28
Amplon RT Series
N
Chapter 9: Specifications
*1:
The power factor can be modi ed into 0.8 to let the UPS rating change from 5kVA/ 4.5kW, 6kVA/ 5.4kW and 10kVA/ 9kW into 5.5kVA/ 4.4kW,
7kVA/ 5.6kW and 11kVA/ 8.8kW respectively.
*2:
At room temperature, at a distance of 1 meter in front of the UPS and when the load is 70% of the rating load.
NOTE:
Ú
Refer to the rating label for the safety rating.
Ú
All speci cations are subject to change without prior notice.
Ú
For power factor modi cation, please contact your local dealer or customer service.
Model
RT5k
RT6k
RT10k
1. Power (Va/W)
5000VA/4500W *
1
6000VA/5400W *
1
10000VA/9000W *
1
2. Waveform
Pure Sine Wave
3. Input
3.1 Input Voltage (Single)
100 ~ 155Vac (50% ~ 100% load)
100 ~ 180Vac (50% ~ 100% load)
156 ~ 280Vac (100% load) /
281 ~ 300Vac (90% load)
180 ~ 280Vac (100% load) /
281 ~ 300Vac (90% load)
3.2 Input Current
29.7A
35.9A
56.1A
- Inrush Current
< 200A
- Power Factor (Full Load)
> 0.99
3.3 Ef ciency (Full Resistance Load)
- On Line Mode (Full Load)
92%
- ECO Mode (Full Load)
96%
3.4 Input Frequency
40 ~ 70 Hz
4. Output
4.1 RMS Output Voltage (Single)
200Vac/208Vac/220Vac/230Vac(default)/240Vac
4.2 Overload Capability
106% ~ 110%: 10 minutes; 111% ~ 125%: 5 minutes; 126% ~ 150%: 30 seconds
4.3 The Overload Release (Rating Load)
95%
4.4 Output Frequency (Battery Mode)
50/60 Hz ± 0.05 Hz
4.5 Crest Factor (CF)
3:1
5. Battery & Charger
5.1 Type
Sealed Lead-Acid Battery
5.2 Number of Battery
12V x 16 pcs
12V x 20 pcs
5.3 Charge Current
4A (maximum)
4A (maximum)
6. Operation
-
Audible Noise
54 dBA
*
2
7. Appearance
7.1 Dimensions- Width x Depth x Height
(I/P & O/P Box Included)
440.0 x 670.5 x 88.5 mm
440.0 x 623.0 x 130.6 mm
7.2 Net Weight
15.5 Kg
21.3 Kg
8. Environment
8.1 Operating Temperature
0 ~ 40°C
8.2 Storage Temperature
-15 ~ 50°C
8.3 Relative Humidity
0 ~ 95% (non-condensing)