141
Installation and Operation Manual for Solar Power Inverter M70A EU V2.0 EN 2020-08-03
10 Maintenance
Replacing the AC surge protection devices
10.10 Replacing the AC surge protection devices
DANGER
Electric shock
Potentially fatal voltages are present in the
inverter during operation. When the inverter
is disconnected from all power sources, this
voltage remains in the inverter for up to 60
seconds.
►
Perform the instructions listed in “10.4 Mak-
ing preparations for maintenance work - dis-
connecting the inverter from the grid (AC)
and solar modules (DC)”, page 115
before
you start work on the inverter!
Type 2 AC surge protection devices are installed
as standard. Type 1+2 combined AC surge pro-
tection devices can be ordered as accessories.
∫
The screws are very small and can easily fall
down. You should therefore use a magnetic
screwdriver.
1. Unscrew and remove the cover of the type 2 AC surge
protection devices.