1. Safety instructions

•   Switch main power off before connecting or disconnecting the device. Danger of  

  explosion!

•   To guarantee sufficient convection cooling, please keep a distance of 50mm above  

  and below the device as well as a lateral distance of 20mm to other units.

•   Please note, that the enclosure of the device can become very hot depending on  

  the ambient temperature and load of the power supply. Risk of burns!

•   The main power must be turned off before connecting or disconnecting wires to the  

  terminals!

•   Do not introduce any objects into the unit!

•   Dangerous voltage present for at least 5 minutes after disconnecting all sources of  

  power.

•  To protect against access to live parts, the PSU must be built-in (must be installed  

  in a protective enclosure). 

•  The power supplies unit must be installed in minimum IP54 enclosure or cabinet  

  in the final installation. The enclosure or cabinet must comply with EN60079-0 or  

  EN60079-15.

•  Warning: Explosion Hazard - Substitution of components may impair suitability for  

  Class I, Division 2.

•  Warning: Explosion Hazard - Do not disconnect equipment or adjust potentiometer  

  unless the power has been switched off or the area is known to be non-hazardous.

2. Device description (Fig. 1)

(1) Input terminal block connector

(2) Output terminal block connector

(3) DC voltage adjustment potentiometer

(4) DC OK control LED (green)

(5) Universal mounting rail system

3. Mounting (Fig. 2)

The  power  supply  unit  can  be  mounted  on  35mm  DIN  rails  in  accordance  with 

EN60715. The device should be installed horizontally  with input terminal blocks on 

the bottom.

Each device is delivered ready to install. 

Snap on the DIN rail as shown in Fig. 2:

 

1. Tilt the unit slightly upwards and put it onto the DIN rail.

 

2. Push downwards until stopped.

 

3. Press against the bottom front side for locking.

 

4. Shake the unit slightly to ensure that it is secured.

4. Dismounting (Fig. 3)

To uninstall, pull or slide down the latch as shown in Fig. 3. Then, slide the PSU in the 

opposite direction, release the latch and pull out the PSU from the rail.

5. Connection

The terminal block connectors allow easy and fast wiring. A plastic cover provides the 

necessary isolation of the electric connection.

You can use flexible (stranded wire) or solid cables with cross section 0.52-2.1mm² 

(AWG 20-14) and torque of 0.78-0.98Nm (6.94-8.68lb in). To secure reliable and shock 

proof connections, the stripping length should not exceed 7mm.

In accordance to EN60950 / UL60950, flexible cables require ferrules.

Use appropriate copper cables that are designed to sustain operating temperature of 

at least 75°C or more to fulfill UL requirements.

For stranded wires it is recommended to use suitable lug to crimp wires (see Fig. 4).

5.1. Input connection (Fig. 1, Fig. 5)

Use L, N and PE connections of input terminal connector (see Fig. 1 (1)) to establish 

the 100-240Vac connection. 

The unit is protected with internal fuse (not replaceable) at L pin and it has been tested 

and approved on 20A (UL) and 16A (IEC) branch circuits without additional protection 

device. An external protection device is only required if the supplying branch has an 

ampacity greater than above. Thus, if an external protective device is necessary, or, 

utilized, a minimum value of 20A B- or 10A C- characteristic breaker should be used.

DEUTSCH

Anleitung

5.2. Anschluss der Ausgangsklemmen (Abb. 1 (2))

Verwenden  Sie  die  Schraubklemmen  „+“  und  „-“,  um  den  12Vdc-Anschluss 

herzustellen. Am Ausgang stehen 12Vdc zur Verfügung. Die Ausgangsspannung kann 

am Potentiometer zwischen 11 und 14Vdc eingestellt werden. Die grüne LED “DC OK” 

zeigt die korrekte Funktion des Ausgangs an (Abb. 1 (4)). Das Gerät verfügt über einen 

Kurzschluss-, Überlast- und Überspannungsschutz, der auf 17.6Vdc begrenzt ist.

5.3. Ausgangskennlinie 

Das  Gerät  funktioniert  normal,  solange  die  Netz-  und  Lastbedingungen  im 

Betriebsbereich  des  Geräts  liegen.  Im  Fall  eines  Kurzschlusses  oder  einer  Überlast 

fallen Ausgangsspannung und –strom ab (bei I

Überlast

 bzw. I

Kurzschluss

 > I

Überstrom 

(150%)). Die 

Sekundärspannung wird dabei so lange abgesenkt, bis der sekundärseitige Kurzschluss 

oder die Überlast behoben sind. 

5.4. Temperaturverhalten (Abb. 6)

Beträgt  die  Umgebungstemperatur  über  +50°C,  muss  die  Ausgangsleistung 

entsprechend  dem  Temperaturanstieg  um  2,5%  pro  Celsius  reduziert  werden 

und  bei  +70°C  bis  +80°C,  muss  die  Ausgangsleistung  entsprechend  dem 

Temperaturanstieg  um  4%  pro  Celsius  reduziert  werden.  Wird  die Ausgangsleistung 

bei  einer  Umgebungstemperatur  von  >  50°C  nicht  herabgesetzt,  löst  der  thermische 

Überlastschutz aus und schaltet das Gerät ab. Das Gerät bleibt dann so lange in diesem 

Zustand bis die Umgebungstemperatur oder die Last soweit abgesenkt wurde, dass das 

Gerät wieder im Normalbetrieb arbeiten kann.

 

Die interne Sicherung darf nicht vom Anwender ausge-

tauscht werden. Schicken Sie das Gerät im Fall eines 

Defekts zur Reparatur zum Hersteller zurück.

ENGLISH

Installation notes

5.2. Output connection (Fig. 1 (2))

Use  the  “+”  and  “-“  screw  connections  to  establish  the  12  Vdc  connection.  The 

output provides 12Vdc. The output voltage can be adjusted from 11 to 14Vdc on the 

potentiometer.  The  green  LED  DC  OK  displays  correct  function  of  the  output  (Fig. 

1  (4)).  The  device  has  a  short  circuit  and  overload  protection  and  an  overvoltage 

protection limited to 17.6Vdc.

5.3. Output characteristic curve 

The device functions normal under operating line and load conditions. In the event of 

a short circuit or over load the output voltage and current collapses (I

O/L

 or I

S/C

 is > I

surge

 

(150%)). The secondary voltage is reduced and bounces until short circuit or over load 

on the secondary side has been removed.

5.4. Thermal behavior (Fig. 6)

In  the  case  of  ambient  temperatures  above  +50°C,  the  output  capacity  has  to 

be  reduced  by  2.5%  per  degree  Celsius  increase  in  temperature,  and  at  +70°C  to 

+80°C, the output capacity has to be reduced by 4% per degree Celsius increase in 

temperature. If the output capacity is not reduced when T

Amb

 > 50°C device will run into 

thermal protection by switching off i.e. device will go in bouncing mode and will recover 

when ambient temperature is lowered or load is reduced as far as necessary to keep 

device in working condition.

 

The internal fuse must not be replaced by the user. 

In case of internal defect, return the unit for inspection to 

the manufacturer.

ENGLISH

Technical data

Input (AC)

Nominal input voltage 

100-240Vac

Voltage range

85-264Vac (DC input range 120-375Vdc)

Frequency

47-63Hz (0Hz @ DC input)

Nominal current 

< 1.35A @ 115Vac, < 0.80A @ 230Vac

Inrush current limitation. I

2

t (+25°C) typ.

< 50A @ 115Vac, < 100A @ 230Vac

Mains buffering at nominal load (typ.)

> 22ms @ 115Vac, > 110ms @ 230Vac

Turn-on time

< 2.5 sec.

Internal fuse

T 3.15 AH / 250V

Leakage current

< 1mA @ 240Vac

Output (DC)

Nominal output voltage U

N

 / tolerance

12Vdc ± 2%

Adjustment range of the voltage

11-14Vdc (maximum power ≤ 60W)

Nominal current

5A

Derating

> 50°C (2.5% / °C), > 70°C (4% / °C)

Startup with capacitive loads

Max. 8,000µF

Max. power dissipation idling / nominal load approx.

≤ 10.2W

Efficiency

> 85.5% @ 115Vac & 230Vac

Residual ripple / peak switching (20MHz) (at nominal values)

< 100mVpp

Parallel operation

With ORing Diode

General Data

Type of housing

Aluminium (Al5052)

Signals

Green LED DC OK

MTBF

> 300,000 hrs. 

Dimensions (L x W x H)

121mm x 32mm x 120mm

Weight

0.33kg

Connection method

Screw connection

Stripping length

7mm max. or use suitable lug to crimp

Operating temperature (Surrounding temperature)

-20°C to +80°C (Refer to Fig. 6)

Storage temperature

-25°C to +85°C

Humidity at +25°C, no condensation

< 95% RH

Vibration (non-operating)

10 to 150Hz, 0.35mm acc. 50m/S², single amplitude (5G 

max.) for 90 min. in each X, Y & Z directions, in acc. 

with IEC60068-2-6

Shock (in all directions)

30G (300m/S²) in all directions according to 

IEC60068-2-27

Pollution degree

2

Climatic class

3K3 according to EN60721

Certification and Standards

Electrical equipments of machines

IEC60204-1 (over voltage category III)

Electronic equipment for use in electrical power installations

TUV Bauart to EN62477-1 / IEC62103

Safety entry low voltage

PELV (EN60204), SELV (EN60950)

Electrical safety (of information technology equipment)

TUV Bauart EN60950-1,

UL/C-UL recognized to UL60950-1, CSA C22.2 No. 

60950-1,

CB scheme to IEC60950-1

Industrial control equipment

UL/C-UL listed UL 508 and CSA C22.2 No. 107.1-01; 

CSA to CSA C22.2 No. 107.1-01

Hazardous location / ATEX

cCSAus to CSA C22.2 No.213-M1987, ANSI / ISA 

12.12.01:2007 [Class I, Division 2, Group A,B,C,D T4,  

Ta = -20°C to +80°C (> +50°C derating)]
EN60079-0:2009, EN60079-15:2010 [

ATEX II 3G

II 3G Ex nA 

IIC T4 Gc, Ta = -20°C to +80°C (> +50°C derating)]

      II 3G ATEX

Certificate No. EPS 12 ATEX 1 491 X

Protection against electric shock

DIN57100-410

CE

In conformance with EMC directive and low voltage 

directive
In conformance with Equipment for explosive 

atmospheres (ATEX) directive

EMC for ITE

EN55022, EN61000-3-2, EN61000-3-3, EN55024

EMC for Industrial

EN55011, EN61000-6-2

Limitation of mains harmonic currents

EN61000-3-2

Safety and Protection

Transient surge voltage protection

VARISTOR

Current limitation at short-circuits approx.

I

surge

 = 150% of Po

max

 typically

Surge voltage protection against internal surge voltages

Yes

Isolation voltage:

Input / output (type test/routine test)

Input / PE (type test/routine test)

Output / PE (type test/routine test)

4.0KVac / 3.0KVac

1.5KVac / 1.5KVac

1.5KVac / 0.5KVac

Protection degree

IPX0

Safety class

Class I with PE connection

DEUTSCH

Technische Daten

Eingangskennwerte (AC)

Nennspannung 

100-240Vac

Spannungsbereich

85-264Vac (DC-Eingangsspannungsbereich 120-

375Vdc)

Frequenzbereich

47-63Hz (0Hz bei DC Eingangsspannung)

Nennstrom 

< 1,35A bei 115Vac, < 0,80A bei 230Vac

Einschaltstrombegrenzung I²t (+25°C) typ.

< 50A bei 115Vac, < 100A bei 230Vac

Netzausfallüberbrückung bei Nennlast (typ.)

> 22ms bei 115Vac, > 110ms bei 230Vac

Einschaltzeit

< 2,5 sec.

Interne Sicherung

T 3,15 AH / 250V

Ableitstrom

< 1mA bei 240Vac

Ausgangskennwerte (DC)

Nennausgangsspannung U

N

 / Toleranz

12Vdc ± 2%

Einstellbereich der Ausgangsspannung

11-14Vdc (max. Leistung ≤ 60W)

Nennstrom

5A

Derating (Leistungsherabsetzung)

> 50°C (2,5% / °C), > 70°C (4% / °C)

Anlaufen bei Kapazitiven Lasten

Max. 8.000µF

Max. Verlustleistung Leerlauf/Nennlast

≤ 10,2W

Wirkungsgrad

> 85,5% bei 115Vac & 230Vac

Restwelligkeit / Schaltspitzen (20MHz) (bei Nennwerten)

< 100mVpp

Parallelschaltbarkeit

mit ORing Diode

Allgemeine Kennwerte

Gehäusetyp

Aluminium (Al5052)

Statusanzeige

Grüne LED „DC OK“

MTBF (mittlere Betriebszeit zwischen Ausfällen)

> 300.000 Std. 

Abmessungen (B x H x T)

121mm x 32mm x 120mm

Gewicht

0,33kg

Art der Anschlussklemme

Schraubanschluss

Abisolierlänge

7mm max. oder geeigneter Kabelschuh zum Quetschen

Betriebstemperaturbereich (Umgebungstemperatur)

-20°C bis +80°C (Leistungsherabsetzung gemäß Abb. 6)

Lagertemperaturbereich

-25°C bis +85°C

Luftfeuchte bei +25°C, keine Betauung

< 95% relative Luftfeuchte

Vibration (außer Betrieb)

10 bis 150Hz, Beschl. 50m / s/S², 0,35mm  Einzelampli-

tude (5G max.) für 90 min. in X, Y & Z Richtung, gemäß 

IEC60068-2-6

Stoßfestigkeit (in alle Richtungen)

30G (300m/S²) in alle Richtungen gemäß 

IEC60068-2-27

Verschmutzungsgrad

2

Klimaklasse

3K3 gemäß EN60721

Zertifizierung und Normen

Elektrische Ausrüstung von Maschinen

IEC60204-1 

(Überspannungskategorie III)

Ausrüstung von Starkstromanlagen mit elektronischen 

Betriebsmitteln

TUV Bauart EN62477-1 / IEC62103

Schutzkleinspannung

PELV (EN60204), SELV (EN60950)

Elektrische Sicherheit (von Einrichtungen der Informati-

onstechnik)

TUV Bauart EN60950-1,

UL/C-UL anerkannt UL60950-1, CSA C22.2 No. 

60950-1,

CB Schema gemäß IEC60950-1

Industrielle Regeleinrichtungen

UL/C-UL gemäß UL 508 und CSA C22.2 No. 107.1-01; 

CSA nach CSA C22.2 No. 107.1-01

Gefährlicher Bereich / ATEX

cCSAus to CSA C22.2 No.213-M1987, ANSI / ISA 

12.12.01:2007 [Class I, Division 2, Group A,B,C,D T4,  

Ta = -20°C to +80°C (> +50°C derating)]
EN60079-0:2009, EN60079-15:2010 [

ATEX II 3G

II 3G Ex nA 

IIC T4 Gc, Ta = -20°C to +80°C (> +50°C derating)]

      II 3G ATEX

Zertifikat Nr. EPS 12 ATEX 1 491 X

Schutz gegen elektrischen Schlag

DIN57100-410

EC

In Konformität zur EMV-Richtlinie und 

Niederspannungsrichtlinie
In Konformität zur Geräte zur Verwendung in 

explosionsgefährdeten Bereichen (ATEX) Richtlinie

EMV für ITE

EN55022, EN61000-3-2, EN61000-3-3, EN55024

EMV für Industrial

EN55011, EN61000-6-2

Begrenzung der Netzoberschwingungen

EN61000-3-2

Sicherheit und Schutzeinrichtungen

Überspannungsschutz gegen transiente 

Überspannungen

VARISTOR

Strombegrenzung bei Kurzschluss

I

Überstrom

 = 150% der max. Ausgangsleistung

Überspannungsschutz gegen interne Überspannungen

Ja

Isolationsspannung

Eingang / Ausgang (Typprüfung/Stückprüfung)

Eingang / Schutzleiter (Typprüfung/Stückprüfung)

Ausgang / Schutzleiter (Typprüfung/Stückprüfung)

4,0KVac / 3,0KVac

1,5KVac / 1,5KVac

1,5KVac / 0,5KVac

Schutzart

IPX0

Schutzklasse

Klasse I mit Schutzleiteranschluss

1. Sicherheitsvorschriften

•  Schalten Sie die Netzspannung ab, bevor Sie das Gerät an das Netz anschließen  

  oder es vom Netz trennen. Explosionsgefahr!

•  Um eine ausreichende Konvektionskühlung zu gewährleisten, halten Sie ober und  

  unterhalb des Gerätes einen Abstand von 50mm ein sowie einen seitlichen Abstand  

  von 20mm zu anderen Geräten.

•  Beachten Sie, dass das Gehäuse des Gerätes sehr heiß werden kann, abhängig  

  von der Umgebungstemperatur und der Last an der Spannungsversorgung. 

  Verbrennungsgefahr!

•  Verbinden und trennen Sie die Anschlüsse nur, wenn die Spannung abgeschaltet  

  ist!

•  Führen Sie keine Objekte in das Gerät ein!

•  Nachdem das Gerät von allen Spannungsquellen getrennt wurde liegt über einen  

  Zeitraum von mindestens 5 Minuten noch gefährliche Spannung an dem Gerät an.

•  Um  vor  Zugriff  auf  elektrische  Teile  zu  schützen,  müssen  alle  Teile  des  Netzteils  

  eingebaut sein (bzw. in einem Schutzgehäuse installiert werden).

•  Die Stromversorgung muss bei der endgültigen Installation mindestens in einem IP54  

  Gehäuse oder Schrank montiert werden. Das Gehäuse oder der Schrank müssen die  

  EN60079-0 oder EN60079-15 Norm erfüllen.

•  Warnung:  Explosionsgefahr  –  Das  Austauschen  von  Komponenten  kann  die  

  Eignung für Klasse I, Abteilung 2 beeinträchtigen.

•   Warnung:  Explosionsgefahr  –  Anlage  nur  dann  abtrennen  oder  potentiometer  

  einstellen, wenn die Stromversorgung unterbrochen oder die Umgebung als nicht  

  gefährlich eingestuft wurde.

2. Gerätebeschreibung (Abb. 1)

(1)  Eingangsklemmen

(2)  Ausgangsklemmen

(3)  Potentiometer zur Einstellung der DC-Ausgangsspannung

(4)  LED für Statusanzeige „DC OK“ (grün)

(5)  Universelles Montageschienensystem

3. Montage (Abb. 2)

Das  Netzteil  kann  auf  35mm  DIN-Schienen  gemäß  EN60715  montiert  werden.  Das 

Gerät sollte waagerecht mit den Eingangsklemmen nach unten montiert werden.

Jedes Gerät wird installationsfertig geliefert.

Einrasten des Geräts in DIN-Schiene, wie in Abb. 2 dargestellt:

 

1. Kippen Sie das Gerät leicht nach oben und setzen Sie es auf die DIN-Schiene  

 

  auf.

 

2. Kippen Sie das Gerät jetzt wieder nach unten bis zum Anschlag am unteren Teil  

 

  der Schiene.

 

3. Drücken Sie nun den unteren Teil des Gerätes so fest gegen die Schiene bis das  

 

  Gerät auf der Schiene einrastet.

 

4. Rütteln Sie leicht am Gerät, um zu überprüfen, ob es korrekt eingerastet ist.

4. Demontage (Abb. 3)

Ziehen Sie zur Demontage den Einrasthebel mit einem Schraubendreher nach unten, 

wie  in Abb.  3  dargestellt.  Kippen  Sie  das  Netzteil  in  die  entgegengesetzte  Richtung 

nach oben, klinken Sie den Einrasthebel aus und nehmen Sie das Netzteil nach oben 

von der DIN-Schiene ab.

5. Anschluss

Die Anschlussklemmen erlauben eine schnelle und einfache Verdrahtung des Geräts. 

Eine Plastikabdeckung sorgt für die notwendige Isolierung der elektrischen Anschlüsse.

Sie können flexible (feindrähtige Leitung) oder feste Kabel mit einem Querschnitt von 

0,52-2,1mm² (AWG 20-14) und einem Anzugsmoment von 0,78-0,98Nm (6,94-8,68lb in) 

verwenden. Um sichere und stoßfeste Anschlüsse gewährleisten zu können, sollte die 

Abisolierlänge ≤ 7mm betragen.

Gemäß EN60950 / UL60950 sind für flexible Kabel Aderendhülsen erforderlich.

Verwenden Sie geeignete Kupferkabel, die für Betriebstemperaturen von mindestens 

75°C ausgelegt sind, um die UL-Anforderungen erfüllen zu können.

Für feindrähtige Leitungen empfiehlt es sich, passende Kabelschuhe zu verwenden, um 

die Drähte entsprechend zu quetschen (siehe Abb. 4).

5.1. Anschluss der Eingangsklemmen (Abb. 1, Abb. 5)

Verwenden Sie die Eingangsklemmen L, N und PE (Schutzleiter), um den 100-240Vac-

Anschluss herzustellen. 

Das Gerät verfügt über eine interne, nicht austauschbare Sicherung am L-Pin. Es wurde 

getestet und zugelassen mit handels üblichen Sicherungen von 20 A (UL) und 16 A (IEC) 

ohne weitere Schutzeinrichtungen. Ein externer Schutz ist nur dann notwendig, wenn 

der Nennstrom größer als 20 A ist. Falls ein externer Schutz zur Anwendung kommt, 

sollte mindestens eine Sicherung des Typs 20 A -B oder 10 A -C verwendet werden. 

ATEX II 3G

Figure 1

(1)

(2)

(5)

(4)

(3)

Figure 2

(1)

(2)

(5)

(4)

(3)

Figure 3

(1)

(2)

(5)

(4)

(3)

Figure 4

(1)

(2)

(5)

(4)

(3)

ATEX II 3G

Figure 5

0

10

20

30

40

50

60

70

80

90

100

110

-20

-10

0

10

20

30

40

50

60

70

80

Pe

rc

en

ta

ge

 o

f M

ax

 L

oa

(%

)

(

o

C)

Surrounding Air Temperature 

Figure 6

Power Derating Curve for PSU

L

N

PE

L     N   PE

TN-S

L

PEN

TN-C

+

L

N

TT

IT

L     N   PE

+

L     N   PE

+

L

N

L     N   PE

+

Manual_CliQ_12V_60W1P_EOE11010159_Rev.07_020916.indd   1

9/2/2016   9:27:05 AM

Reviews: