DVP-EH 

DVP04DA-H 

Analog Input Module

 

Instruction Sheet 

 

WARNING 

  Always read this manual thoroughly before using the DVP04DA-H. 
  The DC input power must be disconnected before any maintenance. 
  This is an OPEN-TYPE built-in DVP04DA-H, and the DVP04DA-H is certified to meet the safety 

requirements of IEC 61131-2 (UL 508) when installed in the enclosure to avoid high temperature, 
high humidity, exceessive vibration, corrosive gases, liquids, airbome dust or metallic particles. 
Also, it is equipped with protective methods such as some special tool or key to open the 
enclosure, so as to avoid the hazard to users and the damage to the DVP04DA-H. 

  Do not connect the AC power to any of the input/output terminals, as it might cause damage to 

the DVP04DA-H. Make sure that all the wiring is well conducted prior to power on. 

  Do not touch the internal circuit for at least 1 minute after the power supply is disconnected. 

  Make sure that the DVP04DA-H is properly grounded 

, to avoid any electromagnetic noise.

 

 

INTRODUCTION 

2.1  Model Explanation and Peripherals

 

 

Thank you for choosing DELTA’s PLC DVP Series. The analog output module of DVP04DA-H 
series can read/write the data of analog output module by using commands FROM / TO via 
DVP-PLC EH Series MPU program. The analog output module receives 12-bit digital data of 4 
groups from PLC MPU and transforms it into 4 points analog output signal (voltage or current).   

 

DVP04DA-H analog output module can update software version by RS-485 communication. 

 

Users can select output from voltage or current via wiring. Voltage output range is 0V ~ +10V DC 
(resolution is 2.5 mV). Current output range is 0mA ~ 20mA (resolution is 5 µA). 

 

Nameplate Explanation

 

20.4VDC ~ 28.8VDC

VX.XX

04DA-H0T4130001

0 ~ +10V or  -0 ~+20mA
2.5mV or 5   A

Model Name

Input power supply spec. 

Analog input/output module spec.

Barcode

 

 

Model Explanation

 

Serial Number

Model

Product Series

Input+Output point

Model type
AD: Analog input module

DA: Analog  output  module

PT: Platinum temperature sensors(PT-100)

TC: Thermocouple sensors(Type J/K)

S: for SS series MPU

P: for EP series MPU

H: for EH series MPU

Production week

Production place (Taoyuan)

Production year (2004)

Production Model

XA: A/D ,  D/A  Functions
RT: Resistor Thermocouple

HC: High speed count input module

PU: single axis positioning unit

 

2.2  Product Profile and Outline 

 

Unit:mm 

 

1. DIN rail location (35mm) 

6. Terminals 

2. Mounting hole to connect expansion 

unit/expansion module   

7. Expansion hole of the expansion unit 

mounting pins 

3. Model name 

8. Terminal layout 

4. Indicator LED for power, error and run state

9. Mounting port to connect expansion 

unit/expansion module 

5. DIN rail clip 

 

2.3 External 

wiring 

V+

I+

COM

V+

I+

COM

24+

24-

DC/DC

+15V

-15V

AG

FG

FG

CH1

CH1

0V~+10V

*2

*3

DC24V

CH2

CH2

AC drive, recorder,

scale valve...

AC drive, recorder,

scale valve...

voltage output

shielding cable *1

shielding cable *1

current output

converter

terminal of

power module

system grounding

class 3 grounding

(100

or less)

Note 1: Please isolate analog output and 

other power wiring. 

Note 2: If wave of input terminal of loaded is 

too big that noise interferes wiring, 
please connect capacitance with 
0.1~0.47µF 25V.   

Note 3: Please connect 

 terminal of 

power module and 

 terminal of 

analog output module to system 
earth point and make system earth 
point be grounding or connects to 
machine cover.   

Warning: DO NOT wire to the No function 

terminal 

 

 

 

STANDARD SPECIFICATIONS 

3.1 Specifications 

Digital/Analog (4D/A) Module

Voltage Output 

Current Output 

Power Supply Voltage 

24 VDC(20.4VDC~28.8VDC) ( –15%~+20%) 

Analog Output Channel 

4 channels / each module 

Analog Output Range 

0~10V 0~20 

mA 

Digital Data Range 

0~4000 0~4000 

Resolution  

12 bits (1

LSB

=2.5 mV) 

12 bits (1

LSB

=5 µA) 

Output Impedance 

0.5

 or lower 

Overall Accuracy 

±

0.5% of full scale of 25

(77

)  

±

1% of full scale during 0~55

 (32~131

Response Time 

3 ms 

×

channels 

Max. Output Current 

20 mA(1K

Ω

~2M

Ω

 

Tolerance Carried Impedance 

 

0

500

Ω

 

Digital Data Format 

2’s complementary of 16-bit, 13 Significant Bits 

Isolation Method 

It has isolation between digital area and analog area. There is no 
isolation among channels. 

Protection 

Voltage output has short circuit protection but short circuit for a long 
time may cause inner wiring damage and current output break.   

Communication mode (RS-485)

Yes, there are ASCII/RTU modes, communication rate can be 4800 
/9600 /19200 /38400 /57600 /115200. Communication format of 
ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). Communication 
format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1). When 
connecting to PLC MPU in series, RS-485 can’t be used. 

Connect to DVP-PLC MPU in 
series 

The input point of the first analog expansion unit it connects from the 
near to the distant is from 0 to 7. The Max. is 8 modules and it won’t 
waste digital I/O point. 

3.2 Other 

Specification 

Power Specification 

Max. Rated Consuming Power 

24 VDC (20.4VDC~28.8VDC) (–15%

+20%), 2W, supply from 

external power 

Environment Condition 

Environment Condition 

It is the same with DVP-PLC MPU. 

Spec. of 

Prevent

 Static Electricity 

(all places between terminal and grounding) 

 
 

 

CR (Control Register) 

 
 

DVP04DA-H Analog Output Module 

Explanation 

CR 
No. 

RS-485 

Parameters 

Address 

Latched Register 

Name b15 b14 b13 b12 b11 b10 b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

#0 H 

4032 

 

R Model 

type 

System used, DVP04DA-H model code=H 0401 

Reserved CH4 CH3 CH2 CH1 

#1 H 

4033 

  R/W Output mode setting

Output mode setting: factory setting is H0000. 

Mode 0: output voltage mode (0V~10V). 
Mode 1: output voltage mode (2V~10V). 
Mode 2: output current mode (4mA~20mA). 
Mode 3: output current mode (0mA~20mA). 
Mode 4: none use. 

#2 ~ #5 

Reserved 

DVP04DA-H Analog Output Module 

Explanation 

CR
No.

RS-485 

Parameters 

Address

Latched Register 

Name b15 

b14 

b13 

b12 

b11 b10 b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

#6

H 4038 

  R/W  CH1 output value 

#7

H 4039 

  R/W  CH2 output value 

#8

H 403A 

  R/W  CH3 output value 

#9

H 403B 

  R/W  CH4 output value 

The output setting range of channel CH1~CH4 is K0~K4000. Factory setting is K0 

#10~#17 Reserved 

#18

H 4044 

  R/W  To adjust OFFSET 

value of CH1 

#19

H 4045 

  R/W  To adjust OFFSET 

value of CH2 

#20

H 4046 

  R/W  To adjust OFFSET 

value of CH3 

#21

H 4047 

  R/W  To adjust OFFSET 

value of CH4 

It is used to set the OFFSET value of CH1~CH4. The setting range is 
K-2000~K2000. The factory setting is K0 and unit is LSB. 

#22 ~ #23 

Reserved 

#24

H 404A 

  R/W  To adjust GAIN 

value of CH1 

#25

H 404B 

  R/W  To adjust GAIN 

value of CH2 

#26

H 404C 

  R/W  To adjust GAIN 

value of CH3 

#27

H 404D 

  R/W  To adjust GAIN 

value of CH4 

It is used to set the GAIN value of CH1~CH4. The setting range is K-1600~K8000. 
The factory setting is K2000 and unit is LSB. 

#28~#29 Reserved 

#30

H 4050 

 

R  Error status 

It is the data register to save all error status. Please refer to fault code chart for detail.

#31

H 4051 

  R/W Communication 

address setting   

It is used to set RS-485 communication address. The setting range is from 01 to 255 
and the factory setting is K1. 

#32

H 4052 

  R/W Communication 

Baud Rate setting 

It is used to set communication baud rate (4800, 9600, 19200, 38400, 57600, 
115200bps). Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). 
Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1). 

b0: 4800 bps (bit/sec).               b1: 9600 bps (bit/sec). (factory setting) 
b2: 19200 bps (bit/sec).              b3: 38400 bps (bit/sec).                  
b4: 57600 bps (bit/sec).              b5: 115200 bps (bit/sec). 
b6-b13: reserved.                     
b14: exchange low and high byte of CRC check code (only for RTU mode) 
b15: ASCII / RTU mode selection 

b15 b14 b13 b12 b11 b10 b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

Reserved CH4 CH3 CH2 CH1 

#33

H 4053 

  R/W  Reset to factory 

setting and set 
characteristics 
adjustable priority 

Factory setting H0000. 
Give CH1 setting for example:   

1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#18, CR#24). 

When b0=1, inhibit user to adjust OFFSET and GAIN value of CH1 (CR#18, 
CR#24). 

2. b1 means if characteristic register is latched. b1=0 (factory setting, latched), b1=1 

(not latched). 

3. When b2 is set to 1, all settings will reset to factory setting.   

#34

H 4054 

 

R  Software version. 

It is hexadecimal to display software version. For example: H 010A means 1.0A. 

#35~#48 System 

used 

 means latched.  

  means not latched.   

R means can read data by using FROM command or RS-485.   
W means can write data by using TO command or RS-485. 
LSB (Least Significant Bit):    1. Voltage output: 1

LSB

=10V/8000=2.5mV.    2. Current output: 1

LSB

=20mA/4000=5µA. 

Explanation: 
1. The content of CR#0 is model type, user can read the data from program to know if there is expansion 

module. 

2. CR#1 is used to set two inner channels working mode of analog output module. Every channel has 

four modes to set and can be set individually. For example: if setting CH1 to mode 2 (b2~b0=010), 
CH2 to mode 1(b5~b3=001). It needs to set CR#1 to H000A. The factory setting of CR#1 is H0000. 

3. CR#2 ~ CR#5, CR#10 ~ CR#17, CR#22, CR#23, CR#28, CR#29 Reserved. 

4. 

CR #6 ~ CR#9 display CH1~CH4 output signal. The setting range is K0~K4000. Factory setting is K0 

and unit is LSB.

 

5. CR#18 ~ CR#21 means the value of adjusting OFFSET value of CH1~CH4. The factory setting is K0 

and unit is LSB. If output value equal to 0 after calculating, the adjustable range of analog output 
voltage or current is -2000~+2000. 
Voltage adjustable range: -5V~+5V(-2000

LSB

~+2000

LSB

). 

Current adjustable range: -10mA~+10mA (-2000

LSB

~+2000

LSB

). 

6. CR#24 ~ CR#27 means the value of adjust GAIN value of CH1~CH4. The factory setting is K2000 and 

unit is LSB. If output value equal to 2000 after calculating, the adjustable range of analog output 
voltage or current is -1600~+8000. 
Voltage adjustable range: -4V~+20V(-1600

LSB

~+8000

LSB

). 

Current adjustable range: -8mA ~+40mA (-1600

LSB

~+8000

LSB

). 

But it needs to notice that GAIN VALUE – OFFSET VALUE = +400

LSB

 ~+6000

LSB 

(voltage or 

current). When

 

this value is under this range, the resolution of the output signal will be thin and the 

variation of value will be larger. When this value exceeds this range, the resolution of output signal will 
be thick and the variation of value will be smaller. 

7. CR#30 is fault code. Please refer to the following chart. 

Fault Description 

Content b15~b8 b7

b6

b5

b4

b3

b2

b1

b0

Power Source Abnormal 

K1(H1) 

0 0 0 0 0 0 0 1 

Analog Input Value Error 

K2(H2) 

0 0 0 0 0 0 1 0 

Setting Mode Error 

K4(H4) 

0 0 0 0 0 1 0 0 

Offset/Gain Error 

K8(H8) 

0 0 0 0 1 0 0 0 

Hardware Malfunction   

K16(H10) 

0 0 0 1 0 0 0 0 

Digital Range Error 

K32(H20) 

0 0 1 0 0 0 0 0 

Average Times Setting Error 

K64(H40) 

0 1 0 0 0 0 0 0 

Command Error 

K128(H80) 

Reserved 

1 0 0 0 0 0 0 0 

Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at the same time. 0 

means normal and 1 means having fault. 

8. CR#31 is used to set RS-485 communication address. The setting range is from 01 to 255. The factory 

setting is K1. 

 

 