Instruction Sheet

 

(1) General precautions

 

Thank you for purchasing this product. This DOP-107DV instruction sheet provides information for the 
DOP-107DV series HMI. Before using this product, read through this instruction sheet carefully to ensure 
the correct use of the product. Keep this sheet handy for quick reference whenever needed. Before 
finishing reading this sheet, follow the instructions below: 

 

Install the product in an indoor location, which is free of vapor and corrosive and inflammable gas. 

 

Refer to the wiring diagram when connecting the wires. 

 

Ensure this product is correctly grounded. The grounding method must comply with the national 
electrical standard guidelines (refer to NFPA 70: National Electrical Code, 2005 Ed.). 

 

Do not disassemble the HMI or change the wiring when power is on. 

 

Do not touch the power supply when power is on, or it may cause electric shock. 

 

When the HMI displays a low power notification and requires a battery change, contact Delta or 
local distributors for the replacement. Do not change the batteries by yourself. 

 

This product can be used with other industrial automation equipment. Read through this sheet 
carefully and install the product according to the instructions to avoid danger. 

 

Cleaning method: use a dry cloth to clean the product. 

 

This product must be used at an altitude below 2,000 m (6561.68 ft). 

 

If the equipment is used in a manner not specified by the manufacturer, the protection function 
provided by the equipment may be impaired. 

 

For repair and maintenance, contact Delta Electronics, Inc. Address: No.18, Xinglong Rd., 
Taoyuan City, Taiwan. TEL: +886-3-3626301. 

If you have any inquiry during operation, contact our local distributors or Delta Customer Service Center. 
The instruction sheet may be revised without prior notice. Contact our distributors or download the latest 
version from the Delta website (http://www.deltaww.com.tw/ia). 

 
  (2) Communication port pin assignment

 

DOP-107DV COM1 

COM Port 

Pin 

MODE1 

MODE2 

MODE3 

COM1 

COM2 

COM1 

COM2 

COM1 

COM2 

RS-232 

RS-485 

RS-485 

RS-485 

RS-232 

RS-422 

 

D+ 

TXD+ 

RXD 

RXD 

TXD 

TXD 

D+ 

D+ 

RXD+ 

GND 

GND 

GND 

D- 

TXD- 

RTS 

RTS 

CTS 

CTS 

D- 

D- 

RXD- 

Note: the mark “-” means connection is not required. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

(3) Description of each part 

DOP-107DV (front view) 

A

 

A

Operation / display area

DOP-107DV (rear view) 

A
B

HO

S

T

SL

A

V

E

CO

M1

CO

M2

C

D

E

 

USB Slave   

USB Host 

Ethernet (LAN) 

Power input connector 
(24AWG wire min.)

 

COM1 

 

(4) Mounting dimensions 

DOP-107DV 

215.6(8.46")

161

(6

.3

4

")

196.9

(7.75")

+1

.0 .0

0

Note:

T

26.2(1.03")

T = 1.6 mm - 6 mm(0.063" - 0.24")

 

Unit: mm (inch)   

Operation temperature: 0°C to 50°C (32°F to 122°F) 

Storage temperature: -20°C to 60°C (-4°F to 140°F) 

 
 
 
 

(5) Installation and wiring 

Precautions: 

 

Mount the HMI according to the following illustration. Incorrect installation direction may result in 
malfunction. 

 

To ensure the HMI is well ventilated, make sure there is sufficient space between the HMI and the 
adjacent objects or walls. 

 

This product should be used on a case or platform which conforms to enclosure Type 4X standard   
(for indoor use only). 

 

The maximum panel thickness for mounting must be no greater than 5 mm (0.2 inches). 

 

Use copper wires. 

 

Installation diagram: 

Step 1: 
Put the waterproof gasket onto the HMI and   
then insert the HMI into the panel cutout. 

Step 2: 
Place the fasteners into the slots and tighten 
the screws until reaching the panel cutouts. 

 

Step 3: 
Tighten the screws with the torque between   
0.5 N-M and 0.7 N-M to avoid damage to the 
plastic case. 
DOP-107DV torque: 6.17 lb-inch (0.7 N-M) 

Step 4: 
For heat dissipation, keep a minimum 
clearance of 60 mm (2.36 inches) and   
45 mm (1.77 inches) respectively on the rear 
and bottom of the HMI. 

 

60

45

 

Wiring: 

Type 

Wire gauge (AWG) 

Stripped length 

Torque 

Solid 

24 - 12 

7 - 8 mm 

(0.28 - 0.31 inches) 

5 kg-cm (4.3 lb-in) 

Stranded 

24 - 12 

7 - 8 mm 

(0.28 - 0.31 inches) 

5 kg-cm (4.3 lb-in) 

 

Refer to the following diagram when wiring the power connector. The temperature rating of 
the cable must be greater than 75°C (167°F).

 

 

 
 
 
 

 