DOP-
103WQ
DOP
-107WV
DOP
-110WS
High Color
‧
Widescreen
‧
User-Friendly HMI Products
Delta Electronics Inc,
No.18, Xinglong Rd., Taoyuan City
33068, Taiwan
Instruction Sheet
(1) Preface
Thank you for purchasing DOP-107WV. This instruction sheet provides information about DOP-107WV.
Before using the product, please read through this manual carefully in order to ensure the correct use of
the product. In addition, please place this manual safely for quick reference whenever is needed. Please
follow the rules below if you have not finished reading this manual yet.
Install the product in a clean and dry location free from corrosive and inflammable gases or liquids,
indoor use only.
Ensure that all wiring instructions and recommendations are followed.
Ensure that HMI is correctly connected to the ground. The grounding method must comply with
the national electrical standard (Please refer to NFPA 70: National Electrical Code, 2005 Ed.
Do not modify the wiring or disassemble HMI interface when HMI is connected to the power.
Do not touch the power supply during operation. Otherwise, it may cause electric shock.
When HMI displays low power notification and requires battery changes, please contact local
distributors or DELTA customer service center for the replacement. Do not change batteries by
yourself.
DOP-100 series can be used for industrial automation equipment. Please read through this
manual carefully and install the product according to the instructions in order to avoid danger.
Cleaning method: Please use dry cloth to clean the product.
The product should be used at an altitude below 2000 m.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by
the equipment may be impaired.
For repairing and maintenance, please contact DELTA Electronics, Inc. Address: No.18, Xinglong
Rd., Taoyuan City, Taiwan. TEL: +886-3-3626301.
If you have any enquiry during operation, please contact our local distributors or Delta sales
representatives. The content of this instruction sheet may be revised without prior notice. Please consult
our distributors or download the latest version at http://www.delta.com.tw/ia.
(2) Communication Port Pin Assignment
DOP-103WQ COM Port
COM Port
Pin
MODE1
MODE2
MODE3
COM1
COM2
COM1
COM2
COM1
COM2
RS-232
RS-485
RS-485
RS-485
RS-232
RS-422
1
D+
TXD+
2
RXD
RXD
3
TXD
TXD
4
D+
D+
RXD+
5
GND
GND
GND
6
D-
TXD-
7
RTS
RTS
8
CTS
CTS
9
D-
D-
RXD-
DOP-107WV / DOP-110WS COM1 Port
COM Port
Pin
MODE1
RS-232
1
2
RXD
3
TXD
4
5
GND
6
7
RTS
8
CTS
9
DOP-107WV / DOP-110WS COM2 Port
COM Port
Pin
MODE1
MODE2
MODE3
COM2
COM3
COM2
COM3
COM2
COM3
RS-232
RS-485
RS-485
RS-485
RS-232
RS-422
1
D+
TXD+
2
RXD
RXD
3
TXD
TXD
4
D+
D+
RXD+
5
GND
GND
GND
6
D-
TXD-
7
RTS
RTS
8
CTS
CTS
9
D-
D-
RXD-
Note 1: Blank means connection is not required.
(3) Part names
DOP-103WQ (Front view)
A
Touch Screen
/
Display
DOP-103WQ (Rear view)
A
B
C
D
E
A
Power Input (24AWG wire min.)
B
COM1
C
USB Slave
D
USB Host
E
Network Port
(
LAN
)
DOP-107WV (Front view)
A
Touch Screen
/
Display
DOP-107WV (Rear view)
A
Power Input
(24AWG wire min.)
B
COM2/ COM3
C
COM1
D
Network Port (LAN)
E
USB Slave
F
USB Host
DOP-110WS (Front view)
A
Touch Screen
/
Display
DOP-110WS (Rear view)
A
Power Input
(24AWG wire min.)
B
COM2/ COM3
C
COM1
D
Network Port (LAN)
E
USB Slave
F
USB Host
G
SD Card
C