General information
The section describes the general technical characteristics of
the AC and DC terminal blocks. The special features which
apply to the installation of the inverter are explained in the fol-
lowing sections.
AC and DC terminal blocks are of the same type.
The specifications in this section have been
defined by Phoenix Contact. Check if the techni-
cal specifications have changed before starting
installation work; see www.phoenixcontact.com.
NOTICE
Danger of a cable fire.
Bending and twisting causes damage to the
inner structure of the conductor, which leads to
punctiform increase in electrical resistance. This
can result in an overheating of the conductor
and destruction of the insulation.
► When bending and twisting cables or
conductors, always comply with the
manufacturer’s instructions.
AC and DC terminal block specifications
Naming
Phoenix Contact UKH 150
Connection type
Screws with hexagon socket head
Screw thread
M10
Rated current I
N
309 A
Rated voltage U
N
1000 V
Attaching the conductor
Type of attachment
M10 screws with hexagon socket
head
Tightening torque
25 ... 30 Nm
Specification for copper cable
Min./max. Wire cross-section
Without wire end sleeve
● Rigid cable
35 ... 150 mm
2
● Flexible cable
50 ... 150 mm
2
with wire end sleeve
● Flexible cable (wire end sleeve
without plastic sleeve)
50 ... 150 mm
2
● Flexible cable (wire end sleeve with
plastic sleeve)
50 ... 150 mm
2
Stripping length
40 mm
Specification for aluminum cable
SE
SM-S
SM-L
RE
RM-S
RM-L
SE
s
ector-shaped,
s
olid conductor
SM-S
s
ector-shaped,
m
ulti-conductor, rigid wires
SM-L
s
ector-shaped,
m
ulti-conductor, (stranded wires)
RE
r
ound,
s
olid conductor
RM-S
r
ound,
m
ulti-conductor, rigid wires
RM-L
r
ound,
m
ulti-conductor, (stranded wires)
The terminals have been specially developed for direct connec-
tion of sector-shaped, solid (SE) aluminum cables:
Min./max. Conductor cross-section
120 / 150 mm
2
Stripping length
40 mm
SE
90°
If other types of aluminum cables are to be used, Al-Cu com-
pression joints (e.g. fromKlauke, Elpress or Mecatraction) must
be used; see „Special instructions for the use of aluminum
Quick installation guide for solar inverter M88H RPI883M121300 RPI883M122300 EU V1 EN 5017414200_00 2019-11-07
18
AC and DC cable requirements
M88H_121 (ST) – AC and DC terminal blocks