Chapter 9 Specification
MS300 (IP66 / NEMA 4X)
9-2
9-1 230V Series
230V, one-phase
Frame
A
B
Model VFD_ _ _ _ _ _ _ SAA
2A8MS21_ _
4A8MS21_ _
7A5MS21MN 7A5MS21MF
11AMS21_ _
MN
MF
MN
MF
MN
MF
Applicable Motor Output (kW)
0.4
0.75
1.5
1.5
2.2
Applicable Motor Output (HP)
0.5
1
2
2
3
Output Rating
Heavy
Duty
Rated Output Capacity
(kVA)
1.1
1.8
2.9
2.9
4.2
Rated Output Current (A)
2.8
4.8
7.5
7.5
11
Carrier Frequency (kHz)
2–15 (Default: 4)
Normal
Duty
Rated Output Capacity
(kVA)
1.2
1.9
3.2
3.2
4.8
Rated Output Current (A)
3.2
5
8.5
8.5
12.5
Carrier Frequency (kHz)
2–15 (Default: 4)
Input Ratin
g Rated Input
Current (A)
Heavy Duty
7.3
10.8
16.5
16.5
24.2
Normal Duty
8.3
11.3
18.5
18.5
27.5
Rated Voltage / Frequency
One-phase AC 200–240 V, 50/60 Hz
Operating Voltage Range (V
AC
)
170–264 (-15–10%)
Frequency Range (Hz)
47–63
Weight (kg)
2.25
2.65
2.6
2.9
3.1
3.95
3.5
4.0
Cooling Method
Convective cooling
Fan cooling
EMC Filter
Optional Built-in Optional Built-in
Optional
Built-in
Optional Built-in
IP Rating
IP66 / NEMA 4X
NOTE
The value of the carrier frequency is set in the factory. To increase the carrier frequency, decrease the current. See the derating curve
diagram for Pr.06-55 for more information.
When the load is a shock or impact load, use a higher level model.
Summary of Contents for Compact Drive MS300 IP66/NEMA 4X Series
Page 3: ......
Page 10: ...Chapter 1 Introduction MS300 IP66 NEMA 4X 1 3 1 2 Model Name 1 3 Serial Number...
Page 18: ...Chapter 1 Introduction MS300 IP66 NEMA 4X 1 11 This page intentionally left blank...
Page 24: ...Chapter 2 Dimensions MS300 IP66 NEMA 4X 2 6 This page intentionally left blank...
Page 28: ...Chapter 3 Installation MS300 IP66 NEMA 4X 3 4 This page intentionally left blank...
Page 29: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 1 Chapter 4 Wiring 4 1 System Wiring Diagram 4 2 Wiring...
Page 32: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 4 4 2 Wiring Figure 4 2...
Page 34: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 6 This page intentionally left blank...
Page 83: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 33 The drive with MKMX SWA...
Page 85: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 35 The drive with MKMX SWB...
Page 87: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 37 The drive with MKMX SWC...
Page 126: ...Chapter 10 Digital Keypad MS300 IP66 NEMA 4X 10 8 This page intentionally left blank...