 Rev 02 6 Dimensions L x W x D 215 x 115 x 50 mm PMT 4V350W1AM Terminal Block ...

Page 7: ... Supply 4 2V 252W 1 Phase PMT 4V350W1A TECHNICAL DATASHEET All parameters are specified at 25 C ambient unless otherwise indicated www DeltaPSU com October 2014 Rev 02 7 L x W x D 215 x 115 x 50 mm PMT 4V350W1AN Front Face ...

Page 8: ...tage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition 3 To ensure sufficient convection cooling always maintain a distance of 20mm from fan ventilated surfaces while the device is in operation 4 Depending on the surrounding air temperature and output load delivered by the p...

Page 9: ...ientations Use flexible cable stranded or solid of AWG No 14 12 The input output connectors allowable current is 23A max per pin User should calculate and select the suitable wire specification type quantity diameter according to actual output current The torque at the connector shall not exceed 13Kgf cm The insulation stripping length should not exceed 0 275 or 7mm Recommended mounting torque of ...

Page 10: ...y Do not touch the device while it is in operation or immediately after power is turned OFF Risk of burning Do not touch the terminals while power is being supplied Risk of electric shock Prevent any foreign metal particles or conductors from entering the device through the openings during installation It may cause electric shock safety hazard fire and or product failure Warning When connecting th...

Page 11: ...in period of time The time required for the output to reach 95 of its set value after the input voltage is removed Graph illustrating the Start up Time Rise Time and Hold up Time Inrush Current Inrush current is the peak instantaneous input current measured and occurs when the input voltage is first applied For AC input voltages the maximum peak value of inrush current will occur during the first ...

Page 12: ... OLP OCP section on this page The power supply will return to normal operation after the short circuit is removed Overvoltage Protection The power supply s overvoltage circuit will be activated when its internal feedback circuit fails The output voltage shall not exceed its specifications defined on Page 3 under Protections Over Temperature Protection As mentioned above the power supply also has O...

Reviews: