Delta Din-rail Power Meter DPM-D520I User Manual
A-2
_A
_1
_1
When measured current is higher than the rated specification for the device, use of an external current
transformer (CT) is necessary. Users can select a suitable CT with reference to the table below.
A.1
DCT1000 Series
Electromagnetic Compatibility: CE-marking, IEC61869-2.
Model
Number
Measurement
Accuracy
Primary
Current
Secondary
Current
Rated
Burden
(VA)
External
Dimension*1
(mm)
Size of
Opening*1
(mm)
DCT-S301C
1.0%
100 A
5 A
1.5
90 x 40 x 111
21 x 32
DCT-S211C
0.5%
200 A
5 A
1
DCT-S221C
0.5%
300 A
5 A
1.5
DCT-S231C
0.5%
400 A
5 A
2.5
DCT-S241C
0.5%
500 A
5 A
2.5
116.5 x 52 x 147
50 x 80
DCT-S251C
0.5%
600 A
5 A
2.5
DCT-S261C
0.5%
750 A
5 A
2.5
DCT-S271C
0.5%
1000 A
5 A
5
DCT-S281C
0.5%
1500 A
5 A
7.5
146.5 x 51.6 x
198
80 x 122
DCT-S291C
0.5%
2000 A
5 A
10
186.5 x 52 x 252 81 x 160.5
DCT-S2A1C
0.5%
2500 A
5 A
15
DCT-S2B1C
0.5%
3000 A
5 A
20
*1: See the following table for detailed information on the external dimensions and sizes of opening.
Summary of Contents for DPM-D520I
Page 3: ......
Page 9: ...Delta Din rail Power Meter DPM D520I User Manual 1 4 _1 _1 MEMO...
Page 15: ...Delta Din rail Power Meter DPM D520I User Manual 2 6 _2 MEMO...
Page 31: ...Delta Din rail Power Meter DPM D520I User Manual 4 10 _4 MEMO...
Page 116: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Page 119: ...Delta Din rail Power Meter DPM D520I User Manual 6 4 _6 Memo...
Page 125: ...Delta Din rail Power Meter DPM D520I User Manual A 6 _A _1 _1 MEMO...