background image

 

 

Warning 

 

Please read this instruction carefully before use.

 

 

Switch off the power before wiring.

 

 

The display panel of TP04 series is waterproof. But please prevent grease, corrosive liquids and sharp objects from 
contacting the TP04 series. 

 

The TP04 series require 24VDC input power. DO NOT connect input AC power supply to any of the RS-485 
communication port; otherwise serious damage may occur. Check all the wiring again before switching on the 
power. 

 

DO NOT touch any terminal when the power is switched on. DO NOT touch any internal circuit in 1 minute after 
the power is switched off. 

 

Make sure the groud terminal 

  is correctly grounded in order to prevent electromagnetic interference. 

 

Please use the fixed support

 

accessory which is packed together with the product provided by Delta. DO NOT 

tighten the screws out of the normal torque specifications; otherwise serious damage may occur. 

 Introduction 

 Model Explanation 

Thank you for choosing Delta TP Series. TP04G-AS2 has the features of high resolution 128×64 dots and is 
able to display 8×4 Chinese character. It provides multilingual display and two built-in communication ports, one 
is for RS-232/RS-422 and the other is for RS-485. RS-232 and RS-485 can be used simultaneously. Besides, it 
also supports built-in RTC, communication/alarm LED indicators. The user can purchase program copy card 
(optional) to copy settings and programs quickly and save download time. Regarding the editing software, there 
are various objects and images for the user’s requirements. 

 Product Outline 

RS-232 LED Indicator

RS-485/RS422 LED Indicator

Alarm LED Indicator

Arrow Keys

Enter Key

Function Keys

Displaying Area

Escape / Exit Key

Shift Key

 

 Panel Function Explanation 

Panel component 

Explanation 

Alarm LED indicator 
(RED) 

Status 1: When power is on, LED will start to blink slowly 
Status 2: When there is an abnormal situation, LED will blink quickly along with an alarm sound. 

RS-232 LED 
indicator (yellow) 

LED will blink when transmits program and communicates via RS-232. 

RS-485/RS-422 LED 
indicator (green) 

LED will blink when communicates via RS-485/RS-422. 

Displaying area 

Liquid Crystal Module display area. It is used to display current program status. 

Escape/Exit key 

It is used to cancel an incorrect input, or to exit a programming step. 

Shift key 

It is used to select function keys F0 ~ F9 and other keys for special function. 

Arrow keys 

UP/Pg Up: It is used to increase the value or move up one page.   

Pg Dn/DOWN: It is used to decrease the value or move down one page. 

Left: This key is left direction key and it can be used to select the position of the value. 

Right: This key is right direction key and it can be used to select the position of the value. 

Enter key 

It is used to input a value or accept a programming command. 

Function keys 

F0/F5: It is used to be constant 0 (F0) and 5 (Shift+F0) when it is in the system menu, the user 

can use it to define functions separately when they are in user page.   

F1/F6: It is used to be constant 1 (F1) and 6 (Shift+F1) when it is in the system menu, the user 

can use it to define functions separately when they are in user page. 

F2/F7: It is used to be constant 2 (F2) and 7 (Shift+F2) when it is in the system menu, the user 

can use it to define functions separately when they are in user page. 

ENGLISH 

Panel component 

Explanation 

Function keys 

F3/F8: It is used to be constant 3 (F3) and 8 (Shift+F3) when it is in the system menu, the user 

can use it to define functions separately when they are in user page.   

F4/F9: It is used to be constant 4 (F4) and 9 (Shift+F4) when it is in the system menu, the user 

can use it to define functions separately when they are in user page. 

 Back Panel 

BATTERY 
SWITCH  OR
RS-485/422

 

5 PIN terminal/Wire gauge: 12-24 AWG/Torque: 4.5 lb.-inch   

 Dimension 

Front panel (unit: mm [inch]) 

Right side diagram (unit: mm [inch]) 

97.00
[3.82]

147.00  [5.79]

 

85.00
[3.35]

 

Mounting dimension (unit: mm [inch]) 

Vertical view (unit: mm) 

Thickness Range 0.5~9mm

135~136.5[5.31~5.37]

85

[3.35]

 

 

 Installation 

Please insert TP04 series to the opening hole of panel and tighten the screws. However, if a firm mounting 
TP04 series to the panel is needed, please use the mounting fixed support accessory which is packed together 
with TP04 series, then insert the fixed support in the back and tighten the screws.   

  If the fixed support is not installed well, Delta will not guarantee the waterproof function. The screw torque 

should be 4-5(kg-cm). DO NOT exceed this specification when tightening the screws; otherwise TP04 series 
may be damaged.   

Notes: The flat surface should be a UL Type 4 "Indoor Use Only" enclosure or equivalent (IP65/NEMA4). Please refer to 
the figures below. 

Thickness: 0.5~9.0mm

Please leave sufficient space (more than 50mm ) 
around the unit for heat dissipation.

 

 

    Specifications 

 Function Specifications

 

Item 

TP04G-AS2 

Screen type 

STN-LCD 

Display color 

Monochromatic 

Backlight 

The back-light automatic turn off time is 1 ~ 99 minutes (0 = DO NOT turn off) 
(The back-light life is about 50 thousand hours at 25°C) 

Resolution 

128x64 dots 

Display range 

(W) x (H) = 72 x 40 (unit: mm); 3.00” (diagonal preferred) 

Contrast adjustment 

10 levels of adjustment 

Language/Font 

ASCII: (Code page 850) Alphanumeric (including European characters) 
Taiwan: (Big 5 codes) Traditional Chinese Fonts 
China: (GB2324-80 codes) Simplified Chinese Fonts 

5×8 dots 

25 characters×8 rows 

8×8 dots 

16 characters×8 rows 

8×12 dots 

16 characters×5 rows 

Display 
text 

8×16 dots 

16 characters×4 rows 

Font Size 

ASCII: 5×8, 8×8, 8×12, 8×16 

Alarm LED indicator (RED) 

1. Power on indication (Blink for three times); 2. Communication error alarm; 
3. Special indication by user programming. 

RS-232 LED indicator 
(yellow) 

It will blink when transmitting program and communicating by using RS-232.   

Display 
screen 

RS-485/RS-422 
LED indicator (green) 

It will blink when communicating by using RS-485/RS-422. 

Program memory 

256KB flash memory 

RAM of system 

32K Byte 

Serial communication port 
RS-232 (COM1)   

Unsynchronized transmission method: RS-232; 
Data length: 7 or 8 bits, Stop bits: 1 or 2 bits; Parity: None/Odd/Even;   
Transmission speed: 9,600 bps ~ 115,200 bps; RS-232: 9 PIN D-SUB male. 

Extension communication 
port RS-422 (COM1) 
RS-485 (COM2)   

Unsynchronized transmission method: RS-485 / RS-422; Data length: 7 or 8 bits; 
Stop bits: 1 or 2 bits; Parity: None/Odd/Even; Transmission speed: 9,600 bps ~ 
115,200 bps; RS-422: 9 PIN D-SUB male; RS-485: 5 PIN removal terminal. 

Extension interface 

1.  Update firmware version. 2. The slot for program copy card.     

Battery cover 

3V DC battery for HMI 

External 
interface 

5 PIN removal terminal 

Include 24V DC input and RS-485 communication input 

 Electrical Specifications 

Specifications 

TP04G-AS2 

Communication interface 

COM1: RS-232/RS422; COM2: RS-485. 

Waterproof class of front panel 

IP65/NEMA4 

Operating temperature for hardware  0 ~ 50°C; 20 ~ 90% RH (non-condensing)   

Storage temperature for hardware 

-20 ~ 60°C 

Vibration 

5Hz

f

9Hz = Continuous: 1.75mm/Occasional: 3.5mm   

9Hz

f

150Hz = Continuous: 0.5g/Occasional: 1.0g 

Shock 

15g peak, 11ms duration, half-sine, three shocks in each direction per axis,   
on 3 mutually perpendicular axes (total of 18 shocks) 

Radiated emission 

CISPR11, Class A 

Electrostatic discharge immunity   

EN61000-4-2 

Radiated immunity   

EN61000-4-3 

Electrical fast transient   

EN61000-4-4 

Weight/dimensions 

0.24kg; 147×97×35.5mm (Width(W)×Height(H)×Deep(D)) 

Cooling method 

Natural air cooling 

 Password Function 

1. If the user forgot the password, the password can be cleared by using the following code: 

8888

. This 

universal code will clear the password and all TP04 series internal programs. The TP04 series will be reset to 
the factory settings by using this code also. Please pay close attention when using it.

 

2. The password can be the alphabet from A to Z or the number from 0 to 9. But it must use the function keys F0 

~ F9 to input the password characters. Please refer to the following table. 
F0/F5: Scrolls in a loop as follows 0

5

A

B

C

D

E

F

F1/F6: Scrolls in a loop as follows 1

6

G

H

I

J

K

F2/F7: Scrolls in a loop as follows 2

7

L

M

N

O

P

F3/F8: Scrolls in a loop as follows 3

8

Q

R

S

T

U

V

F4/F9: Scrolls in a loop as follows 4

9

W

X

Y

Z

 Hardware Operation 

When the user wants to startup TP04 series, a 24V DC power is needed. After applying 24V DC power to 
TP04 series, it will enter into the startup display and then enter the user-designed program. Pressing Esc key 
and holding on for 5 seconds can return to system menu. There are five selections in the system menu and 
are described below.

 

Selections 

Explanation 

Download program 

Use the connection cable (DVPACAB530) to connect the TP04 serial communication port RS-232 to 
a PC. Then use the TPEditor software to download an application program to TP04. 

Upload program 

Use the connection cable (DVPACAB530) to connect the TP04 serial communication port RS-232 to 
a PC. Then use the TPEditor software to upload an application program from TP04. 

Copy program 

Transfer a program between two TP04 units. 
1: transmit programs. 2: receive programs 
When transmit programs and data between two TP04 units. Set one TP04 to “Receive Program” 
mode and the other TP04 to “Transmit Program” mode. Please use twisted pair wires to connect the 
two units via the RS-485 ports. 

TP04 settings 

There are 9 items that used to modify TP04 system settings: 
1.  Communication protocol: Setting the address of TP04, the control port of PLC, and the 

communication string for either RS-232 or RS-485. 

2.  Contrast: Adjust the contrast of LCM display screen. 
3.  Back-light: adjust the automatic turn off time of LCM. Setting range is 00 ~ 99 minutes. If set to 

00, the LCM Back-light will not turn off. 

4.  Date and Time: It is used to set the TP04 built-in RTC including year, month, day, hour, minute, 

second and week. Also the internal battery capacity display is shown here. 

5.  Buzzer: Used to set the buzzer sound, normal mode or quiet mode. 
6.  Language Setting: Used to set the displayed language. English, Traditional Chinese, Simplified 

Chinese or user defined language. 

7.  Password setting: Used to set, enable, and disable the password function. If the password 

function is enabled, it will require the user to input a password before entering any system menu. 
The factory password is 

1234

8.  Startup display: Used to select the TP04 startup display. User can select “user defined” to use the 

file that designed by TPEditor and download to TP04. 

9.  Comm. indicator: The user can determine if the RS-232 and RS-485 LEDs will blink or not during 

communication.   

PLC connection 

There are three methods to connect to PLC: 
1.  Using TP04 serial communication port (COM1) RS-232: set 8-pin DIP switch to RS-485 mode 

and connect the cable (DVPACAB215 or DVPACAB230) to program communication I/O 
RS-232C of PLC. 

2.  Using extension communication port (COM2): set 8-pin DIP switch to RS-485 mode and connect 

5-pin removal terminal of extension communication port to RS-485 of PLC with twisted pair. 

3.  Using extension communication port (COM2): set 8-pin DIP switch to RS-422 mode and connect 

four pins (6, 7, 8, 9) of 9 PIN D-SUB male to RS-422 of PLC with 4-wire cable. 

Execution 

Execute the internal program that download from TPEditor or transmitted from other TP04 units. 
When program is in execution, the user can return to system menu by pressing Escape/Exit (Esc) 
key for 5 seconds. 

 Communication Connection 

 

TP04G may connect to a PC by using connection able DVPACAB515

 

PC or TP02 / 04G

1

5

6

9

9 PIN D-SUB

TO PC (RS-2 32)

TO TP0 2 / 04G

5

1

9

6

9 PIN D-SUB

 

9  PIN D-SUB female

Rx 

2

GND     5

5       GND

PC  COM Port

9  PIN D-SUB female

Tx

Rx

TP02 / 04G COM Port

Tx 

3

 

 

TP04G may connect to a DVP-PLC by using connection  cable DVPACAB215/DVPACAB230/ 
DVPACAB2A30

 

1.  DVPACAB215/DVPACAB230 

TO  P C o r TP 02 / 04 G 

1

13

14

1

5

6

9

25 P IN D-S UB

9 P IN D-SU B

TO P LC

M INI DIN TER MIN AL 

 

2.  DVPACAB2A30 

TO  P C o r TP 02 / 0 4G 

1

5

6

9

9 P IN D-SUB

TO P LC

MINI DIN TERMINAL 

 

8 PIN MINI DIN

25 PIN D-SUB female

PC / TP CO M Po rt

PLC CO M1 Port

Tx 

2

GND

7

 

8 PIN MINI DIN

9 PIN D-SUB fe male

PC / TP CO M P ort

PLC CO M1 Port

Rx 

2

GND    5

6
8

2 0

4
5

1
4
6

7
8

4       Rx 

8       G ND
1 ,2    5 V

1

2

3

4

5

6

7

8

5       Tx

Rx       3

Tx       3

 

 

1

2

3

4

5

6

7

8

4       Rx 

8       G ND
1 ,2    5 V

5       Tx 

 

 

The Pin definition of 9 PIN D-SUB 

1.  RS-232 

3       Tx 

5       GND

RS-232  9 PIN D- SUB male

TP 02 / 0 4G COM Po rt

2       Rx 

 

2.  RS-422 

8       Tx +

RS-422  9 P IN D-S UB male

9       Tx -

TP 02 / 04G COM Port

7       Rx -

6       Rx +

 

3.  DVPACAB630 (RS-422) 

TO  TP02 / 04G 

1

5

6

9

9 PIN D-SUB

TO PLC

MINI DIN TERMINAL 

 

8 PIN MINI DIN

9 P IN D-S UB female

TP 02 / 04G COM Port

MIT SUBIS HI  F X-P LC 

1

2

3

4

5

6

7

8

Tx+      8

 

2       Rx+

3       S G

GND    5

COM1 Port RS -422

7       Tx+ 

Rx+ 

6

Rx - 

7

4       Tx - 

Tx -      9

1       Rx -

 

 

Switch between RS-422/RS-485 (by using 8-PIN DIP switch) 

8-PIN DIP switch 

RS-485 

RS-422 

SW1 ~ SW4 

On 

Off 

SW5 ~ SW8 

Off 

On 

 Battery Life and Precision of Calendar 

Timer 

 

Battery Life 

Temperature (°C) 

-20 

20 

60 

Life (Year) 

1.972 

2.466 

2.712 

2.835 

 

 

Precision of Calendar Timer

 

1. At 0°C/32°F, less than -117 seconds error per month.   

2. At 25°C/77°F, less than 52 seconds error per month. 

3. At 55°C/131°F, less than -132 seconds error per month. 

 

 

注意事項 

 

請在使用之前,詳細閱讀本使用說明書。

 

 

實施配線,務必關閉電源。

 

 

本機顯示操作面板防水,但對油污或具腐蝕性之液體不具防護作用,避免以尖銳之物品刮傷面板使用時請注

意。

 

 

本機輸入電源為直流

24V

,不可連接於

RS-485

通訊口信號端,否則可能造成嚴重的損壞,因此請在上電之前

再次確認電源配線。

 

 

輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。請勿在上電時觸摸任何端子。

 

 

本體上之接地端子

 

 

務必正確的接地,可提高產品抗雜訊能力。

 

 

利用原廠包裝附件之固定架,鎖緊面板固定螺絲時,請勿太緊以免造成機殼損壞。

 

 產品簡介 

  型號說明

 

 

謝謝您採用台達終端顯示器系列產品。

TP04G-AS2

,解析度

128*64

,最大可顯示

8*4

個中文字,支援多國

文字顯示。

 

 

內建兩個通訊口

  (RS-232

RS-485/RS-422

,可同時使用

)

 

 

內建萬年曆、通訊

/

警告指示

LED

 

 

可外接程式複製單元,快速移植程式,節省程式下載時間。

 

 

內建多種物件圖形可供使用者選用。

 

 

產品外觀及各部介紹

 

LC M

顯示區

RS-232

指示燈

退出 取消鍵

/

命令操作鍵

數值鍵及功能鍵

輸入鍵

警示指示燈

RS-485

指示燈

複合功能鍵

 

 

 

面版功能說明

 

面板元件

 

說明

 

警示指示燈

 

(

紅燈

狀態一:當啟動電源時,指示燈慢慢開始閃爍。

 

狀態二:當異常狀態發生,指示燈會重覆持續亮一秒並發出警報聲。

 

RS-232

指示燈

 

(

黃燈

傳送程式及使用

RS-232

通訊時持續閃爍。

 

RS-485/RS-422

指示燈

 

(

綠燈

使用

RS-485/RS-422

通訊時持續閃爍。

 

LCM

顯示區

 

液晶顯示模組,顯示目前程式狀態。

 

退出

/

取消鍵

 

進入系統選單或輸入值錯誤時可按此鍵,刪除文字敘述等。

 

命令操作鍵

 

UP/Pg Up

:此鍵為向上方向鍵,可作為數值遞增輸入或換至上頁等操作。

 

Pg Dn/DOWN

:此鍵為向下方向鍵,可作為數值遞減輸入或換至下頁等操作。

 

Left

:此鍵為左方向鍵,可作為選擇數值位置操作。

 

Right

:此鍵為右方向鍵。可作為選擇數值位置操作。

 

複合功能鍵

 

此鍵是搭配功能鍵

F0 ~ F9

及其他按鍵作為特殊功能的使用。

 

輸入鍵

 

當輸入值確認正確無誤時,即可按下此鍵。

 

功能鍵

 

F0/F5

:在系統選單操作時可作為

0 (F0) 

5 (Shift+F0) 

的常數輸入鍵,在使用者頁面時可

由使用者定義其個別功能。

 

F1/F6

:在系統選單操作時可作為

1 (F1) 

6 (Shift+F1) 

的常數輸入鍵,在使用者頁面時可

由使用者定義其個別功能。

 

 

繁體中文 

面板元件

 

說明

 

功能鍵

 

F2/F7

:在系統選單操作時可作為

2 (F2) 

7 (Shift+F2) 

的常數輸入鍵,在使用者頁面時可

由使用者定義其個別功能。

 

F3/F8

:在系統選單操作時可作為

3 (F3) 

8 (Shift+F3) 

的常數輸入鍵,在使用者頁面時可

由使用者定義其個別功能。

 

F4/F9

:在系統選單操作時可作為

4 (F4) 

9 (Shift+F4) 

的常數輸入鍵,在使用者頁面時可

由使用者定義其個別功能。

 

 

背面介紹

 

BATTERY 
SWITCH  OR
RS-485/422

 

5 PIN 

端子座

  / 

線徑:

12-24 AWG / 

扭力:

4.5 lb.-inch   

 

外觀尺寸

 

正面圖

  (

單位:

mm

[ ]

inch) 

右側圖

  (

單位:

mm

[ ]

inch) 

97.00
[3.82]

147.00 [5.79]

 

85.00
[3.35]

 

嵌入開孔尺寸

  (

單位:

mm

[ ]

inch) 

俯視圖

  (

單位:

mm) 

135~136.5[5.31~5.37]

85

[3.35]

 0.5~9mm

厚度:

 

 

 

安裝方法

 

人機介面安裝於控制盤的方法,請直接將人機由盤面的正面直接放入即可

  (

嵌入式

)

,若要固定更牢固,可再利用

原廠包裝附件之固定架,嵌入後蓋直接四端凹槽處固定,並上、下平均鎖緊面板固定螺絲即可,如下圖為正確安
裝:(

 

固定螺絲時請以扭力:

4-5 (kg-cm) 

鎖緊,請勿超過此範圍以免破壞面板)

 

注意:該安裝的平面必須是要適用

Type 4 

室內使用或相等條件的配電盤外殼。

 

嵌入式

隔板厚度:

0.5~9.0mm

 

 

Reviews: