Delta DRP024V240W3BA Installation Notes Download Page 1

DEUTSCH

Anleitung

ENGLISH

Installation notes

5.2. Output connection (Fig. 1 (2))

Use the “+” and “-“ screw connections to establish the 24Vdc connection. The output 

provides 24Vdc. The output voltage can be adjusted from 24 to 28Vdc on the potentiometer. 

The green LED DC OK displays correct function of the output (Fig. 1 (4)). The device has 

a short circuit and overload protection and an over voltage protection limited to 35Vdc.

5.3. Output characteristic curve 

The device functions normal under operating line and load conditions. In the event of 

a short circuit or over load the output voltage and current collapses (I

O/L

 or I

S/C

 is > I

surge

 

(150%)). The secondary voltage is reduced and bounces until short circuit or over load on 

the secondary side has been removed.

5.4. Thermal behavior (Fig. 6)

In the case of ambient temperatures above +50°C (Vertical) or +40°C (Horizontal), the 

output capacity has to be reduced by 2.5% per degree Celsius increase in temperature, 

and at +70°C to +80°C (Vertical) or +60°C to +70°C (Horizontal), the output capacity has 

to be reduced by 5% per degree Celsius increase in temperature. If the output capacity 

is not reduced when T

Amb

 > 50°C (Vertical) or > 40°C (Horizontal), the device will run into 

thermal protection by switching off i.e. device will go in bouncing mode and will recover 

when ambient temperature is lowered or load is reduced as far as necessary to keep device 

in working condition.

 

The internal fuse must not be replaced by the user. 

In case of internal defect, return the unit for inspection to 

the manufacturer.

ENGLISH

Technical data

Input (AC)

Nominal input voltage and frequency

3 x 400-500Vac / 50-60Hz

Voltage range

320-600Vac

Frequency

47-63Hz

Nominal current 

< 0.75A @ 3 x 400Vac

Inrush current limitation (+25°C) typ.

< 40A @ 3 x 400Vac & 3 x 500Vac, AC Source capability 

up to 3KVA

< 60A @ 3 x 400Vac & 3 x 500Vac, AC Source capability 

up to 18KVA

Mains buffering at nominal load (typ.)

> 20ms @ 3 x 400Vac, > 40ms @ 3 x 500Vac 

Turn-on time

< 1 sec.

Internal fuse

T 3.15A / 500V, 600V

- LITTELFUSE: Type 477 Rated 3.15A/600Vac for 

UL E10480 and 3.15A/500Vac for Europe

- CONQUER: Type UDE/UDE-A Rated 3.15A/500Vac for 

both UL E82636 and Europe

Leakage current

< 3.5mA

Output (DC)

Nominal output voltage U

N

 / tolerance

24Vdc ± 2%

Adjustment range of the voltage

24-28Vdc (maximum power ≤ 240W)

Nominal current

10A

Derating

> 50°C (2.5% / °C), > 70°C (5% / °C) in Vertical

> 40°C (2.5% / °C), > 60°C (5% / °C) in Horizontal

Startup with capacitive loads

Max. 10,000µF

Max. power dissipation idling / nominal load approx.

26.7W

Efficiency (at 400Vac & 500Vac and nominal values)

> 90.0% @ 3 x 400Vac & 3 x 500Vac

Residual ripple / peak switching (20MHz) (at nominal values)

< 50mVpp / < 150mVpp

Parallel operation

DRR-20A / DRR-40A / With ORing diode

General Data

Type of housing

Aluminium

Signals

Green LED DC OK

MTBF

> 300,000 hrs. as per Telcordia

Dimensions (L x W x H)

121mm x 70mm x 117.3mm

Weight

0.89kg

Connection method

Screw connection

Stripping length

7mm

Operating temperature (surrounding air temperature)

-25°C to +80°C (Refer to Fig. 6)

Storage temperature

-25°C to +85°C

Humidity at +25°C, no condensation

< 95% RH

Vibration (non-operating)

10 to 500Hz @ 30m/S² (3G peak); displacement of 

0.35mm; 60 min. per axis for all X, Y, Z directions in acc. 

with IEC60068-2-6

Shock (in all directions)

30G (300m/S²) in all directions according to

IEC60068-2-27

Pollution degree

2

Altitude (operating)

2000 Meters for industrial application

2500 Meters for ITE application

Climatic class

3K3 according to EN60721

Certification and Standards

Electrical equipments of machines

IEC60204-1 (over voltage category III)

Electronic equipment for use in electrical power installations

EN62477-1 / IEC62103

Safety entry low voltage

PELV (EN60204), SELV (EN60950)

Electrical safety (of information technology equipment)

SIQ to EN60950-1, UL/C-UL recognized to UL60950-1 

and CSA C22.2 No. 60950-1, CB scheme to IEC60950-1

Industrial control equipment

UL/C-UL listed to UL508 and CSA C22.2 No.107.1-01, 

CSA to CSA C22.2 No. 107.1-01 (File No.181564)

Hazardous location / ATEX 

(For DRP024V240W3BA)

cCSAus to CSA C22.2 No.213-M1987, ANSI / ISA 

12.12.01:2007 [Class I, Division 2, Group A,B,C,D T4,  

Ta = -25°C to +80°C for Vertical (> +50°C derating) and  

-25°C to +70°C for Horizontal (> +40°C derating)]
EN60079-0:2012, EN60079-15:2010 [      II 3G Ex nA 

IIC T4 Gc, Ta = -25°C to +80°C for Vertical (> +50°C 

derating) and -25°C to +70°C for Horizontal (> +40°C 

derating)]

     II 3G ATEX (For DRP024V240W3BA)

Certificate No. EPS 13 ATEX 1 575 X

Protection against electric shock

DIN57100-410

CE

In conformance with EMC directive and low voltage 

directive

For DRP024V240W3BA:

 

In conformance with Equipment for explosive 

atmospheres (ATEX) directive

Component Power Supply for general use

EN61204-3

ITE

EN55022, EN61000-3-2, EN61000-3-3, EN55024

Industrial

EN55011

Limitation of mains harmonic currents

EN61000-3-2

Safety and Protection

Transient surge voltage protection

VARISTOR

Current limitation at short-circuits approx.

I

surge

 = 150% of Po

max

 typically

Surge voltage protection against internal surge voltages

Yes

Isolation voltage:

Input / output

Input / PE

Output / PE

4.0KVac

2.0KVac

1.5KVac

Protection degree

IP20

Safety class

Class I with PE connection

DEUTSCH

Technische Daten

Eingangskennwerte (AC)

Nennspannung en frequentie

3 x 400-500Vac / 50-60Hz

Spannungsbereich

320-600Vac

Frequenzbereich

47-63Hz

Nennstrom 

< 0,75A bei 3 x 400Vac

Einschaltstrombegrenzung (+25°C) typ.

< 40A bei 3 x 400Vac & 3 x 500Vac, Spannungsquelle 

bis zu 3KVA

< 60A bei 3 x 400Vac & 3 x 500Vac, Spannungsquelle 

bis zu 18KVA

Netzausfallüberbrückung bei Nennlast (typ.)

> 20ms bei 3 x 400Vac, > 40ms bei 3 x 500Vac

Einschaltzeit

< 1 sec.

Interne Sicherung

T 3,15A / 500V, 600V

- LITTELFUSE: Type 477 Rated 3,15A/600Vac for 

UL E10480 and 3,15A/500Vac for Europe

- CONQUER: Type UDE/UDE-A Rated 3,15A/500Vac for 

both UL E82636 and Europe

Ableitstrom

< 3,5mA

Ausgangskennwerte (DC)

Nennausgangsspannung U

N

 / Toleranz

24Vdc ± 2%

Einstellbereich der Ausgangsspannung

24-28Vdc (max. Leistung ≤ 240W)

Nennstrom

10A

Derating (Leistungsherabsetzung)

> 50°C (2,5% / °C), > 70°C (5% / °C) Vertikal

> 40°C (2,5% / °C), > 60°C (5% / °C) Horizontal

Anlaufen bei Kapazitiven Lasten

Max. 10.000µF

Max. Verlustleistung Leerlauf/Nennlast

26,7W

Wirkungsgrad (bei 400Vac & 500Vac und Nennwerten)

> 90,0% bei 3 x 400Vac & 3 x 500Vac

Restwelligkeit / Schaltspitzen (20MHz) (bei Nennwerten)

< 50mVpp / < 150mVpp

Parallelschaltbarkeit

DRR-20A / DRR-40A / mit ORing Diode

Allgemeine Kennwerte

Gehäusetyp

Aluminium

Statusanzeige

Grüne LED „DC OK“

MTBF (mittlere Betriebszeit zwischen Ausfällen)

> 300.000 Std., entsprechend Telcordia

Abmessungen (B x H x T)

121mm x 70mm x 117,3mm

Gewicht

0,89kg

Art der Anschlussklemme

Schraubanschluss

Abisolierlänge

7mm

Betriebstemperaturbereich (Umgebungstemperatur)

-25°C bis +80°C (Leistungsherabsetzung gemäß Abb. 6)

Lagertemperaturbereich

-25°C bis +85°C

Luftfeuchte bei +25°C, keine Betauung

< 95% relative Luftfeuchte

Vibration (außer Betrieb)

10 bis 500Hz, Beschl. 30m/S², 0,35mm

Einzelamplitude (3G max.) für 60 min. in X, Y & Z 

Richtung, gemäß IEC60068-2-6

Stoßfestigkeit (in alle Richtungen)

30G (300m/S²) in alle Richtungen gemäß 

IEC60068-2-27

Verschmutzungsgrad

2

Höhe (Betrieb)

2000 Meters for industrial application

2500 Meters for ITE application

Klimaklasse

3K3 gemäß EN60721

Zertifizierung und Normen

Elektrische Ausrüstung von Maschinen

IEC60204-1 (Überspannungskategorie III)

Ausrüstung von Starkstromanlagen mit elektronischen 

Betriebsmitteln

EN62477-1 / IEC62103

Schutzkleinspannung

PELV (EN60204), SELV (EN60950)

Elektrische Sicherheit (von Einrichtungen der 

Informationstechnik)

SIQ nach EN60950-1, UL/C-UL anerkannt nach 

UL60950-1 und CSA C22.2 Nr. 60950-1, Prüfprotokoll 

und -bericht nach IEC60950-1

Industrielle Regeleinrichtungen

UL/C-UL gelistet nach UL508 und CSA C22.2 Nr.107.1-01, 

CSA nach CSA C22.2 Nr.107-1-01 (File Nr.181564)

Gefährlicher Bereich / ATEX 

(Für DRP024V240W3BA)

cCSAus bis CSA C22.2 No.213-M1987, ANSI / ISA 

12.12.01:2007 [Klasse I, Division 2, Gruppe A,B,C,D T4,  

Ta = -25°C bis +80°C Vertikal (> +50°C derating) und 

-25°C bis +70°C Horizontal (> +40°C derating)]
EN60079-0:2012, EN60079-15:2010 [      II 3G Ex nA IIC 

T4 Gc, Ta = -25°C bis +80°C Vertikal (> +50°C derating) 

und -25°C bis +70°C Horizontal (> +40°C derating)]

      II 3G ATEX (Für DRP024V240W3BA)

Zertifikat Nr. EPS 13 ATEX 1 575 X

Schutz gegen elektrischen Schlag

DIN57100-410

EC

In Konformität zur EMV-Richtlinie und 

Niederspannungsrichtlinie

Für DRP024V240W3BA:

 

In Konformität zur Geräte zur Verwendung in 

explosionsgefährdeten Bereichen (ATEX) Richtlinie

Komponenten-Netzteil zur allgemeinen Verwendung

EN61204-3

ITE

EN55022, EN61000-3-2, EN61000-3-3, EN55024

Industrial

EN55011

Begrenzung der Netzoberschwingungen

EN61000-3-2

Sicherheit und Schutzeinrichtungen

Überspannungsschutz gegen transiente 

Überspannungen

VARISTOR

Strombegrenzung bei Kurzschluss

I

Überstrom

 = 150% der max. Ausgangsleistung

Überspannungsschutz gegen interne Überspannungen

Ja

Isolationsspannung

Eingang / Ausgang

Eingang / Schutzleiter

Ausgang / Schutzleiter

4,0KVac

2,0KVac

1,5KVac

Schutzart

IP20

Schutzklasse

Klasse I mit Schutzleiteranschluss

1. Safety instructions

•   Switch main power off before connecting or disconnecting the device. Risk of explosion!

•   To guarantee sufficient convection cooling, keep a distance of 50mm above and below 

 

  the device as well as a lateral distance of 5mm (for Vertical Mounting) or 50mm (for  

  Horizontal Mounting) to other units.

•   Note  that  the  enclosure  of  the  device  can  become  very  hot  depending  on  the 

 

  ambient  temperature  and  load  of  the  power  supply.  Risk  of  burns!

•   The main power must be turned off before connecting or disconnecting wires to the 

 

 terminals.

•   Do not introduce any objects into the unit!

•   Dangerous  voltage  present  for  at  least  5  minutes  after  disconnecting  all  sources  of 

 

 power.

•  The  power  supplies  are  built  in  units  and  must  be  installed  in  a  cabinet  or  room 

 

  (condensation free environment and indoor location) that is relatively free of conductive  

 contaminants.

• 

CAUTION:

 

  “FOR USE IN A CONTROLLED ENVIRONMENT”.

For DRP024V240W3BA:

•  The power supplies unit must be installed in minimum IP54 enclosure or cabinet in the 

 

  final installation. The enclosure or cabinet must comply with EN60079-0 or EN60079-15.

•  Warning:  Explosion  Hazard  -  Substitution  of  components  may  impair  suitability  for 

 

  Class I, Division 2.

•  Warning:  Explosion  Hazard  -  Do  not  disconnect  equipment  or  adjust  potentiometer 

 

  unless the power has been switched off or the area is known to be non-hazardous.

2. Device description (Fig. 1)

(1) Input terminal block connector

(2) Output terminal block connector

(3) DC voltage adjustment potentiometer

(4) DC OK control LED (green)

(5) Universal mounting rail system

3. Mounting (Fig. 2)

The power supply unit can be mounted on 35 mm DIN rails in accordance with EN 60715. 

For Vertical Mounting, the device should be installed with input terminal block on the 

bottom. For Horizontal Mounting, the device should be installed with input terminal block 

on the left side.

Each device is delivered ready to install. 

Snap on the DIN rail as shown in Fig. 2:

 

1. Tilt the unit slightly upwards and put it onto the DIN rail.

 

2. Push downwards until stopped.

 

3. Press against the bottom front side for locking.

 

4. Shake the unit slightly to ensure that it is secured.

4. Dismounting (Fig. 3)

To uninstall, pull or slide down the latch as shown in Fig. 3. Then, slide the PSU in the 

opposite direction, release the latch and pull out the PSU from the rail.

5. Connection

The terminal block connectors allow easy and fast wiring. 

You can use flexible (stranded wire) or solid cables with the following cross sections:

 

Table 1

To secure reliable and shock proof connections, the stripping length should be 7mm (see 

Fig. 4 (1)). Please ensure that wires are fully inserted into the connecting terminals as 

shown in Fig. 4 (2).

In accordance to EN60950 / UL60950, flexible cables require ferrules.

Use appropriate copper cables designed to sustain operating temperature of: 

 1. 

60°C, 60°C / 75°C for USA

 2. 

At least 75°C for ambient not exceeding 40°C, and 90°C for ambient exceeding 

          40°C for Canada.

5.1. Input connection (Fig. 1, Fig. 5)

Use L1, L2, L3 and PE connections of input terminal connector (see Fig. 5) to establish 

the 3 x 400-500Vac connection. Fig. 5 shows the connection to the various network types.

In the event of a phase failure, unrestricted operation is possible with nominal capacity.

The unit is protected with internal fuse (not replaceable) at L pin and it has been tested and 

approved on 20A (UL) and 16A (IEC) branch circuits without additional protection device. 

An external protection device is only required if the supplying branch has an ampacity 

greater than above. Thus, if an external protective device is necessary, or, utilized, a 

minimum value of 13A B- or 6A C- characteristic breaker should be used.

Figure 6

Figure 2

Figure 3

Figure 4

Figure 1

Figure 5

7 mm

1

2

1

2

3

(2)

(1)

(4)

(3)

(5)

1

2

3

7 mm

1

2

1

2

3

(2)

(1)

(4)

(3)

(5)

1

2

3

7 mm

1

2

1

2

3

(2)

(1)

(4)

(3)

(5)

1

2

3

7 mm

1

2

1

2

3

(2)

(1)

(4)

(3)

(5)

1

2

3

5.2. Anschluss der Ausgangsklemmen (Abb. 1 (2))

Verwenden Sie die Schraubklemmen „+“ und „-“, um den 24Vdc-Anschluss herzustellen. Am 

Ausgang stehen 24Vdc zur Verfügung. Die Ausgangsspannung kann am Potentiometer zwischen 

24 und 28Vdc eingestellt werden. Die grüne LED “DC OK” zeigt die korrekte Funktion des Ausgangs 

an (Abb. 1 (4)). Das Gerät verfügt über einen Kurzschluss-, Überlast- und Überspannungsschutz, 

der auf 35Vdc begrenzt ist.

5.3. Ausgangskennlinie 

Das Gerät funktioniert normal, solange die Netz- und Lastbedingungen im Betriebsbereich des 

Geräts liegen. Im Fall eines Kurzschlusses oder einer Überlast fallen Ausgangsspannung und –

strom ab (bei I

Überlast

 bzw. I

Kurzschluss

 > I

Überstrom

 (150%)). Die Sekundärspannung wird dabei so lange 

abgesenkt, bis der sekundärseitige Kurzschluss oder die Überlast behoben sind. 

5.4. Temperaturverhalten (Abb. 6)

Beträgt die Umgebungstemperatur über +50°C (Vertikal) oder +40°C (Horizontal), muss die 

Ausgangsleistung entsprechend dem Temperaturanstieg um 2,5% pro Celsius reduziert werden 

und bei +70°C bis +80°C (Vertikal) oder +60°C bis +70°C (Horizontal), muss die Ausgangsleistung 

entsprechend  dem  Temperaturanstieg  um  5%  pro  Celsius  reduziert  werden.  Wird  die 

Ausgangsleistung bei einer Umgebungstemperatur von > 50°C (Vertikal) oder > 40°C (Horizontal) 

nicht herabgesetzt, löst der thermische Überlastschutz aus und schaltet das Gerät ab. Das Gerät 

bleibt dann so lange in diesem Zustand bis die Umgebungstemperatur oder die Last soweit 

abgesenkt wurde, dass das Gerät wieder im Normalbetrieb arbeiten kann.

 

Die interne Sicherung darf nicht vom Anwender ausge-

tauscht werden. Schicken Sie das Gerät im Fall eines 

Defekts zur Reparatur zum Hersteller zurück.

1. Sicherheitsvorschriften

•  Schalten Sie die Netzspannung ab, bevor Sie das Gerät an das Netz anschließen oder es vom 

 

  Netz trennen. Explosionsgefahr!

•  Um eine ausreichende Konvektionskühlung zu gewährleisten, halten Sie ober und unterhalb 

 

  des Gerätes einen Abstand von 50mm ein. Bei vertikaler Montage sollte ein seitlicher Abstand  

  von 5mm zu anderen Geräten gewährleistet sein, bei horizontaler Montage ein Abstand von  

 50mm.

•  Beachten  Sie,  dass  das  Gehäuse  des  Gerätes  sehr  heiß  werden  kann,  abhängig  von  der 

 

  Umgebungstemperatur und der Last an der Spannungsversorgung. 

  Verbrennungsgefahr!

•  Verbinden und trennen Sie die Anschlüsse nur, wenn die Spannung abgeschaltet ist!

•  Führen Sie keine Objekte in das Gerät ein!

•  Nachdem das Gerät von allen Spannungsquellen getrennt wurde liegt über einen Zeitraum von 

 

  mindestens 5 Minuten noch gefährliche Spannung an dem Gerät an.

•  Die Netzgeräte sind eingebaute Geräte und müssen in einem Schrank oder Raum (Innenraum 

 

  ohne Kondensation) installiert werden, der relativ frei von leitenden Schmutzstof fen ist.

• 

VORSICHT:

 

  „Zum Einsatz nur im Innenbereich“.

Für DRP024V240W3BA:

•  Die Stromversorgung muss bei der endgültigen Installation mindestens in einem IP54 Gehäuse 

 

  oder Schrank montiert werden. Das Gehäuse oder der Schrank müssen die EN60079-0 oder  

  EN60079-15 Norm erfüllen.

•  Warnung:  Explosionsgefahr  –  Das  Austauschen  von  Komponenten  kann  die  Eignung  für 

 

  Klasse I, Abteilung 2 beeinträchtigen.

•   Warnung: Explosionsgefahr – Anlage nur dann abtrennen oder potentiometer einstellen, wenn 

 

  die Stromversorgung unterbrochen oder die Umgebung als nicht gefährlich eingestuft wurde.

2. Gerätebeschreibung (Abb. 1)

(1)  Eingangsklemmen

(2)  Ausgangsklemmen

(3)  Potentiometer zur Einstellung der DC-Ausgangsspannung

(4)  LED für Statusanzeige „DC OK“ (grün)

(5)  Universelles Montageschienensystem

3. Montage (Abb. 2)

Das Netzteil kann auf 35mm DIN-Schienen gemäß EN60715 montiert werden. Bei vertikalem 

Einbau sollte das Gerät so eingebaut werden, dass der Klemmenleistenblock unten ist. Beim 

horizontalen Einbau sollte das Gerät so eingebaut werden, dass der Klemmenleistenblock auf 

der linken Seite ist.
Jedes Gerät wird installationsfertig geliefert.

Einrasten des Geräts in DIN-Schiene, wie in Abb. 2 dargestellt:

 

1. Kippen Sie das Gerät leicht nach oben und setzen Sie es auf die DIN-Schiene auf.

 

2. Kippen Sie das Gerät jetzt wieder nach unten bis zum Anschlag am unteren Teil der    

 

    Schiene.

 

3. Drücken Sie nun den unteren Teil des Gerätes so fest gegen die Schiene bis das Gerät auf  

 

    der Schiene einrastet.

 

4. Rütteln Sie leicht am Gerät, um zu überprüfen, ob es korrekt eingerastet ist.

4. Demontage (Abb. 3)

Ziehen Sie zur Demontage den Einrasthebel mit einem Schraubendreher nach unten, wie in Abb. 3 

dargestellt. Kippen Sie das Netzteil in die entgegengesetzte Richtung nach oben, klinken Sie den 

Einrasthebel aus und nehmen Sie das Netzteil nach oben von der DIN-Schiene ab.

5. Anschluss

Die Anschlussklemmen erlauben eine schnelle und einfache Verdrahtung des Geräts. Sie können 

flexible (feindrähtige Leitung) oder feste Kabel mit folgenden Querschnitt verwenden:

 

Tabelle 1

Um sichere und stoßfeste Anschlüsse gewährleisten zu können, sollte die Abisolierlänge 7mm 

betragen (siehe Abb. 4 (1)). Bitte sorgen Sie dafür, dass die Kabel vollständig in die Anschluss-

klemmen eingeführt werden, siehe Abb. 4 (2).

Gemäß EN60950 / UL60950 sind für flexible Kabel Aderendhülsen erforderlich.

Verwenden Sie geeignete Kupferkabel, die für Betriebstemperaturen von mindestens 60°C, 

60°C / 75°C für die USA und mindestens 75°C für Umgebungstemperaturen unter 40°C und 

mindestens 90°C für Umgebungstemperaturen über 40°C für Kanada ausgelegt sind, um die UL-

Anforderungen erfüllen zu können.

5.1. Anschluss der Eingangsklemmen (Abb. 1, Abb. 5)

Verwenden Sie die Eingangsklemmen L1, L2, L3 und PE (Schutzleiter), um den 3-phasigen 

400-500Vac-Anschluss herzustellen. Abb. 5 zeigt den Anschluss an die unterschiedlichen 

Netztypen.
Im Fall eines Phasenausfalls ist ein uneingeschränkter Betrieb des Gerätes bei Nennleistung noch 

möglich.
Das Gerät verfügt über eine interne, nicht austauschbare Sicherung am L-Pin. Es wurde getestet 

und zugelassen mit handels üblichen Sicherungen von 20 A (UL) und 16 A (IEC) ohne weitere 

Schutzeinrichtungen. Ein externer Schutz ist nur dann notwendig, wenn der Nennstrom größer als 

20 A ist. Falls ein externer Schutz zur Anwendung kommt, sollte mindestens eine Sicherung des 

Typs 13 A -B oder 6 A -C verwendet werden. 

Siehe 

Abb. 1:

Flexibel / Starr

Anzugsmoment

(mm²)

(AWG)

(Kgf-cm)

(lb in)

(1)

0,82-3,3

18-12

9,3

8,1

(2)

1,3-3,3

16-12

6,2

5,4

Refer to 

Fig. 1:

        Stranded / Solid

                Torque

(mm²)

(AWG)

(Kgf-cm)

(lb in)

(1)

0.82-3.3

18-12

9.3

8.1

(2)

1.3-3.3

16-12

6.2

5.4

0

10

20

30

40

50

60

70

80

90

100

110

-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80

Pe

rc

en

ta

ge

 o

f M

ax

 L

oa

(%

)

Surrounding Air Temperature 

(

o

C)

Vertical Mounting

Horizontal Mounting

Power Derating Curve for PSU

TN-C

TT

IT

TN-S

L1

    

L2

    

L3 

  

PE

+

L1

L2

L3

N

PE

L1

    

L2

    

L3 

  

PE

+

L1

L2

L3

PEN

L1

    

L2

    

L3 

  

PE

+

L1

L2

L3

N

L1

    

L2

    

L3 

  

PE

+

L1

L2

L3