A Series Temperature Controller 

Instruction Sheet

 

Thank you very much for purchasing DELTA A Series. Please read this instruction sheet 

before using your A series to ensure proper operation and please keep this instruction 

sheet handy for quick reference. 

Precaution 

 

DANGER!

 

Caution! Electric Shock! 

 

1. Do not touch the AC terminals while the power is supplied to the controller to 

prevent an electric shock. 

2. Make sure power is disconnected while checking the unit inside. 

3. The symbol 

 indicates that this Delta A Series Temperature Controller is 

protected throughout by DOUBLE INSULATION or REINFORCED INSULATION 
(equivalent to Class II of IEC 536). 

 

WARNING!

 

 

This controller is an open-type temperature controller. Make sure to evaluate any 

dangerous application in which a serious human injury or serious property damage 

may occur. 

1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 

screw, width is 7.0mm, hole diameter 3.2mm). 

Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer).  

Recommended tightening torque: 0.4 N.m (4kgf.cm). 

Applicable wire: Solid/twisted wire of 2 mm

2

, 12AWG to 24AWG.  

Please be sure to tighten them properly. 

2. Do not allow dust or foreign objects to fall inside the controller to prevent it from 

malfunctioning. 

3. Never modify or disassemble the controller. 

4. Do not connect anything to the “No used” terminals. 

5. Make sure all wires are connected to the correct polarity of terminals. 

6. Do not install and/or use the controller in places subject to: 

• 

Dust or corrosive gases and liquid. 

• 

High humidity. 

• 

High radiation. 

• 

Vibration and shock. 

• 

High voltage and high frequency 

7. Must turn power off when wiring and changing a temperature sensor. 

8. Be sure to use compensating wires that match the thermocouple types when 

extending or connecting the thermocouple wires. 

9. Please use wires with resistance when extending or connecting a platinum 

resistance thermometer (RTD). 

10. Please keep the wire as short as possible when wiring a platinum resistance 

thermometer (RTD) to the controller and please route power wires as far as 

possible from load wires to prevent interference and induced noise. 

11. This controller is an open-type unit and must be placed in an enclosure away from 

high temperature, humidity, dripping water, corrosive materials, airborne dust and 

electric shock or vibration. 

12. Please make sure power cables and signals from instruments are all installed 

properly before energizing the controller, otherwise serious damage may occur. 

13. Please do not touch the terminals in the controller or try to repair the controller 

when power is applied to prevent an electric shock. 

14. Wait at least one minute after power is disconnected to allow capacitors to 

discharge, and please do not touch any internal circuit within this period. 

15. Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to 

clean the controller. 

16. This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or 

power supply switch is required, install the protection close to the instrument.  

 

Recommended fuse rating: Rated voltage 250 V, Rated current 1 A.   

 

Fuse type: Time-lag fuse 

 

Note: This controller does not provide overcurrent protection. Use of this product 

requires that suitable overcurrent protection device(s) must be added to ensure 

compliance with all relevant electrical standards and codes. (Rated 250 V, 15 

Amps max). A suitable disconnecting device should be provided near the 

controller in the end-use installation. 

 

 

 

Display, LED and Pushbuttons 

 

• 

PV Display

 : to display the process value or parameter type. 

• 

SV Display

 : to display set point, parameter operation read value, manipulated 

variable  or set value of the parameter. 

• 

AT 

: flashes when the Auto-tuning operation is ON. 

• 

OUT 

: lights when the output is ON. 

• 

 

Function key

. 1. Press this key to select the desired function mode. 

 

2. Press this key to confirm a setting value. 

• 

 

Mode key

. Press this key to set parameters within each function mode.

 

• 

o

C, 

o

F : 

Temperature unit LEDs

o

C LED lights when this parameter is configured for 

Celsius and 

o

F LED lights if configured for Fahrenheit.

 

• 

ALM1 / ALM2 : 

Alarm output LED

. The ALM1 / ALM2 LED lights when Alarm 1 or 

Alarm 2 output is ON.

 

• 

 

Up key

. Press this key to increase values displayed on the SV display. Hold 

down this key to speed up the incremental action.

 

• 

 

:

 Down key

. Press this key to decrease values displayed on the SV display. Hold 

down this key to speed up the decrements. 

 

 

Specifications 

 

Input Voltage 

100 to 240VAC 

50/60Hz 

Operation Voltage Range  85% to 110% of rated voltage 
Power Consumption 

5VA  max. 

Display Method 

7-segment digit LED Display 
Process value (PV): Red color, Set point (SV): Green color 
Thermocouple: K, J, T, E, N, R, S, B, U, L, Txk 

Sensor Type

 

3-wire Platinum RTD: Pt100, JPt100 

Control Mode 

PID, ON/OFF control or Manual tuning 
Relay output:(resistive load): SPDT (SPST: 1/16 DIN size), 
250VAC, 5A 
Voltage Pulse output: DC 14V, Max. load current 40mA 

Control Output 

Current output: 4 to 20mADC (Load resistance: Max. 600

Ω

)

Display Accuracy 

0.1% of measuring range 

Sampling Rate 

500 msec/per scan 

Vibration Resistance 

10 to 55Hz, 10m/s

2

 for 10min, each in X, Y and Z directions

Shock Resistance 

Max. 300m/ s

2

, 3 times in each 3 axes, 6 directions 

Ambient Temperature 

0

o

C to +50

 o

C

Storage Temperature 

-20

 o

C to +65

 o

C

Relative Humidity 

35% to 80% (non-condensing) 

Altitude 

2000m or less 

Installation Environment 

Installation Category 

33

, Pollution Degree 2. Conforming to 

EN61010-1 

 

 

Parameters List 

1. Operation Mode: Perform per the settings of related control parameters 

LED Display

Explanation 

Default

RUN/STOP: Control setting begins. Run (

) or Stop 

(

) mode on the SV display. 

 

RUN 

ALARM1 HIGH: Upper-limit alarm 1 

4.0

 

o

ALARM1 LOW: Lower-limit alarm 1 

4.0

 

o

ALARM2 HIGH: Upper-limit alarm 2 

4.0

 

o

ALARM2 LOW: Lower-limit alarm 2 

4.0

 

o

Setting lock: Lock 1 (

), Lock 2 (

) or OFF

(

) on the SV display. Lock 1 mode can lock all settings 

and Lock 2 mode only can lock others than SV value. When 
OFF mode is selected, the Lock function will be OFF. If you 

press 

 and 

 key simultaneously, the “Lock” status can 

be released and the controller will be back to the previous 
display. 

OFF 

OUT: Output value display and output value adjustment in 
manual tuning control (This function is not available in 
ON/OFF control or Auto-tuning setting) 

CT: In case of using an external current transformer (CT), the 
controller displays the current value being measured by CT, if 
the control output is ON 

Read only

2. Regulation Mode: Set the control parameters 

LED Display

Explanation 

Default

AT: Auto-tuning setting. When AT key is set to ON (

), 

the execution of the PID auto-tuning function is automatically 
started. (PID control) 

OFF 

P: Proportional Band (PID control) 

47.6 

I: Integral Time (PID control) 

260 

D: Derivative Time (PID control) 

41 

PdoF: Offset output when P or PD control function is ON. (PID 
control and Ki=0) 

ioF: Default value of integral volume when PID control function 
is ON and integral time constant is not equal to 0(zero). AT 
can automatically set this parameter. (PID control and Ki

0) 

 

HTS: Set Heating hysteresis when ON/OFF control function is 
ON. 

 

CTS: Set Cooling hysteresis when ON/OFF control function is 
ON. 

 

HTPD: PID heating control cycle setting (PID control) 

 

CLPD: PID cooling control cycle setting (PID control) 

Output 
Selection: 
V: 4 sec. 
R: 20 sec. 

 

TPOF: Regulate temperature deviation value 

 

CRHI: Regulate 20mA output deviation value 

 

CRLO: Regulate 4mA output deviation value 

3. Initial Setting Mode: Initial settings of the controller and communication   

parameters 

LED Display

Explanation 

Default

 

INPUT: Select input temperature sensor type  
(Please refer to the contents of the “Temperature Sensor Type 
and Temperature Range” for detail)

 

PT2 

  UNIT: Temperature display unit, 

o

C (

) and 

o

F (

o

 

T-HIGH: Upper limit for temperature range 

500.0 

 

T-LOW: Lower limit for temperature range 

-20.0 

CONTROL: Control method setting on the SV display: PID 

(

), ON/OFF control (

), or manual tuning 

(

PID 

SWITCH: Select Heating (

) or Cooling (

action 

HEAT 

AL1 SET: Alarm 1 setting 

AL2 SET: Alarm 2 setting 

C WE: Write-in function disable/enable 
(Displayed when using serial communication) 

OFF 

C NO: Address setting 
(Displayed when using serial communication) 

BPS: Baud rate setting 
(Displayed when using serial communication) 

9600 

LENGTH: Data length setting 
(Displayed when using serial communication) 

PARITY: Parity bit setting  
(Displayed when using serial communication) 

STOP BIT: Stop bit setting 
(Displayed when using serial communication) 

Note: Alarm values should be set in the initial setting mode so AL1H, AL1L, AL2H 

and AL2L would display in operation mode. 

 

Heating and Cooling Control 

 

Temperature control is achieved either by heating or by cooling. The heating function 
starts when the process temperature (PV) is going down, and the cooling function when 
the temperature is getting high. It is impossible to operate both functions simultaneously 
in this controller.

 

 

Temperature Sensor Type and Temperature Range 

 

Input Temperature Sensor Type

Register 

Value 

LED 

Display 

Temperature 

Range 

Platinum resistance (Pt100) type3 

15 

 

0.0 to 100.0

 

o

Platinum resistance (Pt100) type2 

14 

 

-20.0 to 500.0

 

o

Platinum resistance (Pt100) type1 

13 

 

-200 to 600

 

o

Platinum resistance (JPt100) type2

12 

 

0.0 to 100.0

 

o

Platinum resistance (JPt100) type1

11 

 

-20.0 to 400.0

 

o

Thermocouple (TC) B type 

10 

 

100 to 1800

 

o

Thermocouple (TC) S type 

 

0 to 1700

 

o

Thermocouple (TC) R type 

 

0 to 1700

 

o

Thermocouple (TC) N type 

 

-200 to 1300

 

o

Thermocouple (TC) E type 

 

0 to 600

 

o

Thermocouple (TC) T type2 

 

-20.0 to 400.0

 

o

Thermocouple (TC) T type1 

 

-200 to 400

 

o

Thermocouple (TC) J type2 

 

-20.0 to 400.0

 

o

Thermocouple (TC) J type1 

 

-100 to 850

 

o

Thermocouple (TC) K type2 

 

-20.0 to 500.0

 

o

Thermocouple (TC) K type1 

 

-200 to 1300

 

o

Thermocouple (TC) L type 

16 

 

-200 to 850

 

o

Thermocouple (TC) U type 

17 

 

-200 to 500

 

o

Thermocouple (TC) Txk type 

18 

 

-200 to 800

 

o

 

 

Input Error Indication 

 

Setting 

value

Temperature sensor is 

not connected 

Measured temperature value 

exceeds the temperature range

Unknown input 

PV 

 

 

 

SV 

 

 

 

 

Operation 

 

There are three modes of operation: operation, regulation and initial setting. When power 

is applied, controller gets into the operation mode. Press the 

 key to switch to 

regulation mode. If the 

 

key is pressed for more than 3 seconds, controller will switch 

to the initial setting mode. Pressing the 

 key while in the regulation mode or initial 

setting mode, forces the controller to return to the operation mode. 
PV/SV: Sets the temperature set point and displays the temperature process value. Use 

the 

 and 

 

keys to set the temperature set point. 

Setting method: While in any function mode, press the 

 

key to select the desired 

function and use the 

 and 

 

keys to change settings. Press 

 key to save the 

changes. 
The next flow chart shows how to switch for settings and internal functions:

 

Regulation

Mode

Operation

Mode

Initial Setting

Mode

Press              key less than 3 sec

Press              key

Press              key

Press              key more than 3 sec

 

Regulation

Mode

 

Operation

Mode

 

Initial Setting

Mode

 

Press

Auto-tuning

(In PID control and RUN mode)

Set PID PB
(In PID control)

Set PID Ti 

(In PID control)

Set PID Td

(In PID control)

P/PD control Offset setting

(When PID control is ON and Ki 0,
set the value of PdoF; If Ki 0, AT

will automatically set the value of
ioF

=

Heating/Cooling hysteresis

(In ON/OFF control)

or

(In PID control)

Set Heating/Cooling 
control cycle

or

or

Regulate temperature

deviation value

Regulate 20mA output
deviation value

(Display when current output)

Return to auto-tuning setting

Regulate 4mA output
deviation value

(Display when current output)

Press

Press

Press

Press

Press

Press

Press

Press

Press

Control setting 
RUN or STOP

Upper-limit alarm 1

Use

set temperature of target

Lower-limit alarm 1

(This parameter is available only
 when ALA1 function enables)

Upper-limit alarm 2

Lower-limit alarm 2

Setting lock mode

Return to temperature display

(This parameter is available only
 when ALA1 function enables)

(This parameter is available only

 when ALA2 function enables)

(This parameter is available only
 when ALA2 function enables)

to

Output value display

and adjust

Press

Press

Press

Press

Press

Press

Press

Press

Press

CT function is selected

In case of using an external CT, 
the controller displays the current
value being measured by CT, if 

the control output is ON. 

Set input type

Set temperature unit

Set upper-limit of
temperature range

Set lower-limit of

temperature range

Select control method

Select heating/cooling

functions

Alarm 1 setting

Alarm 2 setting

Write-in function
disable/enable

(Displayed when using serial
 communication)

Baud rate setting

Data length setting

Parity bit setting

Address setting

Press

Press

Press

Press

Press

Press

Press

Press

Press

Press

Press

Press

Press

(Displayed when using serial
 communication)

(Displayed when using serial

 communication)

(Displayed when using serial

 communication)

(Displayed when using serial
 communication)

Stop bit setting

Return to input type setting

Press

(Displayed when using serial
 communication)

 

 

 

 