DVP-PCC01

 

Program Transfer Module 

Instruction Sheet 

 

1  

Warning 

Please set the RD/WR switch before operating the . 

Do not disconnect PCC01 before Transmission ends; otherwise, it may cause data loss in the PCC01 

Do not change the RD/WR switch during PCC01 operation. 

2  

Introduction 

 

PCC01 can read or write PLC programs, devices (coils and registers) and passwords to all series of PLC via 

COM. It provides rapidly and safely data transmission to PLC. 

 

Applicable Models and Read/Write Device Types: 

Program area   

PLC device area 

Device type 

Models 

Program (Steps) 

D register 

M device 

File register 

DVP-ES/EX/EC/SS 4K 

D0~D599 M0~M1279 

N/A 

DVP-SA/SX/SC 8K D0~D4999 

M0~M4095 

1600 

DVP-EH/SV 16K 

D0~D9999 

M0~M4095 

10000 

 

Product Profile 

 

PO

WE

R

OK

CO

M

ER

A

S

E

D

VP-

PC

C

0

1

ER

R

5

6

33

66.3

300

1

2 3

4

WR

RD

 

 

Unit: mm 

1. Power LED 

4. Error LED 

2. Communication Indicator LED 

5. Operation mode: read/write functional switch 

3. Operation completed LED 

6. PCC01 Data Erase button 

 

Specification 

Data Retention 

10 years 

Write Cycles 

At Least 10,000 times 

Transmission speed 

9600 /19200 bps (PB: 9600 bps only) 

Storage  

-25

~70

  (Temperature), 5~95% (Humidity) 

Operation 

0

~55

  (Temperature), 50~95% (Humidity), Pollution degree 2 

Noise Immunity 

ESD: 

±

4KV Air Discharge 

EFT: Power Line: 2KV 
RS: 0.15MHz~80MHz, 10V/m 
Surge : 

±

1KV 

Vibration / Shock 
Resistance 

International Standard: IEC1131-2, IEC 68-2-6

TEST Fc

 

IEC1131-2 & IEC 68-2-27 (TEST Ea) 

 

3   

Operation and Function Description 

3.1 Read/Write Operation Sequence: 

Step 

 (PLC

PCC01) RD (Read) 

 (PLC

PCC01) WR (Write) 

Set RD/WR switch to “RD” mode 

Set RD/WR switch to “WR” mode and confirm PLC 
is STOP status 

Connect PCC01 to PLC COM1.Reading will start 
after 5sec. waiting. 

Set RD/WR switch to “WR” mode and place the 
PLC RUN/STOP switch in the STOP position. 

After reading data from PLC, “OK” LED will light 

Connect PCC01 to PLC COM1.Writing will start 
after 5 sec. 

Disconnect PCC01 when read process is done. 

Disconnect PCC01 when write process is done. 

3.2 Password 

Function 

 

The PCC01 transfer module can obtain a password from the source PLC along with the program. When the 

program is transferred from the ACPGMXFER to the destination PLC it will compare the password and if the 

password in the PLC matches or no password was previously set the transfer will complete. This will require 

future ACPGMXFER transfers to a password protected PLC to have the same password as the PLC, Also if a 

password is set via the transfer module any WPLSOFT users will be required to enter the password before any 

program changes can be made.   

 

The password is entered into registers D1086 and D1087 and set on by enabling M1086. These addresses 

serve only as an entry point for the password at the source PLC. When the file is ‘Wrote’ to the destination PLC 

the unit will be password protected and registers D1086 and D1087 will not be populated with the password. If 

M1086 is not set on the passwords will be ignored.   

 

The password is set in the source PLC by using the Batch Monitoring feature of the PLC software or hand held 

programmer to enter the password into registers D1086 and D1087. Enter the value in Hexadecimal format, a 

password of 1234 would be entered as follows. H3132 into register D1086 followed by H3334 into register 

D1087. Refer to the table in section 6 for cross reference of valid ASCII characters. Next set M1086 on to make 

this password active.   

 

Connect the transfer module to the source PLC with the switch set to read. This will upload the program and the 

password of 1234. The destination PLC will have to be in the stop mode, next connect the transfer module to 

the destination PLC with the switch set to the “write” position. The transfer module will download the program 

and set the password to 1234. 

 

The password key has four digits. Each digit is 8bits number and form with ASCII in D1086 and D1087. 

Example as follows: 

D1086 

D1087 

     Password Key 

Password setting 

High byte 

Low byte 

High byte 

Low byte 

Byte 1 

Byte 2 

Byte 3 

Byte 4 

ASCII code (HEX) 

1 (0x31=H31) 

2 (0x32=H32) 

3 (0x33=H33) 

4 (0x34=H34) 

3.3  The conditions when PCC01 will read/write to an PLC:(w/ PW: with password; w/o PW: without password) 

Read 

Write 

                              PCC01

PLC Status 

w/o PW 

w/ PW 

w/o PW 

w/ PW 

w/o PW

Able to read 

Password verify error

Unable to write 

Unable to write 

RUN 

w/ PW 

Unable to read 

Unable to read 

Unable to write 

Unable to write 

w/o PW

Able to read 

Password verify error

Able to write 

Able to write and 
write password to 
PLC 

STOP 

w/ PW 

Unable to read 

Unable to read 

Password verify error

Able to write after 
verification 

3.4  PCC01 force PLC in RUN/STOP status 

PCC01 provide Run/Stop function in DVP-ES/EX/EC series MPUs. When PCC01 ERR and OK LEDs are blinking 

simultaneously in WR mode and PLC is in RUN status, user can press the ERASE button within 30 seconds to force 

PLC in STOP After that, disconnect PCC01 from the PLC and then connect to PLC again. Once data write-in is 

completed, push ERASE within 30 seconds while PCC01’s OK LED is ON to switch PLC status from STOP to RUN. 

3.5  PCC01 Data Erase function: 

Once PCC01 connects to PLC, please press and hold the ERASE button within 5 secs. Continue to hold the button 

until the OK LED turns on. Release the button and the ACPGMXFER module can now be removed. 

3.6  Data Duplication Function 

 

Besides program transfer, the PCC01 can also read/write register and coil data to/from the PLC. The PCC01 

will monitor coil M1085 to see if it should read/write the data.    When M1085 is OFF, the PCC01 will read or 

write the data depending on the operation selected. If M1085 is ON he PCC01 will not read or write the data.   

 

Data Duplication steps:   

1.) Set M1085 On/Off in PLC 

2.) Select PCC01 RD/WR switch in reading or writing mode.   

3.) Connect PCC01 to PLC COM1 communication port 

4.) After operation is completed, “OK” LED will turn on. 

5.) Disconnect PCC01 from the PLC. 

3.7  Estimation of Read/Write Operating Timing 

 

M1085=OFF 

M1085=ON 

Model 

Read 

Write 

Read 

Write 

DVP-ES/EX/SS 

35 sec. 

45 sec. 

30 sec. 

35 sec. 

DVP-SA/SX/SC 

1 min. 10 sec. 

1 min. 15 sec. 

1 min. 5 sec. 

1 min. 10 sec. 

DVP-EH/SV 

2 min. 50 sec. 

3 min. 

1 min. 10 sec. 

1 min. 20 sec. 

 

4  Error 

Indication 

PCC01 will show an error or warning status with the ERR and OK LEDs. 

 

Below is the summary: 

Indicator 

Error Message 

ERR 

OK 

Recommend 

 

 

PCC01 Internal memory 
error 

On Off 

PCC01 hardware may be damaged, please replace it. 

 

 

Incompatible model 

Blinking Off 

Make sure PCC01 model record is compatible with PLC 
model. 

 

 

Operation error – unable 
to write 

Synchronous blinking 

PCC01 doesn’t contain a valid program for “WR” mode. 
PCC01 in “WR” mode, and PLC is in RUN mode. Please 
place PLC in STOP mode. 
Communication protocol error! Please confirm the PLC is in 
STOP mode and reboot the PLC. 
Check PLC program syntax. 

 

 

Operation error – unable 
to read 

Cross blinking 

PLC protect with password. 
Communication protocol error! Please confirm PLC in STOP 
mode and remove/apply power to. 

 

 

Password verify error 

On Blinking 

PCC01 is in “RD” mode, and is protected by password. 
Please push erase button when PCC01 connect to the PLC. 
For more detailed operation of erasure, please reference to 
section 3.4. 
PCC01 is in “WR” mode, and PLC is protected by password. 
Please disable the password in PLC, or set the same PLC’s 
password in the PCC01. For more detailed operation , please 
reference to section 3.2. 

 

 

ERASE completed 

Off On 

Please refer to section 3.5. 

 

5  Troubleshooting 

 

If ERR LED is always ON or blinking. Please refer to section 4.   

 

Disconnecting the PCC01 or powering down the PLC when the operation in progress will cause unexpected 

results: 

 

PCC01 in “RD” mode: 

PCC01 data will be invalid. Please reboot the PLC again or re-connect PCC01 to PLC. 

 

PCC01 in “WR” mode: 

PLC program will be invalid. Please reboot PLC again or re-connect the PCC01 to PLC. 

 

6  Appendix: 

ASCII 

Table 

The password composed of 4 bytes. Each byte is an ASCII character of ‘0’~’9’, ‘A’~’Z’. ‘a’ ~’z’. The password is case 

sensitive. Below is ASCII table. 

HEX

A

B

C

D

E

ASCII

 

 

 

 

 

 

HEX

10

11 

12 

13 

14 

15 

16 

17

18

19

1A

1B

1C

1D

1E

1F

ASCII

 

 

 

 

 

 

HEX

20

21 

22 

23 

24 

25 

26 

27

28

29

2A

2B

2C

2D

2E

2F

ASCII

SP

! " # $ % & ' ( ) * + , - . / 

HEX

30

31 

32 

33 

34 

35 

36 

37

38

39

3A

3B

3C

3D

3E

3F

ASCII

0 1 2 3 4 5 6 7 8 9  :  ;  < = > ? 

HEX

40

41 

42 

43 

44 

45 

46 

47

48

49

4A

4B

4C

4D

4E

4F

ASCII

@

A B C D E F G

H

I  J K

L M

N

O

HEX

50

51 

52 

53 

54 

55 

56 

57

58

59

5A

5B

5C

5D

5E

5F

ASCII

P

Q R S T U V W

X

Y

HEX

60

61 

62 

63 

64 

65 

66 

67

68

69

6A

6B

6C

6D

6E

6F

ASCII

` a b C d e f g h i  j k l M

n o 

HEX

70

71 

72 

73 

74 

75 

76 

77

78

79

7A

7B

7C

7D

7E

7F

ASCII

p q r s t u v w x y z {  |  } ~ 

Note: ‘

Denotes invalid ASCII character, do not use.

 

Reviews: