MASTER SLAVE
SM15K INTERFACES
6 / 19
DELTA ELEKTRONIKA B.V.
rev. Nov. 2019
3
MASTER SLAVE INTERFACE
Warning!
carefully read the chapter "Safety Instructions" in
this manual before connecting or operating the unit!
3.1
CONDENSATION
During normal operation, humidity will not harm the
interfaces, provided the air is not aggressive. The heat
normally produced in the power supply will keep it dry.
Avoid condensation inside the interfaces, break-down could
be the result. Condensation can occur during a period the
power supply has been switched off (or operating at no load)
and the ambient temperature is increasing. Always allow the
power supply to dry before switching it on again.
3.2
TEMPERATURE & COOLING
The storage temperature range is
–40 to +85 °C.
The operating temperature range is
–20 to +50 °C. But this
temperature range only holds when the air-intake and air-
outlet of the power supply are unobstructed and the
temperature of the air-intake is not higher than +50°C.
When the power supply is mounted in a cabinet, please note
that the temperature of the air-intake should be kept low and
avoid a short circuit in the airflow i.e. the hot air leaving the
air-outlet entering the air-intake again.
Please note: a lower temperature extends the life of the
interface.
3.3
FIRMWARE
First install the interface inside the unit, then check the
firmware package is P0120 or higher. In the front menu, go
to: SYSTEM INFO -> UNIT-> VERSION.
If an update is required, refer to the SM15K unit manual how
to do this.
3.4
HARDWARE INSTALLATION
Warning!
Never make connections to the Power Inputs and
Outputs or the Sense Connector when the SM15K unit is
connected to the mains supply or power outlet!
Safety covers are used to cover these in- and outputs.
3.4.1
INSERT INTERFACES
Note: the M/S
-2
interfaces can be used in SM15K only.
In SM3300 use the M/S interfaces.
Switch off the units.
Disconnect the units from the mains supply.
o
Remove the cable from mains supply.
o
Wait for 5 minutes to allow internal capacitors to discharge.
The Interface can be inserted in slot 3 or slot 4.
o
See figure 3 - 1 for location of the slots.
o
Unscrew the 2pcs. torx T10 screws and remove the slot
cover.
o
Insert the interface.
o
Place the 2 screws back to secure the interface.
3.4.2
DC POWER CONNECTIONS FOR M/S-PARALLEL
It is strongly advised to use one of the M/S PAR kits from
Delta Elektronika for best and safest results!
o
These kits include special copper bars, bolts, nuts, specific
washers, patch cables and extra safety covers.
o
Each kit is designed for a specific number of units.
o
Download the or contact factory for more information.
Place all the units in a 19 inch rack.
o
Remove the input covers from the units.
o
Remove the mains supply cables.
o
Insert the units in the rack.
o
Stack the units with minimum spacing in between them.
Distance between sets of output terminals is 3U =
133.35mm.
Assign a unit as Master.
fig 3 - 1
Slot 3 and 4 are valid for INT MOD M/S-2.