Note:
Refer to Electrical Schematics for further diagnostics.
Unit Not
Cooling
Is
Compressor
On?
YES
NO
Check
Setpoint. Is
Setpoint
below
ambient?
YES
NO
Is snowflake
LED lit on
controller?
Set Setpoint between
70 to 95 deg F
YES
NO
Is evaporator
Fan on?
YES
NO
Is there voltage
to compressor?
Use meter
3
Check for faulty
evaporator fan
3
Measure Temperature at
Evaporator & Verify Heat Load
Requirements. Is unit capacity
adequate for internal head load?
Possible low refrigerant.
Is compressor
thermal
overload open?
Use ohm
meter.
3
Check for error
code
CA,LA,HA,LA2,HA2,
P1, or P2
YES
NO
Check contactor
circuit. Does it
have power?
3
NO
YES
Refer to Alarm
Signals in Digital
Temperature
Controller
Programming
Section
Contact Customer
Support
NO
YES
Verify contact coil is
being activated.
Check connectivity
3
,
if issue persists
component
replacement may be
needed.
Contact
Customer
Support
YES
NO
YES
Contact Customer
Support
Replace Thermal
Overload.