Chapter 7 Optional Accessories
MS300 (IP66 / NEMA 4X)
7-5
7-3 Fuse Specification Table
Use only the test approved fuse specifications as listed in the table below. Do not use values larger
than the values listed in the fuse specification table. Using AC input values smaller than the listed
values is allowed only when the fuse current root mean square value is larger than the actual input
current value. If the drive operates under an overloaded condition, that is, 150% of its output, you
must multiply the input current corresponded in the table by 1.5.
For installation in the United States, branch circuit protection must be provided in accordance with the
National Electrical Code (NEC) and any applicable local codes. Use UL classified fuses to fulfill this
requirement.
For installation in Canada, branch circuit protection must be provided in accordance with Canadian
Electrical Code and any applicable provincial codes. Use UL classified fuses to fulfill this requirement.
Model
Voltage/
one-phase
(three-phase)
Current Input / Output
(Maximum)
AC Input Terminal
Fuse
[A]
Brake Fuses
(Terminal B1&B2)
[A]
Normal Duty
Heavy Duty
VFD2A8MS21MNSXX
VFD2A8MS21MFSXX
230V /
one
-phase
6.7 A / 3.2 A
5.9 A / 2.8 A
12.8
HINODE
1000GH-16UL
Class T JJS-15
VFD4A8MS21MNSXX
VFD4A8MS21MFSXX
10.5 A / 5.0 A 10.1 A / 4.8 A
20
HINODE
1000GH-16UL
Class T JJS-20
VFD7A5MS21MNSXX
VFD7A5MS21MFSXX
17.9 A / 8.5 A 15.8 A / 7.5 A
34
HINODE
1000GH-16UL
Class T JJS-35
VFD11AMS21MNSXX
VFD11AMS21MFSXX
26.3 A / 12.5 A 23.1 A / 11.0 A
50
HINODE
1000GH-16UL
Class T JJS-50
VFD1A6MS23MNSXX
230V /
three
-phase
2.2 A / 1.8 A
1.9 A / 1.6 A
7.2
HINODE
1000GH-16UL
Class T JJS-10
VFD2A8MS23MNSXX
3.8 A / 3.2 A
3.4 A / 2.8 A
12.8
HINODE
1000GH-16UL
Class T JJS-15
VFD4A8MS23MNSXX
6.0 A / 5.0 A
5.8 A / 4.8 A
20
HINODE
1000GH-16UL
Class T JJS-20
VFD7A5MS23MNSXX
9.6 A / 8.0 A
9.0 A / 7.5 A
32
HINODE
1000GH-16UL
Class T JJS-35
VFD11AMS23MNSXX
15.0 A / 12.5 A 13.2 A / 11.0 A
50
HINODE
1000GH-16UL
Class T JJS-50
VFD17AMS23MNSXX
23.4 A / 19.5 A 20.4 A / 17.0 A
78
HINODE
1000GH-32UL
Class T JJS-80
VFD25AMS23MNSXX
32.4 A / 27.0 A 30.0 A / 25.0 A
59.4
HINODE
1000GH-40UL
Class T JJS-60
VFD1A5MS43MNSXX
VFD1A5MS43MFSXX
460V /
three
-phase
2.5 A / 1.8 A
2.1 A / 1.5 A
7.2
HINODE
1000GH-16UL
Class T JJS-10
VFD2A7MS43MNSXX
VFD2A7MS43MFSXX
4.2 A / 3.0 A
3.7 A / 2.7 A
12
HINODE
1000GH-16UL
Class T JJS-15
VFD4A2MS43MNSXX
VFD4A2MS43MFSXX
6.4 A / 4.6 A
5.8 A / 4.2 A
18.4
HINODE
1000GH-16UL
Class T JJS-20
Summary of Contents for Compact Drive MS300 IP66/NEMA 4X Series
Page 3: ......
Page 10: ...Chapter 1 Introduction MS300 IP66 NEMA 4X 1 3 1 2 Model Name 1 3 Serial Number...
Page 18: ...Chapter 1 Introduction MS300 IP66 NEMA 4X 1 11 This page intentionally left blank...
Page 24: ...Chapter 2 Dimensions MS300 IP66 NEMA 4X 2 6 This page intentionally left blank...
Page 28: ...Chapter 3 Installation MS300 IP66 NEMA 4X 3 4 This page intentionally left blank...
Page 29: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 1 Chapter 4 Wiring 4 1 System Wiring Diagram 4 2 Wiring...
Page 32: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 4 4 2 Wiring Figure 4 2...
Page 34: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 6 This page intentionally left blank...
Page 83: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 33 The drive with MKMX SWA...
Page 85: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 35 The drive with MKMX SWB...
Page 87: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 37 The drive with MKMX SWC...
Page 126: ...Chapter 10 Digital Keypad MS300 IP66 NEMA 4X 10 8 This page intentionally left blank...