Unit Speci fica tions
The following table provides electrical and refrigeration specifications for the EL-20C Series Air
Conditioners.
EL-20C Series
Nominal Capacity Rating: 20,000 BTUH
Standard Maximum Ambient: 140°F
Unit Weight: 230VAC
– 170lbs, 480VAC – 247lbs
Model
Operatin
g Voltage
Range
(Volts)
Inrush
Current
(Start
Up
Current)
(Amps)
Loading
Current
(Running
Current)
(Amps)
SCCR
(Short
Circuit
Current
Rating)
(Amps)
Recommended
Circuit
Protection
(Amps)
KVA
Rating
Refrigerant
Type
Refrigerant
Amount
(ounces)
Low/High
Unit
Pressures
(psi)
EL-20C-236
207-253
50
12.47
*2
20 Amp Class
CC, CCMR
Time Delay *
2.9
R407c
36
86/353
EL-20C-486
414-506
25
6.30
*2
15 Amp Class
CC, CCMR
Time Delay *
3.0
R407c
36
86/353
* HACR Type Circuit Breakers or Time-delay Fuses with the following electrical characteristics are recommended.
Fast-acting fuses are not recommended.
% of Ampere Rating
Opening Time
110 %
15min Minimum
125 %
1hr Maximum
200 %
12sec Minimum
4min Maximum
*2
SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / enclosure per
UL50 & UL508a to protect the AC unit. Typically 100KA