A H 5 0 0 H a r d w a r e a n d O p e r a t i o n M a n u a l
1 2 - 5 6
12.3.7
Troubleshooting for AH10DNET-5A
The parameters which are mentioned in the table below are set in DeviceNet Builder version 1.07 or above.
Error
code
Description
Remedy
16#A0F0
The node ID of AH10DNET-5A
is the same as other node ID on
the network, or exceeds the
range.
Make sure that the node ID of AH10DNET-5A is the only
one on the network. If the node ID of AH10DNET-5A is not
the only one on the network, please change the node ID,
and supply power to AH10DNET-5 again.
16#A0F1
No slave is put on the scan list
of AH10DNET-5A.
Put slaves on the scan list, and then download the scan list
to AH10DNET-5A.
16#A0F2
The working voltage of
AH10DNET-5A is low.
Check whether the working voltage of AH10DNET-5A and
that of an AH500 series CPU module are normal.
16#A0F3
AH10DNET-5A enters the test
mode.
Switch IN 1 on the module OFF, and supply power to
AH10DNET-5A again.
16#A0F4
The bus of AH10DNET-5A
becomes OFF.
1. Check whether the communication cable is normal, and
whether the shielded cable is grounded.
2. Check whether the serial transmission speeds of other
devices on the network are the same.
3. Check whether the both ends of the cable are
connected to 121 Ω terminal resistors.
4. Supply power to AH10DNET-5A again.
16#A0F5
AH10DNET-5A detects that
there is no power supply to the
DeviceNet network.
Check whether the communication cable is normal, and
whether the network power supply is normal.
16#A0F6
Something is wrong with the
internal memory of
AH10DNET-5A.
Supply power to AH10DNET-5A again. If the error still
occurs, please contact the local authorized distributors.
16#A0F7
Something is wrong with the
data exchange unit of
AH10DNET-5A.
Supply power to AH10DNET-5A again. If the error still
occurs, please contact the local authorized distributors.
16#A0F8
The product ID of
AH10DNET-5A is incorrect.
Supply power to AH10DNET-5A again. If the error still
occurs, please contact the local authorized distributors.
16#A0F9
An error occurs when the data
is read from AH10DNET-5A, or
when the data is written into
AH10DNET-5A.
Supply power to AH10DNET-5A again. If the error still
occurs, please contact the local authorized distributors.
16#A0FA
The node ID of AH10DNET-5A
is the same as that of the slave
set on the scan list.
Method 1: Set the node ID of AH10DNET-5A again. The
new node ID can not be the same as the node ID of the
slave set on the scan list. Supply power to AH10DNET-5A
again.
Method 2: Put no slave on the scan list, and download the
blank scan list to AH10DNET-5A through the simulated
online mode in the software. Supply power to
AH10DNET-5A again.
16#A0FB
The data exchange between
AH10DNET and AH CPU failed.
Supply power to the AH10DNET and AH CPU and try to
exchange data again. If the issue continuses, contact the
local authorized distributors.
Summary of Contents for AH500 series
Page 35: ...AH500 Hardware and Operation Manual 2 2 2 12 2 Profiles 2 117 2 12 3 Dimensions 2 118 ...
Page 153: ...AH500 Hardware and Operation Manual 2 120 MEMO ...
Page 167: ...AH500 Hardware and Operation Manual 3 14 MEMO ...
Page 343: ...AH500 Hardware and Operation Manual 6 38 MEMO ...
Page 361: ...AH500 Hardware and Operation Manual 7 18 MEMO ...
Page 403: ...Chapter 8 Hardware Configuration 8 42 MEMO ...
Page 412: ...Chapter 9 Network Configuration 9 9 ...
Page 445: ...AH500 Hardware and Operation Manual 9 42 MEMO ...
Page 552: ...Chapter 12 Troubleshooting 12 3 12 1 3 Troubleshooting Procedure ...
Page 649: ...AH500 Hardware and Operation Manual A 8 ...
Page 657: ...AH500 Hardware and Operation Manual A 16 MEMO ...
Page 658: ...B 1 Appendix B Device Addresses Table of Contents B 1 Device Addresses B 2 ...
Page 663: ...AH500 Hardware and Operation Manual C 4 MEMO ...
Page 681: ...AH500 Hardware and Operation Manual 3 14 MEMO ...