Analog Output Module 

Instruction Sheet 

 

Warning 

9

 

Please read this instruction carefully before use.

 

9

 

Switch off the power before wiring.

 

9

 

DVP04DA-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of 
airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance 
staff from operating the device (e.g. key or specific tools are required to open the enclosure) in case 
danger and damage on the device may occur.

 

9

 

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may 
occur. Check all the wiring again before switching on the power.

   

9

 

DO NOT tough any terminal when the power is switched on. DO NOT touch any internal circuit in 1 
minute after the power is switched off.

   

9

 

Make sure the groud terminal 

  is correctly grounded in order to prevent electromagnetic 

interference.

 

 

Introduction

 

1.1  Model Explanation & Peripherals 
 

™

 

Thank you for choosing Delta DVP series. DVP04DA-H2 is able to read and write data of DVP04DA-H2 analog 

signal output modules through FROM/TO instructions given by the program of DVP-EH2 series MPU. The 
analog signal output module receives 4 groups of 12-bit digital data from PLC MPU and converts the data into 4 
points of analog signals for output in either voltage or current. 

™

 

The user can select voltage or current output by wiring. Range of voltage output: 0V ~ +10VDC (resolution: 

2.5mV). Range of current output: 0mA ~ 20mA (resolution: 5

μ

A).

 

™

 

Nameplate Explanation

 

 

04 DA -H2 0T6 500 00 1

VX.XXXX

24Vdc  4.5W

MADE  IN  XXXXX X

2.5 mV or  5    A

 0V ~ + 10V or 0mA ~ +20mA

Power input specification

Delta PLC model name

Barcode, Serial No., Version

Analog I/O module specification

 

™

 

Model/Serial No. Explanation

 

 

 

1.2  Product Profile (Indicators, Terminal Block, I/O Terminals) 

 

Unit: mm

 

D -

V

 +

I +

V

 +

24V

0

V

+

V

 +

I +

V

 +

I +

D +

C

O

M

8

C

H

1

C

H2

C

H

3

C

H4

R

S

-485

FG

FG

FG

CO
M

C

O

M

CO
M

 

 

1

 

DIN rail (35mm) 

6

 

Terminals 

2

 

Connection port for extension modules 

7

 

Mounting hole 

3

 

Model name 

8

 

I/O terminals 

4

 

POWER, ERROR, D/A indicator 

9

 

Mounting port for extension modules 

5

 

DIN rail clip 

 

 

 
1.3 External 

Wiring 

 

V+

I+

COM

V+

I+

COM

24+

24-

DC/DC

+15V

-15V

AG

FG

FG

CH1

CH1

0V~+10V

*2

*3

0mA~20mA

DC24V

CH4

CH4

AC drive, recorder,

scale valve...

AC drive, recorder,
scale valve...

voltage output

shielding cable *1

shielding cable *1

current output

converter

terminal of

power module

system grounding

class 3 grounding

(100

or less)

 

Note: 

1.

 

When performing analog output, please isolate other power wirings.   

2.

 

If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the 
wiring to 0.1 ~ 0.47

μ

F 25V capacitor. 

3.

 

Please connect the 

 

terminal on both the power modules and DVP04DA-H2 to the system earth point and ground the 

system contact or connect it to the cover of power distribution cabinet. 

4.

 

DO NOT wire empty terminals 

 

 

Specifications

 

2.1. Functions 

Digital/Analog (4D/A) Module 

Voltage Output 

Current Output 

Power supply voltage 

24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%) 

Analog output channel 

4 channels/module 

Range of analog output 

0 ~ 10V 

0 ~ 20mA 

Range of digital data 

0 ~ 4,000 

0 ~ 4,000 

Resolution 

12 bits (1

LSB

 = 2.5mV) 

12 bits (1

LSB

 = 5 

μ

A) 

Output impedance 

0.5

 or lower 

Overall accuracy 

±

0.5% when in full scale (25°C, 77°F) 

±

1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F 

Responding time 

3ms × the number of channels 

Max. output current 

10mA (1K

 ~ 2M

) - 

Tolerable load impedance 

0 ~ 500

 

Digital data format 

11 significant bits out of 16 bits are available; in 2’s complement 

Isolation 

Internal circuit and analog output terminals are isolated by optical coupler. 
No isolation among analog channels. 

Protection 

Voltage output is protected by short circuit. Short circuit lasting for too long may 
cause damage on internal circuits. Current output can be open circuit. 

Communication mode 
(RS-485) 

ASCII/RTU mode.   
Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200 bps 
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1) 
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1) 
RS-485 cannot be used when connected to PLC MPU. 

When connected to 
DVP-PLC MPU in series 

The modules are numbered from 0 to 7 automatically by their distance from MPU. 
No.0 is the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed 
to connect to MPU and will not occupy any digital I/O points.   

2.2. Others 

Power Supply 

Max. rated power 
consumption 

24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)., 4.5W supplied by external power 

Environment 

Operation/storage 

Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2 
Storage: -40°C ~ 70°C (temperature); 5 ~ 95% (humidity) 

Vibration/shock 
immunity 

International standards: IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 
68-2-27 (TEST Ea) 

 

 

 

 

 

Control Registers

 

DVP04DA-H2 analog output module 

Description 

CR# 

RS-485 

parameter 

address

 

Latched  Register content 

b15  b14  b13  b12  b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 

#0 

H’4032 

 

Model name 

Set up by the system. DVP04DA-H2 model code = H’6401 

reserved 

CH4 

CH3 

CH2 

CH1 

#1 

H’4033 

  R/W 

Output mode 
setting 

Output mode: Default = H’0000 
Mode 0: Voltage output (0V ~ 10V) 

Mode 1: Voltage output (2V ~ 10V) 
Mode 2: Current output (4mA ~ 20mA) 
Mode 3: Current output (0mA ~ 20mA) 

#2 ~ #5 

Reserved 

#6 

H’4038 

 

R/W  CH1 output value 

#7 

H’4039 

 

R/W  CH2 output value 

#8 

H’403A 

 

R/W  CH3 output value 

#9 

H’403B 

 

R/W  CH4 output value 

Range of output value at CH1 ~ CH4: K0 ~ K4,000 
Default = K0 (unit: LSB) 

#10 ~ #17 

Reserved 

#18 

H’4044 

  R/W 

Adjusted OFFSET 
value of CH1 

#19 

H’4045 

  R/W 

Adjusted OFFSET 
value of CH2 

#20 

H’4046 

  R/W 

Adjusted OFFSET 
value of CH3 

#21 

H’4047 

  R/W 

Adjusted OFFSET 
value of CH4 

Range of OFFSET at CH1 ~ CH4: K-2,000 ~ K2,000 
Default = K0 (unit: LSB) 

#22 ~ #23 

Reserved 

#24  H’404A 

  R/W 

Adjusted GAIN 
value of CH1 

#25  H’404B 

  R/W 

Adjusted GAIN 
value of CH2 

#26  H’404C 

  R/W 

Adjusted GAIN 
value of CH3 

#27  H’404D 

  R/W 

Adjusted GAIN 
value of CH4 

Range of GAIN at CH1 ~ CH4: K-1,600 ~ K8,000 
Default = K2,000 (unit: LSB) 

#28 ~ #29 

Reserved 

#30 

H’4050 

 

Error status 

Register for storing all error status. See the table of error status for more information. 

#31 

H’4051 

  R/W 

Communication 
address setting 

For setting up RS-485 communication address. Range: 01 ~ 255 
Default = K1 

#32 

H’4052 

  R/W 

Communication 
speed (baud rate) 
setting 

Default = H’0002. For setting up communication speed: 4,800 / 9,600 / 19,200 / 
38,400 / 57,600 / 115,200bps 
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1) 
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1)   
b0: 4,800bps   b1: 9,600bps (default) 
b2: 19,200bps  b3: 38,400bps 
b4: 57,600bps  b5: 115,200bps 
b6 ~ b13: reserved 
b14: High/low bit exchange of CRC checksum (only valid in RTU mode) 
b15: Switch between ASCII/RTU mode. 0 = ASCII mode (default) 

b15  b14  b13  b12  b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 

reserved  CH4 CH3 CH2 CH1 

#33  H’4053 

  R/W 

Return to default 
setting; 
OFFSET/GAIN 
tuning 
authorization 

Default = H’0000. Take the setting of CH1 for example: 

1.    When b0 = 0, the user is allowed to tune CR#18 (OFFSET) and CR#24 (GAIN) 

of CH1. When b0 = 1, the user is not allowed to tune CR#18 (OFFSET) and 
CR#24 (GAIN) of CH1.

 

2.    b1 represents whether the OFFSET/GAIN tuning registers are latched. b1 = 0 

(default, latched); b1 = 1 (non-latched)   

3.    When b2 = 1, all settings will return to default values. (except CR#31, CR#32) 

#34 

H’4054 

 

Firmware version 

Displaying the current firmware version In hex; e.g. version 1.0A is indicated as   
H’010A. 

#35 ~ #48 

 

For system use. 

Symbols 

: latched (when written in through RS-485 communication) 

: non-latched 

R: Able to read data by FROM instruction or RS-485 communication 
W: Able to write data by TO instruction or RS-485 communication 
LSB (Least Significant Bit): For voltage output    1

LSB 

= 10V/4,000 = 2.5mV

 

For current output    1

LSB 

= 20mA/4,000 = 5

μ

A

 

Explanations: 

1.

   CR#0: Model name. The user can read the model name from the program and see if the extension module 

exists.  

2.

   CR#1: The working mode of the four channels in the analog input module. There are 4 modes for each channel 

which can be set up separately. For example, if the user needs to set up CH1: mode 0 (b2 ~ b0 = 000); CH2: 
mode 1 (b5 ~ b3 = 001), CH3: mode 2 (b8 ~ b6 = 010) and CH4: mode 3 (b11 ~ b9 = 011), CR#1 has to be set 
as H’000A and the higher bits (b12 ~ b15) have to be reserved. Default value = H’0000. 

3.

   CR#2 ~ CR#5, CR#10 ~ CR#17, CR#22, CR#23, CR#28 and CR#29 are reserved. 

4.

   CR#6 ~ CR#9: The output values of CH1 ~ CH4 (range: K0 ~ K4,000; default = K0; unit: LSB) 

5.

   CR#18 ~ CR#21: The adjusted OFFSET value of CH1 ~ CH4 (default = K0, unit = LSB), representing the analog 

output voltage or current when the output digital value = 0 after calculation. The adjustable range: -2,000 ~ 
+2,000. 

The adjustable range of voltage: -5V ~ +5V (-2,000

LSB 

~ +2,000

LSB

The adjustable range of current: -10mA ~ +10mA (-2,000

LSB 

~ +2,000

LSB

6.

   CR#24 ~ CR#2: The adjusted GAIN value of CH1 ~ CH4 (default = K2,000, unit = LSB), representing the analog 

output voltage or current when the output digital value = 2,000 after calculation. 