InfraSuite - CoolDoor
48
5.3
Power Supply
Please supply power to the cooling device. With power supply, it enters the standby mode
automatically. For safety reason, the fan will not run automatically. With the power supply
connected to the system, the read screen appears on the touch display and status page
shows up spontaneously.
Air state
26.3°C
Percentage of air volume
100%
(Figure 5-1: Status Page)
For how to interpret the values shown on the status page and the operation, refer to
5. Operation
.
5.4
Ventilation
WARNING:
When performing this installation step, ensure the safety of personnel. Wear
protective gear, especially goggles to protect the eyes, to prevent impact from
water stream.
The following steps can help check that the system pressure supply is normal. Use a stable
pressure supply to remove air from the closed chilled water system. Part of the air
accumulated in the coil can also be removed by following the steps below. The following
actions can only remove the air in the coil of the CoolDoor, and cannot ensure that the air in
the closed chilled water system is completely removed. The air release valve should be used
for automatic exhaust at the highest and most reasonable point of the closed circuit system.
1. It is recommended that the tool filling soft tube should be equipped with a refill tool that
has a switch; the connection size of the exhaust valve is 7/16”, as shown in the figure on
the right.