Installation notes
5.2. Output connection (Fig. 1 (2))
Use the “+” and “-“ screw connections to establish the 24Vdc connection. The output
provides 24Vdc. The output voltage can be adjusted from 24 to 28Vdc on the potentiometer.
The green LED DC OK displays correct function of the output (Fig. 1 (4)). The device has
a short circuit and overload protection and an over voltage protection limited to 35Vdc.
5.3. Output characteristic curve
The device functions normal under operating line and load conditions. In the event of
a short circuit or over load the output voltage and current collapses (I
O/L
or I
S/C
is > I
surge
(150%)). The secondary voltage is reduced and bounces until short circuit or over load on
the secondary side has been removed.
5.4. Thermal behavior (Fig. 6)
In the case of ambient temperatures above +50°C (Vertical) or +40°C (Horizontal), the
output capacity has to be reduced by 2.5% per degree Celsius increase in temperature,
and at +70°C to +80°C (Vertical) or +60°C to +70°C (Horizontal), the output capacity has
to be reduced by 5% per degree Celsius increase in temperature. If the output capacity
is not reduced when T
Amb
> 50°C (Vertical) or > 40°C (Horizontal), the device will run into
thermal protection by switching off i.e. device will go in bouncing mode and will recover
when ambient temperature is lowered or load is reduced as far as necessary to keep device
in working condition.
The internal fuse must not be replaced by the user.
In case of internal defect, return the unit for inspection to
the manufacturer.
ENGLISH
Technical data
Input (AC)
Nominal input voltage and frequency
3 x 400-500Vac / 50-60Hz
Voltage range
320-600Vac
Frequency
47-63Hz
Nominal current
< 0.75A @ 3 x 400Vac
Inrush current limitation (+25°C) typ.
< 40A @ 3 x 400Vac & 3 x 500Vac, AC Source capability
up to 3KVA
< 60A @ 3 x 400Vac & 3 x 500Vac, AC Source capability
up to 18KVA
Mains buffering at nominal load (typ.)
> 20ms @ 3 x 400Vac, > 40ms @ 3 x 500Vac
Turn-on time
< 1 sec.
Internal fuse
T 3.15A / 500V, 600V
- LITTELFUSE: Type 477 Rated 3.15A/600Vac for
UL E10480 and 3.15A/500Vac for Europe
- CONQUER: Type UDE/UDE-A Rated 3.15A/500Vac for
both UL E82636 and Europe
Leakage current
< 3.5mA
Output (DC)
Nominal output voltage U
N
/ tolerance
24Vdc ± 2%
Adjustment range of the voltage
24-28Vdc (maximum power ≤ 240W)
Nominal current
10A
Derating
> 50°C (2.5% / °C), > 70°C (5% / °C) in Vertical
> 40°C (2.5% / °C), > 60°C (5% / °C) in Horizontal
Startup with capacitive loads
Max. 10,000µF
Max. power dissipation idling / nominal load approx.
26.7W
Efficiency (at 400Vac & 500Vac and nominal values)
> 90.0% @ 3 x 400Vac & 3 x 500Vac
Residual ripple / peak switching (20MHz) (at nominal values)
< 50mVpp / < 150mVpp
Parallel operation
DRR-20A / DRR-40A / With ORing diode
General Data
Type of housing
Aluminium
Signals
Green LED DC OK
MTBF
> 300,000 hrs. as per Telcordia
Dimensions (L x W x H)
121mm x 70mm x 117.3mm
Weight
0.89kg
Connection method
Screw connection
Stripping length
7mm
Operating temperature (surrounding air temperature)
-25°C to +80°C (Refer to Fig. 6)
Storage temperature
-25°C to +85°C
Humidity at +25°C, no condensation
< 95% RH
Vibration (non-operating)
10 to 500Hz @ 30m/S² (3G peak); displacement of
0.35mm; 60 min. per axis for all X, Y, Z directions in acc.
with IEC60068-2-6
Shock (in all directions)
30G (300m/S²) in all directions according to
IEC60068-2-27
Pollution degree
2
Altitude (operating)
2000 Meters for industrial application
2500 Meters for ITE application
Climatic class
3K3 according to EN60721
Certification and Standards
Electrical equipments of machines
IEC60204-1 (over voltage category III)
Electronic equipment for use in electrical power installations
EN62477-1 / IEC62103
Safety entry low voltage
PELV (EN60204), SELV (EN60950)
Electrical safety (of information technology equipment)
SIQ to EN60950-1, UL/C-UL recognized to UL60950-1
and CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial control equipment
UL/C-UL listed to UL508 and CSA C22.2 No.107.1-01,
CSA to CSA C22.2 No. 107.1-01 (File No.181564)
Hazardous location / ATEX
(For DRP024V240W3BA)
cCSAus to CSA C22.2 No.213-M1987, ANSI / ISA
12.12.01:2007 [Class I, Division 2, Group A,B,C,D T4,
Ta = -25°C to +80°C for Vertical (> +50°C derating) and
-25°C to +70°C for Horizontal (> +40°C derating)]
EN60079-0:2012, EN60079-15:2010 [ II 3G Ex nA
IIC T4 Gc, Ta = -25°C to +80°C for Vertical (> +50°C
derating) and -25°C to +70°C for Horizontal (> +40°C
derating)]
II 3G ATEX (For DRP024V240W3BA)
Certificate No. EPS 13 ATEX 1 575 X
Protection against electric shock
DIN57100-410
CE
In conformance with EMC directive and low voltage
directive
For DRP024V240W3BA:
In conformance with Equipment for explosive
atmospheres (ATEX) directive
Component Power Supply for general use
EN61204-3
ITE
EN55022, EN61000-3-2, EN61000-3-3, EN55024
Industrial
EN55011
Limitation of mains harmonic currents
EN61000-3-2
Safety and Protection
Transient surge voltage protection
VARISTOR
Current limitation at short-circuits approx.
I
surge
= 150% of Po
max
typically
Surge voltage protection against internal surge voltages
Yes
Isolation voltage:
Input / output
Input / PE
Output / PE
4.0KVac
2.0KVac
1.5KVac
Protection degree
IP20
Safety class
Class I with PE connection
DEUTSCH
Technische Daten
Eingangskennwerte (AC)
Nennspannung en frequentie
3 x 400-500Vac / 50-60Hz
Spannungsbereich
320-600Vac
Frequenzbereich
47-63Hz
Nennstrom
< 0,75A bei 3 x 400Vac
Einschaltstrombegrenzung (+25°C) typ.
< 40A bei 3 x 400Vac & 3 x 500Vac, Spannungsquelle
bis zu 3KVA
< 60A bei 3 x 400Vac & 3 x 500Vac, Spannungsquelle
bis zu 18KVA
Netzausfallüberbrückung bei Nennlast (typ.)
> 20ms bei 3 x 400Vac, > 40ms bei 3 x 500Vac
Einschaltzeit
< 1 sec.
Interne Sicherung
T 3,15A / 500V, 600V
- LITTELFUSE: Type 477 Rated 3,15A/600Vac for
UL E10480 and 3,15A/500Vac for Europe
- CONQUER: Type UDE/UDE-A Rated 3,15A/500Vac for
both UL E82636 and Europe
Ableitstrom
< 3,5mA
Ausgangskennwerte (DC)
Nennausgangsspannung U
N
/ Toleranz
24Vdc ± 2%
Einstellbereich der Ausgangsspannung
24-28Vdc (max. Leistung ≤ 240W)
Nennstrom
10A
Derating (Leistungsherabsetzung)
> 50°C (2,5% / °C), > 70°C (5% / °C) Vertikal
> 40°C (2,5% / °C), > 60°C (5% / °C) Horizontal
Anlaufen bei Kapazitiven Lasten
Max. 10.000µF
Max. Verlustleistung Leerlauf/Nennlast
26,7W
Wirkungsgrad (bei 400Vac & 500Vac und Nennwerten)
> 90,0% bei 3 x 400Vac & 3 x 500Vac
Restwelligkeit / Schaltspitzen (20MHz) (bei Nennwerten)
< 50mVpp / < 150mVpp
Parallelschaltbarkeit
DRR-20A / DRR-40A / mit ORing Diode
Allgemeine Kennwerte
Gehäusetyp
Aluminium
Statusanzeige
Grüne LED „DC OK“
MTBF (mittlere Betriebszeit zwischen Ausfällen)
> 300.000 Std., entsprechend Telcordia
Abmessungen (B x H x T)
121mm x 70mm x 117,3mm
Gewicht
0,89kg
Art der Anschlussklemme
Schraubanschluss
Abisolierlänge
7mm
Betriebstemperaturbereich (Umgebungstemperatur)
-25°C bis +80°C (Leistungsherabsetzung gemäß Abb. 6)
Lagertemperaturbereich
-25°C bis +85°C
Luftfeuchte bei +25°C, keine Betauung
< 95% relative Luftfeuchte
Vibration (außer Betrieb)
10 bis 500Hz, Beschl. 30m/S², 0,35mm
Einzelamplitude (3G max.) für 60 min. in X, Y & Z
Richtung, gemäß IEC60068-2-6
Stoßfestigkeit (in alle Richtungen)
30G (300m/S²) in alle Richtungen gemäß
IEC60068-2-27
Verschmutzungsgrad
2
Höhe (Betrieb)
2000 Meters for industrial application
2500 Meters for ITE application
Klimaklasse
3K3 gemäß EN60721
Zertifizierung und Normen
Elektrische Ausrüstung von Maschinen
IEC60204-1 (Überspannungskategorie III)
Ausrüstung von Starkstromanlagen mit elektronischen
Betriebsmitteln
EN62477-1 / IEC62103
Schutzkleinspannung
PELV (EN60204), SELV (EN60950)
Elektrische Sicherheit (von Einrichtungen der
Informationstechnik)
SIQ nach EN60950-1, UL/C-UL anerkannt nach
UL60950-1 und CSA C22.2 Nr. 60950-1, Prüfprotokoll
und -bericht nach IEC60950-1
Industrielle Regeleinrichtungen
UL/C-UL gelistet nach UL508 und CSA C22.2 Nr.107.1-01,
CSA nach CSA C22.2 Nr.107-1-01 (File Nr.181564)
Gefährlicher Bereich / ATEX
(Für DRP024V240W3BA)
cCSAus bis CSA C22.2 No.213-M1987, ANSI / ISA
12.12.01:2007 [Klasse I, Division 2, Gruppe A,B,C,D T4,
Ta = -25°C bis +80°C Vertikal (> +50°C derating) und
-25°C bis +70°C Horizontal (> +40°C derating)]
EN60079-0:2012, EN60079-15:2010 [ II 3G Ex nA IIC
T4 Gc, Ta = -25°C bis +80°C Vertikal (> +50°C derating)
und -25°C bis +70°C Horizontal (> +40°C derating)]
II 3G ATEX (Für DRP024V240W3BA)
Zertifikat Nr. EPS 13 ATEX 1 575 X
Schutz gegen elektrischen Schlag
DIN57100-410
EC
In Konformität zur EMV-Richtlinie und
Niederspannungsrichtlinie
Für DRP024V240W3BA:
In Konformität zur Geräte zur Verwendung in
explosionsgefährdeten Bereichen (ATEX) Richtlinie
Komponenten-Netzteil zur allgemeinen Verwendung
EN61204-3
ITE
EN55022, EN61000-3-2, EN61000-3-3, EN55024
Industrial
EN55011
Begrenzung der Netzoberschwingungen
EN61000-3-2
Sicherheit und Schutzeinrichtungen
Überspannungsschutz gegen transiente
Überspannungen
VARISTOR
Strombegrenzung bei Kurzschluss
I
Überstrom
= 150% der max. Ausgangsleistung
Überspannungsschutz gegen interne Überspannungen
Ja
Isolationsspannung
Eingang / Ausgang
Eingang / Schutzleiter
Ausgang / Schutzleiter
4,0KVac
2,0KVac
1,5KVac
Schutzart
IP20
Schutzklasse
Klasse I mit Schutzleiteranschluss
1. Safety instructions
• Switch main power off before connecting or disconnecting the device. Risk of explosion!
• To guarantee sufficient convection cooling, keep a distance of 50mm above and below
the device as well as a lateral distance of 5mm (for Vertical Mounting) or 50mm (for
Horizontal Mounting) to other units.
• Note that the enclosure of the device can become very hot depending on the
ambient temperature and load of the power supply. Risk of burns!
• The main power must be turned off before connecting or disconnecting wires to the
terminals.
• Do not introduce any objects into the unit!
• Dangerous voltage present for at least 5 minutes after disconnecting all sources of
power.
• The power supplies are built in units and must be installed in a cabinet or room
(condensation free environment and indoor location) that is relatively free of conductive
contaminants.
•
CAUTION:
“FOR USE IN A CONTROLLED ENVIRONMENT”.
For DRP024V240W3BA:
• The power supplies unit must be installed in minimum IP54 enclosure or cabinet in the
final installation. The enclosure or cabinet must comply with EN60079-0 or EN60079-15.
• Warning: Explosion Hazard - Substitution of components may impair suitability for
Class I, Division 2.
• Warning: Explosion Hazard - Do not disconnect equipment or adjust potentiometer
unless the power has been switched off or the area is known to be non-hazardous.
2. Device description (Fig. 1)
(1) Input terminal block connector
(2) Output terminal block connector
(3) DC voltage adjustment potentiometer
(4) DC OK control LED (green)
(5) Universal mounting rail system
3. Mounting (Fig. 2)
The power supply unit can be mounted on 35 mm DIN rails in accordance with EN 60715.
For Vertical Mounting, the device should be installed with input terminal block on the
bottom. For Horizontal Mounting, the device should be installed with input terminal block
on the left side.
Each device is delivered ready to install.
Snap on the DIN rail as shown in Fig. 2:
1. Tilt the unit slightly upwards and put it onto the DIN rail.
2. Push downwards until stopped.
3. Press against the bottom front side for locking.
4. Shake the unit slightly to ensure that it is secured.
4. Dismounting (Fig. 3)
To uninstall, pull or slide down the latch as shown in Fig. 3. Then, slide the PSU in the
opposite direction, release the latch and pull out the PSU from the rail.
5. Connection
The terminal block connectors allow easy and fast wiring.
You can use flexible (stranded wire) or solid cables with the following cross sections:
Table 1
To secure reliable and shock proof connections, the stripping length should be 7mm (see
Fig. 4 (1)). Please ensure that wires are fully inserted into the connecting terminals as
shown in Fig. 4 (2).
In accordance to EN60950 / UL60950, flexible cables require ferrules.
Use appropriate copper cables designed to sustain operating temperature of:
1.
60°C, 60°C / 75°C for USA
2.
At least 75°C for ambient not exceeding 40°C, and 90°C for ambient exceeding
40°C for Canada.
5.1. Input connection (Fig. 1, Fig. 5)
Use L1, L2, L3 and PE connections of input terminal connector (see Fig. 5) to establish
the 3 x 400-500Vac connection. Fig. 5 shows the connection to the various network types.
In the event of a phase failure, unrestricted operation is possible with nominal capacity.
The unit is protected with internal fuse (not replaceable) at L pin and it has been tested and
approved on 20A (UL) and 16A (IEC) branch circuits without additional protection device.
An external protection device is only required if the supplying branch has an ampacity
greater than above. Thus, if an external protective device is necessary, or, utilized, a
minimum value of 13A B- or 6A C- characteristic breaker should be used.
Figure 6
Figure 2
Figure 3
Figure 4
Figure 1
Figure 5
7 mm
1
2
1
2
3
(2)
(1)
(4)
(3)
(5)
1
2
3
7 mm
1
2
1
2
3
(2)
(1)
(4)
(3)
(5)
1
2
3
7 mm
1
2
1
2
3
(2)
(1)
(4)
(3)
(5)
1
2
3
7 mm
1
2
1
2
3
(2)
(1)
(4)
(3)
(5)
1
2
3
5.2. Anschluss der Ausgangsklemmen (Abb. 1 (2))
Verwenden Sie die Schraubklemmen „+“ und „-“, um den 24Vdc-Anschluss herzustellen. Am
Ausgang stehen 24Vdc zur Verfügung. Die Ausgangsspannung kann am Potentiometer zwischen
24 und 28Vdc eingestellt werden. Die grüne LED “DC OK” zeigt die korrekte Funktion des Ausgangs
an (Abb. 1 (4)). Das Gerät verfügt über einen Kurzschluss-, Überlast- und Überspannungsschutz,
der auf 35Vdc begrenzt ist.
5.3. Ausgangskennlinie
Das Gerät funktioniert normal, solange die Netz- und Lastbedingungen im Betriebsbereich des
Geräts liegen. Im Fall eines Kurzschlusses oder einer Überlast fallen Ausgangsspannung und –
strom ab (bei I
Überlast
bzw. I
Kurzschluss
> I
Überstrom
(150%)). Die Sekundärspannung wird dabei so lange
abgesenkt, bis der sekundärseitige Kurzschluss oder die Überlast behoben sind.
5.4. Temperaturverhalten (Abb. 6)
Beträgt die Umgebungstemperatur über +50°C (Vertikal) oder +40°C (Horizontal), muss die
Ausgangsleistung entsprechend dem Temperaturanstieg um 2,5% pro Celsius reduziert werden
und bei +70°C bis +80°C (Vertikal) oder +60°C bis +70°C (Horizontal), muss die Ausgangsleistung
entsprechend dem Temperaturanstieg um 5% pro Celsius reduziert werden. Wird die
Ausgangsleistung bei einer Umgebungstemperatur von > 50°C (Vertikal) oder > 40°C (Horizontal)
nicht herabgesetzt, löst der thermische Überlastschutz aus und schaltet das Gerät ab. Das Gerät
bleibt dann so lange in diesem Zustand bis die Umgebungstemperatur oder die Last soweit
abgesenkt wurde, dass das Gerät wieder im Normalbetrieb arbeiten kann.
Die interne Sicherung darf nicht vom Anwender ausge-
tauscht werden. Schicken Sie das Gerät im Fall eines
Defekts zur Reparatur zum Hersteller zurück.
1. Sicherheitsvorschriften
• Schalten Sie die Netzspannung ab, bevor Sie das Gerät an das Netz anschließen oder es vom
Netz trennen. Explosionsgefahr!
• Um eine ausreichende Konvektionskühlung zu gewährleisten, halten Sie ober und unterhalb
des Gerätes einen Abstand von 50mm ein. Bei vertikaler Montage sollte ein seitlicher Abstand
von 5mm zu anderen Geräten gewährleistet sein, bei horizontaler Montage ein Abstand von
50mm.
• Beachten Sie, dass das Gehäuse des Gerätes sehr heiß werden kann, abhängig von der
Umgebungstemperatur und der Last an der Spannungsversorgung.
Verbrennungsgefahr!
• Verbinden und trennen Sie die Anschlüsse nur, wenn die Spannung abgeschaltet ist!
• Führen Sie keine Objekte in das Gerät ein!
• Nachdem das Gerät von allen Spannungsquellen getrennt wurde liegt über einen Zeitraum von
mindestens 5 Minuten noch gefährliche Spannung an dem Gerät an.
• Die Netzgeräte sind eingebaute Geräte und müssen in einem Schrank oder Raum (Innenraum
ohne Kondensation) installiert werden, der relativ frei von leitenden Schmutzstof fen ist.
•
VORSICHT:
„Zum Einsatz nur im Innenbereich“.
Für DRP024V240W3BA:
• Die Stromversorgung muss bei der endgültigen Installation mindestens in einem IP54 Gehäuse
oder Schrank montiert werden. Das Gehäuse oder der Schrank müssen die EN60079-0 oder
EN60079-15 Norm erfüllen.
• Warnung: Explosionsgefahr – Das Austauschen von Komponenten kann die Eignung für
Klasse I, Abteilung 2 beeinträchtigen.
• Warnung: Explosionsgefahr – Anlage nur dann abtrennen oder potentiometer einstellen, wenn
die Stromversorgung unterbrochen oder die Umgebung als nicht gefährlich eingestuft wurde.
2. Gerätebeschreibung (Abb. 1)
(1) Eingangsklemmen
(2) Ausgangsklemmen
(3) Potentiometer zur Einstellung der DC-Ausgangsspannung
(4) LED für Statusanzeige „DC OK“ (grün)
(5) Universelles Montageschienensystem
3. Montage (Abb. 2)
Das Netzteil kann auf 35mm DIN-Schienen gemäß EN60715 montiert werden. Bei vertikalem
Einbau sollte das Gerät so eingebaut werden, dass der Klemmenleistenblock unten ist. Beim
horizontalen Einbau sollte das Gerät so eingebaut werden, dass der Klemmenleistenblock auf
der linken Seite ist.
Jedes Gerät wird installationsfertig geliefert.
Einrasten des Geräts in DIN-Schiene, wie in Abb. 2 dargestellt:
1. Kippen Sie das Gerät leicht nach oben und setzen Sie es auf die DIN-Schiene auf.
2. Kippen Sie das Gerät jetzt wieder nach unten bis zum Anschlag am unteren Teil der
Schiene.
3. Drücken Sie nun den unteren Teil des Gerätes so fest gegen die Schiene bis das Gerät auf
der Schiene einrastet.
4. Rütteln Sie leicht am Gerät, um zu überprüfen, ob es korrekt eingerastet ist.
4. Demontage (Abb. 3)
Ziehen Sie zur Demontage den Einrasthebel mit einem Schraubendreher nach unten, wie in Abb. 3
dargestellt. Kippen Sie das Netzteil in die entgegengesetzte Richtung nach oben, klinken Sie den
Einrasthebel aus und nehmen Sie das Netzteil nach oben von der DIN-Schiene ab.
5. Anschluss
Die Anschlussklemmen erlauben eine schnelle und einfache Verdrahtung des Geräts. Sie können
flexible (feindrähtige Leitung) oder feste Kabel mit folgenden Querschnitt verwenden:
Tabelle 1
Um sichere und stoßfeste Anschlüsse gewährleisten zu können, sollte die Abisolierlänge 7mm
betragen (siehe Abb. 4 (1)). Bitte sorgen Sie dafür, dass die Kabel vollständig in die Anschluss-
klemmen eingeführt werden, siehe Abb. 4 (2).
Gemäß EN60950 / UL60950 sind für flexible Kabel Aderendhülsen erforderlich.
Verwenden Sie geeignete Kupferkabel, die für Betriebstemperaturen von mindestens 60°C,
60°C / 75°C für die USA und mindestens 75°C für Umgebungstemperaturen unter 40°C und
mindestens 90°C für Umgebungstemperaturen über 40°C für Kanada ausgelegt sind, um die UL-
Anforderungen erfüllen zu können.
5.1. Anschluss der Eingangsklemmen (Abb. 1, Abb. 5)
Verwenden Sie die Eingangsklemmen L1, L2, L3 und PE (Schutzleiter), um den 3-phasigen
400-500Vac-Anschluss herzustellen. Abb. 5 zeigt den Anschluss an die unterschiedlichen
Netztypen.
Im Fall eines Phasenausfalls ist ein uneingeschränkter Betrieb des Gerätes bei Nennleistung noch
möglich.
Das Gerät verfügt über eine interne, nicht austauschbare Sicherung am L-Pin. Es wurde getestet
und zugelassen mit handels üblichen Sicherungen von 20 A (UL) und 16 A (IEC) ohne weitere
Schutzeinrichtungen. Ein externer Schutz ist nur dann notwendig, wenn der Nennstrom größer als
20 A ist. Falls ein externer Schutz zur Anwendung kommt, sollte mindestens eine Sicherung des
Typs 13 A -B oder 6 A -C verwendet werden.
Siehe
Abb. 1:
Flexibel / Starr
Anzugsmoment
(mm²)
(AWG)
(Kgf-cm)
(lb in)
(1)
0,82-3,3
18-12
9,3
8,1
(2)
1,3-3,3
16-12
6,2
5,4
Refer to
Fig. 1:
Stranded / Solid
Torque
(mm²)
(AWG)
(Kgf-cm)
(lb in)
(1)
0.82-3.3
18-12
9.3
8.1
(2)
1.3-3.3
16-12
6.2
5.4
0
10
20
30
40
50
60
70
80
90
100
110
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80
Pe
rc
en
ta
ge
o
f M
ax
L
oa
d
(%
)
Surrounding Air Temperature
(
o
C)
Vertical Mounting
Horizontal Mounting
Power Derating Curve for PSU
TN-C
TT
IT
TN-S
L1
L2
L3
PE
+
L1
L2
L3
N
PE
L1
L2
L3
PE
+
L1
L2
L3
PEN
L1
L2
L3
PE
+
L1
L2
L3
N
L1
L2
L3
PE
+
L1
L2
L3
Manual_CliQII_240W3P_DRP024V240W3BA_DRP024V240W3BN_DECA_rev.06_050916.indd 1
9/5/2016 9:32:16 AM