move the sensors, change antenna positions, or add repeaters to achieve the desired result. As
each receiver location is verified, record the signal strength measurements on the floor plan.
Setting Up the O3-DIN EnOcean Gateway
The O3-DIN EnOcean Gateway requires a controller and an EnOcean receiver. The controller
can be an O3-DIN-CPU or an O3-DIN-SRC. The receiver can be an EnOcean-capable O3 Hub
(O3-HUB-02-E8 or O3-HUB-O2-E9) or a CON-ENOC adapter.
O3 Hub devices communicate with O3-DIN controllers over an O3BUS (CAN-based) network.
CON-ENOC devices communicate with O3-DIN controllers over an RS-485 connection at 38400
bps.
l
The O3 DIN-CPU controller can support up to 8 O3 Hub devices or 1 CON-ENOC.
l
The O3-DIN-SRC controller can support up to 2 O3 Hub devices or 1 CON-ENOC.
l
You cannot use O3 Hubs and CON-ENOCs together.
To set up an O3-DIN EnOcean Gateway with one or more O3 Hubs:
1. Shut off power to the controller.
2. Connect the O3 Hub’s O3BUS port to the controller’s NET3 port.
3. Connect the O3 Hub’s PWR input to PWR OUT 1 on an O3 DIN-CPU controller or to an
external 24 VDC power supply.
4. If you are connecting only one O3 Hub to the O3BUS network, leave the device address as
the default setting (2). If you are connecting more than one O3 Hub, wire the hubs in a daisy
chain and set each hub to a unique address between 2 and 9. The total length of the O3BUS
network must not exceed 70 m (230 ft).
5. The O3BUS network must be terminated at both ends. O3 Hubs and the latest O3-DIN
controllers have a built-in termination switch. Set the switch to TERM on the device at each
end of the daisy chain. (Older O3-DIN controllers need a 120 Ω termination resistor across
the NET3 port pins for termination.)
6. Turn on power to the controller and the O3 Hub(s). If an O3 Hub is being powered by the
controller (that is, it is connected to PWR OUT 1 on an O3 DIN-CPU), in enteliWEB,
command the BO1 object on the controller to On.
To set up an O3-DIN EnOcean Gateway with a CON-ENOC, connect the CON-ENOC to the
controller’s RS-485 port (NET1, NET2, or NET3 on an O3-DIN-CPU; NET1 on an O3-DIN-SRC).
For more information, refer to the product installation guides on
.
©