UL 864 DAC-633 Installation Guide 

Document Edition 1.5 

Updated November 17, 2015

 

 

 

 

Document Edition 1.5 

Product Description 

The DAC-633 Delta Application Controller is a Native BACnet 

Application Controller that communicates on an RS-485 LAN 

using the MS/TP BACnet protocol.  The controller is designed 

for a wide range of applications with small local I/O 

requirements.  Both firmware and controller databases are 

loadable over the network. 

With 6 inputs, 3 analog outputs and 3 binary triac outputs, the 

DAC-633 is suitable for controlling various packaged units and 

other equipment with small I/O requirements.  As the controller 

is completely programmable, GCL programs and BACnet 

objects can be tailored to the specific application. 

 

 

 

Important Information  

 

 

ORCAview OWS and controller firmware must all be of the same version number to be 

compatible. When upgrading any of these products from older versions (i.e. 3.22 or 3.30), you 

must upgrade all the remaining products. Exception: UL 864 model, DAC-633-UL864 can be 

used with V3.33 and V3.40 firmware. 

Package Contents 

 

Product: DAC-633 (Rev. 3.2) 

 

DAC-633 (Rev. 3.2) Installation Guide 

Related Documents 

 

Delta Controls Wiring Guidelines 

 

ORCAview Operator Guide 

 

ORCAview Technical Reference Manual  

 

Release Notes for related Firmware 

 

Summary of Contents for DAC-633

Page 1: ...controlling various packaged units and other equipment with small I O requirements As the controller is completely programmable GCL programs and BACnet objects can be tailored to the specific applica...

Page 2: ...ations Impedance value for which ground faults are detected is zero ohms Cautions or Warnings This controller is an Electro statically sensitive device Proper ESD protection ground strap should be use...

Page 3: ...ing The DAC 633 includes a plastic enclosure that can be quickly mounted with two screws not provided This controller should be mounted in an appropriate location within packaged equipment or another...

Page 4: ...Delta Controls Page 4 of 12 Board Layout...

Page 5: ...st still have a unique dip switch address even when using software to define the controller number DNA Controller Addressing The Dip Switch is a binary switch Each individual DIP switch represents a u...

Page 6: ...gned to use a 24 VAC Class 2 power supply The proper specified cabling must be used 18 16 AWG 2 conductor wire A single transformer may be used to power multiple controllers and or auxiliary field dev...

Page 7: ...d to ensure reliable communications 22 AWG twisted pair 100 120 ohms impedance 17 pF ft or lower capacitance with a braided or aluminum foil shield Controllers should always be wired together in a dai...

Page 8: ...ors that use a 0 5 VDC signal 10V For sensors that use a 0 10 VDC signal Binary Output Power Source The binary triac outputs can be selected to use either an internal or external power source by placi...

Page 9: ...ceiving data through the port If communication is good both LEDs will flash at a high rate Network NET2 MS TP RS485 Communication Status Indicators The green LED flashes to indicate when the controlle...

Page 10: ...RJ 11 Jack Used with Delta Controls service tool devices for example CON 768 Inputs 6 Universal Inputs 10 bit jumper configurable for the following input types 0 5 VDC 0 10 VDC 10 K Thermistor Dry Con...

Page 11: ...rmonics Class A EN 61000 3 3 1994 A1 2001 01 Power Line Fluctuations Pst 1 Plt 0 65 EN 61000 6 1 2001 Light Industrial Residential Immunity Requirements EN 61000 4 2 1995 A2 2000 11 ESD Immunity Level...

Page 12: ...ul interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at...