5.11.7.3. Install Settings
Correct passwords are requested when entering Install Settings. Install Settings for
user and installation technician are different. The password cannot be revised. After
confirmation as the general user password, user can set Inverter ID, and Insulation.
CAUTION!
C
AUTIONS APPEAR BEFORE THE TEXT IT REFERENCES
.
CAUTIONS APPEAR IN CAPITAL LETTERS
TO EMPHASIZE THAT THE MESSAGE CONTAINS VITAL HEALTH AND SAFETY INFORMATION
.
Insulation
Inverter will measure the impedance between Array and PE before connect to grid. If
the impedance between Array and PE is lower than the value that set in Insulation
Settings, inverter will stop connecting to grid. There are 4 modes users can select in
Insulation settings: ON, Positive Ground, Negative Ground, or Disable. Installer can
also select different impedance according to the actual situation.
Figure 5-38. Install Setting Page -User Mode
Figure 5-39. Insulation Setting
After confirmation as the installation technician passwords, system will add setting
options of DC-Injection, Return to Factory, Country and Grid Setting. In Grid Setting
selection, technician can adjust the parameter for protection (OVR, UVR, OFR, UFR,
etc.) to Utility. Before setting of the protection to Utility in Grid Settings page, please
Password
21. Jun 2010 13:50
*
ENT
ENT
EXIT
Install Settings
21. Jun 2010 13:50
Inverter ID
Insulation
RCMU
Country
Germany MV
[ 001 ]
[ --- ]
Grid Settings
[
]
Reconnection Time [
]
60 s
Ramp-up Power
20
%/m
ENT
EXIT
Install Settings
21. Jun 2010 13:50
Inverter ID
Insulation
RCMU
Country
Germany MV
[ 001 ]
[ --- ]
Grid Settings
[
]
Reconnection Time [
]
60 s
Ramp-up Power
20
%/m
Insulation
21. Jun 2010 13:50
Mode
Resistance
ON
1200
[
[
]
] kohm
Summary of Contents for PhotoVoltaic RPI-C500
Page 1: ...PhotoVoltaic Inverter RPI C500 PV Inverter ...
Page 88: ...INSTALLATION GUIDE 82 ...
Page 89: ...光伏逆变器 RPI C500 光伏逆变器 ...
Page 100: ...安装手册 5 产品外观 外部三角视图 3 2 2 外部三角视图 图 3 2 外部后视图 进气孔 ...
Page 114: ...安装手册 20 安装说明 DC 端连接 图 5 4 DC 端连接端尺寸图 ...
Page 116: ...安装手册 22 安装说明 AC 端连接 5 3 AC 端连接 1 如图 5 6 所示将连接到 AC 端的电缆穿过底板 图 5 6 AC 端配线 ...
Page 119: ...安装手册 25 安装说明 AC 端连接 图 5 9 AC 端连接端尺寸图 ...
Page 156: ...安装手册 62 维修保养 更换风扇模块 7 维修保养 7 1 更换风扇模块 1 按拉且扭转把手 之后打开后门 图 7 1 按拉扭转把手 ...
Page 158: ...安装手册 64 维修保养 更换风扇模块 4 松开锁附在上风扇与机壳上的螺丝 然后将上风扇移除 图 7 4 松开上风扇的螺丝 ...
Page 160: ...安装手册 66 维修保养 更换进气口滤网 3 松开锁附在滤网上的螺丝 图 7 7 松开滤网的螺丝 4 取出滤网 图 7 8 取出滤网 ...
Page 162: ...安装手册 68 维修保养 清理排气孔滤网 4 直接取出挡板和排气孔滤网 图 7 11 取出排气孔滤网 ...
Page 165: ...安装手册 71 维修保养 更换 SURGE PROTECTION DEVICE 4 退出已损坏的 SPD 并更换新的 Figure 7 15 退出已损坏的 SPD ...
Page 176: ...Version 01180521 5013209808 ...