http://www.delta.com.tw/products/plc.asp
DVP-EH
DVP04DA-H
Analog Input Module
Instruction Sheet
1
WARNING
Always read this manual thoroughly before using the DVP04DA-H.
The DC input power must be disconnected before any maintenance.
This is an OPEN-TYPE built-in DVP04DA-H, and the DVP04DA-H is certified to meet the safety
requirements of IEC 61131-2 (UL 508) when installed in the enclosure to avoid high temperature,
high humidity, exceessive vibration, corrosive gases, liquids, airbome dust or metallic particles.
Also, it is equipped with protective methods such as some special tool or key to open the
enclosure, so as to avoid the hazard to users and the damage to the DVP04DA-H.
Do not connect the AC power to any of the input/output terminals, as it might cause damage to
the DVP04DA-H. Make sure that all the wiring is well conducted prior to power on.
Do not touch the internal circuit for at least 1 minute after the power supply is disconnected.
Make sure that the DVP04DA-H is properly grounded
, to avoid any electromagnetic noise.
2
INTRODUCTION
2.1 Model Explanation and Peripherals
Thank you for choosing DELTA’s PLC DVP Series. The analog output module of DVP04DA-H
series can read/write the data of analog output module by using commands FROM / TO via
DVP-PLC EH Series MPU program. The analog output module receives 12-bit digital data of 4
groups from PLC MPU and transforms it into 4 points analog output signal (voltage or current).
DVP04DA-H analog output module can update software version by RS-485 communication.
Users can select output from voltage or current via wiring. Voltage output range is 0V ~ +10V DC
(resolution is 2.5 mV). Current output range is 0mA ~ 20mA (resolution is 5 µA).
Nameplate Explanation
20.4VDC ~ 28.8VDC
VX.XX
04DA-H0T4130001
0 ~ +10V or -0 ~+20mA
2.5mV or 5 A
Model Name
Input power supply spec.
Analog input/output module spec.
Barcode
Model Explanation
Serial Number
Model
Product Series
Input+Output point
Model type
AD: Analog input module
DA: Analog output module
PT: Platinum temperature sensors(PT-100)
TC: Thermocouple sensors(Type J/K)
S: for SS series MPU
P: for EP series MPU
H: for EH series MPU
Production week
Production place (Taoyuan)
Production year (2004)
Production Model
XA: A/D , D/A Functions
RT: Resistor Thermocouple
HC: High speed count input module
PU: single axis positioning unit
2.2 Product Profile and Outline
Unit:mm
1. DIN rail location (35mm)
6. Terminals
2. Mounting hole to connect expansion
unit/expansion module
7. Expansion hole of the expansion unit
mounting pins
3. Model name
8. Terminal layout
4. Indicator LED for power, error and run state
9. Mounting port to connect expansion
unit/expansion module
5. DIN rail clip
2.3 External
wiring
V+
I+
COM
V+
I+
COM
24+
24-
DC/DC
+15V
-15V
AG
FG
FG
CH1
CH1
0V~+10V
*2
*3
DC24V
CH2
CH2
AC drive, recorder,
scale valve...
AC drive, recorder,
scale valve...
voltage output
shielding cable *1
shielding cable *1
current output
converter
terminal of
power module
system grounding
class 3 grounding
(100
or less)
Note 1: Please isolate analog output and
other power wiring.
Note 2: If wave of input terminal of loaded is
too big that noise interferes wiring,
please connect capacitance with
0.1~0.47µF 25V.
Note 3: Please connect
terminal of
power module and
terminal of
analog output module to system
earth point and make system earth
point be grounding or connects to
machine cover.
Warning: DO NOT wire to the No function
terminal
●
.
3
STANDARD SPECIFICATIONS
3.1 Specifications
Digital/Analog (4D/A) Module
Voltage Output
Current Output
Power Supply Voltage
24 VDC(20.4VDC~28.8VDC) ( –15%~+20%)
Analog Output Channel
4 channels / each module
Analog Output Range
0~10V 0~20
mA
Digital Data Range
0~4000 0~4000
Resolution
12 bits (1
LSB
=2.5 mV)
12 bits (1
LSB
=5 µA)
Output Impedance
0.5
Ω
or lower
Overall Accuracy
±
0.5% of full scale of 25
℃
(77
℉
)
±
1% of full scale during 0~55
℃
(32~131
℉
)
Response Time
3 ms
×
channels
Max. Output Current
20 mA(1K
Ω
~2M
Ω
)
-
Tolerance Carried Impedance
-
0
〜
500
Ω
Digital Data Format
2’s complementary of 16-bit, 13 Significant Bits
Isolation Method
It has isolation between digital area and analog area. There is no
isolation among channels.
Protection
Voltage output has short circuit protection but short circuit for a long
time may cause inner wiring damage and current output break.
Communication mode (RS-485)
Yes, there are ASCII/RTU modes, communication rate can be 4800
/9600 /19200 /38400 /57600 /115200. Communication format of
ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). Communication
format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1). When
connecting to PLC MPU in series, RS-485 can’t be used.
Connect to DVP-PLC MPU in
series
The input point of the first analog expansion unit it connects from the
near to the distant is from 0 to 7. The Max. is 8 modules and it won’t
waste digital I/O point.
3.2 Other
Specification
Power Specification
Max. Rated Consuming Power
24 VDC (20.4VDC~28.8VDC) (–15%
〜
+20%), 2W, supply from
external power
Environment Condition
Environment Condition
It is the same with DVP-PLC MPU.
Spec. of
Prevent
Static Electricity
(all places between terminal and grounding)
4
CR (Control Register)
DVP04DA-H Analog Output Module
Explanation
CR
No.
RS-485
Parameters
Address
Latched Register
Name b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
#0 H
4032
○
R Model
type
System used, DVP04DA-H model code=H 0401
Reserved CH4 CH3 CH2 CH1
#1 H
4033
○
R/W Output mode setting
Output mode setting: factory setting is H0000.
Mode 0: output voltage mode (0V~10V).
Mode 1: output voltage mode (2V~10V).
Mode 2: output current mode (4mA~20mA).
Mode 3: output current mode (0mA~20mA).
Mode 4: none use.
#2 ~ #5
Reserved
DVP04DA-H Analog Output Module
Explanation
CR
No.
RS-485
Parameters
Address
Latched Register
Name b15
b14
b13
b12
b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
#6
H 4038
○
R/W CH1 output value
#7
H 4039
○
R/W CH2 output value
#8
H 403A
○
R/W CH3 output value
#9
H 403B
○
R/W CH4 output value
The output setting range of channel CH1~CH4 is K0~K4000. Factory setting is K0
#10~#17 Reserved
#18
H 4044
○
R/W To adjust OFFSET
value of CH1
#19
H 4045
○
R/W To adjust OFFSET
value of CH2
#20
H 4046
○
R/W To adjust OFFSET
value of CH3
#21
H 4047
○
R/W To adjust OFFSET
value of CH4
It is used to set the OFFSET value of CH1~CH4. The setting range is
K-2000~K2000. The factory setting is K0 and unit is LSB.
#22 ~ #23
Reserved
#24
H 404A
○
R/W To adjust GAIN
value of CH1
#25
H 404B
○
R/W To adjust GAIN
value of CH2
#26
H 404C
○
R/W To adjust GAIN
value of CH3
#27
H 404D
○
R/W To adjust GAIN
value of CH4
It is used to set the GAIN value of CH1~CH4. The setting range is K-1600~K8000.
The factory setting is K2000 and unit is LSB.
#28~#29 Reserved
#30
H 4050
╳
R Error status
It is the data register to save all error status. Please refer to fault code chart for detail.
#31
H 4051
○
R/W Communication
address setting
It is used to set RS-485 communication address. The setting range is from 01 to 255
and the factory setting is K1.
#32
H 4052
○
R/W Communication
Baud Rate setting
It is used to set communication baud rate (4800, 9600, 19200, 38400, 57600,
115200bps). Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1).
Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).
b0: 4800 bps (bit/sec). b1: 9600 bps (bit/sec). (factory setting)
b2: 19200 bps (bit/sec). b3: 38400 bps (bit/sec).
b4: 57600 bps (bit/sec). b5: 115200 bps (bit/sec).
b6-b13: reserved.
b14: exchange low and high byte of CRC check code (only for RTU mode)
b15: ASCII / RTU mode selection
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Reserved CH4 CH3 CH2 CH1
#33
H 4053
○
R/W Reset to factory
setting and set
characteristics
adjustable priority
Factory setting H0000.
Give CH1 setting for example:
1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#18, CR#24).
When b0=1, inhibit user to adjust OFFSET and GAIN value of CH1 (CR#18,
CR#24).
2. b1 means if characteristic register is latched. b1=0 (factory setting, latched), b1=1
(not latched).
3. When b2 is set to 1, all settings will reset to factory setting.
#34
H 4054
○
R Software version.
It is hexadecimal to display software version. For example: H 010A means 1.0A.
#35~#48 System
used
○
means latched.
╳
means not latched.
R means can read data by using FROM command or RS-485.
W means can write data by using TO command or RS-485.
LSB (Least Significant Bit): 1. Voltage output: 1
LSB
=10V/8000=2.5mV. 2. Current output: 1
LSB
=20mA/4000=5µA.
Explanation:
1. The content of CR#0 is model type, user can read the data from program to know if there is expansion
module.
2. CR#1 is used to set two inner channels working mode of analog output module. Every channel has
four modes to set and can be set individually. For example: if setting CH1 to mode 2 (b2~b0=010),
CH2 to mode 1(b5~b3=001). It needs to set CR#1 to H000A. The factory setting of CR#1 is H0000.
3. CR#2 ~ CR#5, CR#10 ~ CR#17, CR#22, CR#23, CR#28, CR#29 Reserved.
4.
CR #6 ~ CR#9 display CH1~CH4 output signal. The setting range is K0~K4000. Factory setting is K0
and unit is LSB.
5. CR#18 ~ CR#21 means the value of adjusting OFFSET value of CH1~CH4. The factory setting is K0
and unit is LSB. If output value equal to 0 after calculating, the adjustable range of analog output
voltage or current is -2000~+2000.
Voltage adjustable range: -5V~+5V(-2000
LSB
~+2000
LSB
).
Current adjustable range: -10mA~+10mA (-2000
LSB
~+2000
LSB
).
6. CR#24 ~ CR#27 means the value of adjust GAIN value of CH1~CH4. The factory setting is K2000 and
unit is LSB. If output value equal to 2000 after calculating, the adjustable range of analog output
voltage or current is -1600~+8000.
Voltage adjustable range: -4V~+20V(-1600
LSB
~+8000
LSB
).
Current adjustable range: -8mA ~+40mA (-1600
LSB
~+8000
LSB
).
But it needs to notice that GAIN VALUE – OFFSET VALUE = +400
LSB
~+6000
LSB
(voltage or
current). When
this value is under this range, the resolution of the output signal will be thin and the
variation of value will be larger. When this value exceeds this range, the resolution of output signal will
be thick and the variation of value will be smaller.
7. CR#30 is fault code. Please refer to the following chart.
Fault Description
Content b15~b8 b7
b6
b5
b4
b3
b2
b1
b0
Power Source Abnormal
K1(H1)
0 0 0 0 0 0 0 1
Analog Input Value Error
K2(H2)
0 0 0 0 0 0 1 0
Setting Mode Error
K4(H4)
0 0 0 0 0 1 0 0
Offset/Gain Error
K8(H8)
0 0 0 0 1 0 0 0
Hardware Malfunction
K16(H10)
0 0 0 1 0 0 0 0
Digital Range Error
K32(H20)
0 0 1 0 0 0 0 0
Average Times Setting Error
K64(H40)
0 1 0 0 0 0 0 0
Command Error
K128(H80)
Reserved
1 0 0 0 0 0 0 0
Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at the same time. 0
means normal and 1 means having fault.
8. CR#31 is used to set RS-485 communication address. The setting range is from 01 to 255. The factory
setting is K1.