Series Temperature Controller 

Instruction Sheet 

Thank you very much for choosing Delta DTE series temperature controller. Please read this instruction sheet carefully before 
using your DTE to ensure proper operation. Keep this instruction sheet handy for quick reference. 

 Warning 

DANGER! CAUTION! ELECTRIC SHOCK! 

DTE is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, 
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from 
operating the device (e.g. key or specific tools are required for opening the enclosure) in case danger and 
damage on the device may occur

.

1.  Prevent dust or metallic debris from falling into the device and cause malfunctions. 

DO NOT

 modify or uninstall the circuit 

board of DTE without being permitted. 

DO NOT

 use empty terminals. 

2.  Keep away from high-voltage and high-frequency environment during the installation in case of interference. Prevent using 

the device in premises which contain:   

(a) dust or corrosive gas;    (b) high humidity and high radiation;    (c) shock and vibration. 

3.  The power has to be switched off when wiring or changing the temperature sensor. 

4.  When installing the circuit board of the accessory, please make sure the power of the main unit is switched off and insert 

the accessory into the correct slot on the main unit. 

5.  Make sure to use compensation wire which matches the thermocouple or platinum resistance when extending or 

connecting the thermocouple or platinum resistance. 

6.  Keep the wire as short as possible when wiring a sensor to the controller. Separate the power cable and load wire in order 

to prevent interference and induced noise. 

7.  Make sure the power cables and signal device are installed correctly before switching on the power; otherwise serious 

damage may occur. 

8.

DO NOT

 touch the terminal or repair the device when the power is on; otherwise an electric shock may occur.   

9.  Please wait for 1 minute after the power is switched off to allow the capacitor to discharge and 

DO NOT

 touch the internal 

wiring within this period.   

10.

DO NOT

 touch the internal terminal when DTE is either switched on or off in case you may damage the circuit. 

11. Please place DTE with other heating objects (e.g. power supply) within proper distance while installing DTE. 

 

Ordering Information

Series name 

DTE: Delta E series temperature controller 

 1  

Device type 

1: main unit       

2: accessory 

 2   3

0T: 4-channel TC 
0P: 4-channel PT 

0T: 4-channel TC 
0P: 4-channel PT 
0V: 4 channels of voltage pulse output 
0C: 4 channels of linear current output 
0R: 4 channels of relay output 
0L: 4 channels of linear voltage output 
CT: 4 channels of current transformer sensors 
DS: Display and setup module 

 Functions & Electrical Specifications

Power input 

DC 24V, isolated switching power supply 

Voltage range 

90% ~ 110% rated voltage 

Power consumption 

Max. 10W + 3W × number of DTC2000 controllers connected in parallel (Max. 7) 

Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK 

Input sensor 

Platinum resistance: Pt100, JPt100, Cu50 

Sampling cycle 

Thermocouple or platinum resistance: 1.0 second/all input 

Control method 

PID, PID programmable, manual, ON/OFF 

Relay output: SPST, Max. AC 250V load, 3A resistive load 

Voltage pulse output: DC 24V, Max. 40mA current output 

Current output: DC 4 ~ 20mA output (resistive load < 500

Ÿ

); for OUT1 and OUT2 only 

Output accessories 
(optional)

Analog voltage output: 0 ~ 10V (resistive load > 1,000

Ÿ

); for OUT1 and OUT2 only 

Output functions 

Control output, alarm output or proportional output (proportional output is only applicable in 
the model with linear voltage and current output for OUT1, OUT2) 

Alarm modes 

12 alarm modes available 

Communication 

RS-485 digital communication; supports baud rate 2,400bps ~ 115,200bps 

Communication
protocol

Supports Modbus ASCII/RTU 

Extension port 

The extension port transmits 24V power supply and communication signals to extension 

module DTC2000. 

Vibration resistance 

10 ~ 55Hz    10m/s

2

 3 axes  10mins 

Shock resistance 

Max. 300m/s

2

    3 axes 6 directions, 3 times each 

Ambient temperature 

0°C ~ +50°C 

Storage temperature 

-20°C ~ +65°C 

Operation altitude 

< 2,000m 

Ambient humidity 

35% to 85% RH (non-condensing) 

Pollution degree 

 Product Profile & Outline

DTE10T/P

1 I/O 

terminals 

2 Status 

LED 

3 Display 

and 

setup 

unit 

DIN rail clip 

Power input port 

RS-485 communication port 

Extension module fixing clip 

8 Extension 

port 

 Panel Layout

 Input

The standard DTE main unit is attached with 4 channels of inputs. You can purchase additional DTE20T or DTE20P to expand 
the number of input channels. DTE supports maximum 8 channels of inputs which belong to group INA and group INB. Each 
group possesses 4 input channels. 

DTE series supports the following input sensors:

Input Sensor Type 

Register Value 

Range

For DTE10P / DTE20P 

 

C

°

0

5

1

 

~

 

0

5

-

 

3

1

 

)

0

5

u

C

(

 

e

c

n

a

t

s

i

s

e

r

 

t

n

e

m

e

r

u

s

a

e

m

 

e

r

u

t

a

r

e

p

m

e

T

 

C

°

0

0

6

 

~

 

0

0

2

-

 

2

1

 

)

0

0

1

t

P

(

 

e

c

n

a

t

s

i

s

e

r

 

m

u

n

i

t

a

l

P

 

C

°

0

0

4

 

~

 

0

2

-

 

1

1

 

)

0

0

1

t

P

J

(

 

e

c

n

a

t

s

i

s

e

r

 

m

u

n

i

t

a

l

P

For DTE10T / DTE20T 

 

C

°

0

0

8

 

~

 

0

0

2

-

 

0

1

 

e

p

y

t

 

K

X

T

 

e

l

p

u

o

c

o

m

r

e

h

T

 

C

°

0

0

5

 

~

 

0

0

2

-

 

9

 

e

p

y

t

 

U

 

e

l

p

u

o

c

o

m

r

e

h

T

 

C

°

0

5

8

 

~

 

0

0

2

-

 

8

 

e

p

y

t

 

L

 

e

l

p

u

o

c

o

m

r

e

h

T

 

C

°

0

0

8

,

1

 

~

 

0

0

1

 

7

 

e

p

y

t

 

B

 

e

l

p

u

o

c

o

m

r

e

h

T

 

C

°

0

0

7

,

1

 

~

 

0

 

6

 

e

p

y

t

 

S

 

e

l

p

u

o

c

o

m

r

e

h

T

 

C

°

0

0

7

,

1

 

~

 

0

 

5

 

e

p

y

t

 

R

 

e

l

p

u

o

c

o

m

r

e

h

T

 

C

°

0

0

3

,

1

 

~

 

0

0

2

-

 

4

 

e

p

y

t

 

N

 

e

l

p

u

o

c

o

m

r

e

h

T

 

C

°

0

0

6

 

~

 

0

 

3

 

e

p

y

t

 

E

 

e

l

p

u

o

c

o

m

r

e

h

T

 

C

°

0

0

4

 

~

 

0

0

2

-

 

2

 

e

p

y

t

 

T

 

e

l

p

u

o

c

o

m

r

e

h

T

 

C

°

0

0

2

,

1

 

~

 

0

0

1

-

 

1

 

e

p

y

t

 

J

 

e

l

p

u

o

c

o

m

r

e

h

T

 

C

°

0

0

3

,

1

 

~

 

0

0

2

-

 

0

 

e

p

y

t

 

K

 

e

l

p

u

o

c

o

m

r

e

h

T

Note:

 The default setting in DTE10T is “thermocouple K type”. The default setting in DTE10P is “Pt100".   

Communication address: Input sensor types at H10A0 ~ H10A7; input upper limits at H1010 ~ H1017; input lower limits at 
H1018 ~ H101F.

 Output

DTE supports maximum 16 channels of outputs, belonging to output groups OUT1, OUT2, SUB1 and SUB2, each group with 4 
channels. See the explanations below for how input channels correspond to output groups. 

 Without group INB (4 channels of input): Every channel corresponds to 2 groups of output and 2 groups of alarms. OUT1 and 

SUB1 are for control output, and OUT1 can be used for proportional output. OUT2 and SUB2 are fixed for alarm output.   

 With group INB (8 channels of input): Every channel is paired with 2 groups of outputs. OUT1 and OUT2 are used for control 

output or proportional output of CH1 ~ CH8. SUB1 and SUB2 are used for control output or alarm output. 

See Table 1 for the relations between input and output. 

4 channels of input 

8 channels of input   

Output Group

INA (CH1 ~ CH4) 

INA (CH1 ~ CH4) 

INB (CH5 ~ CH8) 

OUT1 

Main control output or 

proportional output 

Main control output or proportional 

output

No corresponding output 

OUT2 

Alarm 1 output 

No corresponding output 

Main control output or proportional 

output

SUB1 

Control output 

Control output or alarm output 

No corresponding output 

SUB2 

Alarm 2 output 

No corresponding output 

Control output or alarm output 

Table 1 

Note: 

SUB1 and SUB2 do not support DTE20L and DTE20C. Please install the optional output modules you purchase into 

the correct slot. 

Communication Address of Output & How to Set up Parameters: 

See Table 2 for the communication addresses of output and Table 3 for the definition of the value in the address.   

INA 

INB

CH1

CH2

CH3

CH4

CH5

CH6

CH7

CH8

OUT1, OUT2 

H10A8

H10A9

H10AA

H10AB

H10AC

H10AD

H10AE

H10AF

SUB1, SUB2 

H10B0

H10B1

H10B2

H10B3

H10B4

H10B5

H10B6

H10B7

Table 2 

 

Value = 0 

Value = 1 

Value = 2 

Value = 3 

OUT1, OUT2** 

Heating control 

Cooling control 

Proportional output 

Disable output 

SUB1, SUB2** 

Heating control 

Cooling control 

Alarm output* 

Disable output 

Table 3 

*

When there are only 4 channels of inputs, SUB1 cannot be used for alarm output but heating/cooling control only.   

**

When there are only 4 channels of inputs, OUT2 and SUB2 cannot be set up by the user but set up automatically as "alarm 

output” by the controller.

Control Output: 

DTE offers PID control, ON/OFF control, manual control and programmable PID control. Control output methods are set at 
address H10B8 ~ H10BF (default = 0: PID), PID parameters at H1028 ~ H105F, ON/OFF parameters at H1058 ~ H106F, and 
manual control parameters at H1070 ~ H107F.   

Alarm Output: 

DTE offers 12 alarm modes. The alarm modes are set up at address H10C0 ~ H10C7, upper limits at H1080 ~ H1087 and 
lower limits at H1088 ~ H108F.   

SV

Alarm Mode 

Alarm Output Operation 

0 No 

alarm 

Off 

1

Alarm output is enabled when the temperature reaches upper and lower 
limits: The alarm will be enabled when PV exceeds SV + AL-H or falls below 
SV – AL-L.   

ON

OFF

AL-L

SV

AL-H

2

Alarm output will be enabled when the temperature reaches the upper limit: 
The alarm will be enabled when the PV exceeds SV + AL-H.   

ON

OFF

SV

AL-H

3

Alarm output will be enabled when the temperature reaches the lower limit: 
The alarm will be enabled when the PV falls below SV – AL-L.   

ON

OFF

AL-L

SV

4

Alarm output will be enabled when the PV is between SV + AL-H and SV – 
AL-L.

ON

OFF

AL-L

SV

AL-H

5

Alarm output will be enabled when the temperature reaches the absolute 
value of the upper and lower limits: The alarm will be enabled when the PV 
exceeds AL-H or falls below AL-L.   

ON

OFF

AL-L

AL-H

6

Alarm output will be enabled when the temperature reaches the absolute 
value of the upper limit: The alarm will be enabled when the PV exceeds 
AL-H.

ON

OFF

AL-H

7

Alarm output will be enabled when the temperature reaches the absolute 
value of the lower limit: The alarm will be enabled when the PV falls below 
AL-L.

ON

OFF

AL-L

8

Upper/lower limit standby alarm: The alarm will be enabled when the PV 
reaches SV and further exceeds SV + AL-H or falls below SV – AL-L.   

ON

OFF

AL-L

AL-H

SV

9

Upper limit standby alarm: The alarm will be enabled when the PV reaches 
SV and further exceeds SV + AL-H.   

ON

OFF

SV

AL-H

10

Lower limit standby alarm: The alarm will be enabled when the PV reaches 
SV and further falls below SV 

 AL-L.   

ON

OFF

AL-L

SV

11 

Upper limit hysteresis alarm: The alarm will be enabled when the PV exceeds 
SV + AL-H. The alarm will be disabled when the PV falls below SV + AL-L.   

ON

OFF

AL-L

AL-H

12

Lower limit hysteresis alarm: The alarm will be enabled when the PV falls 
below SV 

 AL-H. The alarm will be disabled when the PV exceeds SV 

AL-L.

ON

OFF

AL-L

AL-H

 LED Display

PWR: On 

 DTE is powered. 

RUN: On 

 Any of the channel is executing. 

COM: Flashing 

 Communication in progress 

ERR: Indicating errors (red) 

ERR LED is on indicates one of the following errors occur, and the output has to be disabled. 

1. Memory EEPROM error. 

2.  Any of the input points is not connected. 

3.  Any of the input points exceeds the setup range. 

4.  Any of the input temperatures has not been stabilized. 

 Synchronous Communication Protocol & Auto ID Setup

This function allows the auto setup of communication protocol in extension module DTC2000 and DTC2001 following the 
communication protocol set in the DTE main unit. The station IDs of DTC decrease. See below for the steps. 

1.  Set the auto communication ID of DTE as “1” (communication address: H10F8). 

2.  Switch off DTE. Connect DTE with extension module DTC2000, DTC2001 and switch on DTE again. 

3.  Default communication protocol: 9,600bps, 7 bits, Even, 1 stop bit, communication address = 01. 