Delta HEX100PC Series Instruction Manual Download Page 1

HEX100PC series

Dimension drawing

Features

Unit

    

 IP55 waterproof at external side

    

 "One touch" dry run test and dust cleaning

    

 Standalone temperature control

W/K (W/

)

    

 Clear LED status indicator

VDC

    

 Dry contact alarm output

A

W

Design

VDC

    

 Air to air heat exchange

°C

    

 Rated voltage at 48V

dB-A

    

 Reduntant fan quantity design

Kg (Lb)

    

 High efficiency and reliable fan

    

 Easy installation and maintenance

Dimension (H x W x D)

mm

(inch)

690 x 360 x 242

(27 x 14 x 10)

* Specifications are subject to change without notice.

* Note : The cooling capacity (W/K , W/°C or W/

) is defined as  Q/ (TI-TA)

              Q : Heat dissipation (W) from inside of cabinet

Opearting power

Operating voltage range

Operating temperature range

-10 ~ +65

              TI : Return temperature of internal air circuit (K , °C or 

)

82

173

1.7

Weight

13 (29)

External door mount

              TA : Ambient temperature of external air circuit (K , °C or 

)

Main feature

Cooling capacity

*Note

Specification

3.6

40 ~ 60

Noise (1.5 meter)

65.0

70.0

Rated voltage

70 (39)

90 (50)

48

Operating current

Summary of Contents for HEX100PC Series

Page 1: ...ntenance Dimension H x W x D mm inch 690 x 360 x 242 27 x 14 x 10 Specifications are subject to change without notice Note The cooling capacity W K W C or W is defined as Q TI TA Q Heat dissipation W from inside of cabinet Opearting power Operating voltage range Operating temperature range 10 65 TI Return temperature of internal air circuit K C or 82 173 1 7 Weight 13 29 External door mount TA Amb...

Page 2: ...HEX100PC Heat Exchanger Instruction Manual ...

Page 3: ...4 Electrical specification 3 4 1 Connection and LED indicator on HEX panel 3 4 2 Standalone control mode 5 5 Mechanical feature 6 5 1 Thermal path and Airflow baffle 6 5 2 Configuration 6 6 Maintenance and Replacement 7 6 1 Maintenance 7 6 2 Replacement 8 7 MTBF and Reliability 8 7 1 MTBF 8 7 2 Relibability 8 8 Safety 9 9 Accessory 9 9 1 Power cable 9 9 2 Function cable 9 10 General Safety and War...

Page 4: ...nal air loop conforms to IP55 protection rating 2 2 Specification Main feature Unit Model Number HEX100PC Outline Dimension H x W x D mm in 690 x 360 x 242 27 x 14 x 10 Cooling Capacity Note 1 W K W 70 39 90 50 Rated Voltage VDC 48 Rated Current Note 2 A 4 2 Operating Voltage Range VDC 40 60 Operating Current A 1 7 3 6 Operating Power Consumption W 82 173 Acoustic Noise at 1 5M SPL dB A 65 0 70 0 ...

Page 5: ...4 F 149 F Storage temperature 40 C 70 C 40 F 158 F Humidity External air circuit 0 100 RH Internal air circuit 0 90 RH Ingress protection on external side l IEC60529 IP55 NEMA 3 GR 487 720hrs salt spray 3 Installation 3 1 Outline drawing 1 Material Aluminum sheet t 1 5mm 2 Finish Power paint Color RAL7032 3 Dimensional tolerance 1mm 0 04 ...

Page 6: ...tout and waterproof foam sticking 4 Electrical specification 4 1 Connection and LED indicator on HEX panel Power Connection on panel plate CVILUX 3W3CS0000100000 mate with CVILUX 3W3CP0000100000 COMM connection on panel plate CVILUX CD5115PA100 mate with CVILUX CD5115SA100 ...

Page 7: ... Dry contact max rating 75VDC 50mA LED indicator INNER FAN OUTER FAN STATUS LEDs indicate fan and NTC sensor status Depress TEST button to start auto test of outer and inner fans running from low to high speed Turn off by depressing the TEST button again INNER FAN OUTER FAN STATUS Normal GREEN GREEN GREEN Failed RED RED RED Normal touch TEST CLEAN Blinking GREEN Blinking GREEN N A Failed touch TES...

Page 8: ...port Pin7 Pin8 via J13 connector on controller as shown below to change sensor location 4 2 Standalone control mode HEX can detect ambient temperature to control cooling capacity Internal fan and external fan speed default settings are shown below Cooling capacity W K vs Temperature Inner fan speed vs Temperature Outer fan speed vs Temperature ...

Page 9: ...ng The air supply of the cold air will be used to cool down the system On the opposite side cooler air from the surrounding environment will be drawn in from the external air inlet side and push the heat of the HEX out from the external air exhaust side The thermal exchange path is shown in the figure below 5 2 Configuration Item Q ty Description 1 1 Chassis assy 2 4 Fan guard 3 1 Controller 4 2 I...

Page 10: ... 3 Note the connection location Use brush and low pressure air to remove dust on internal plate assy Item 7 internal fan item 4 and heat exchange core opening Hold internal plate assy Item 7 and connect fan to controller Item 3 Re attach internal plate assy Item 7 and use screw driver to secure screw with chassis assy Item 1 External loop maintenance The maintenance is from the external side Use s...

Page 11: ...d submit spare part s below for replacement Internal fan P N AFB1548EH BJ51 External fan P N AFB1548VH AL1F Controller P N HEX100PC 000C User can then refer to maintaince sequence on previous page or request Delta authorized support for assistance 7 MTBF and Reliability 7 1 MTBF L10 Fan life is expected to be a minimum 80 000 hours continuous operation at 40 C with 15 65 RH label rated vo ltage 7 ...

Page 12: ...ure Use caution at all times Incorrect installation may cause damage and or injury Installation and maintenance should be performed only by qualified personnel Use caution at all times Ensure the grounding wire is connected before powering on the system Ensure the cover and the mounting hardware are secure upon installation All the cables connected to the unit must confirm to UL standards ...