This instruction sheet only provides descriptions for electrical specifications, general specifications, installation and 

wiring. 

 

This is an OPEN TYPE Controller. The DVPPF01-S should be kept in an enclosure away from airborne dust, humidity, 

electric shock risk and vibration. Also, it is equipped with protective methods such as some special tool or key to open 

the enclosure, so as to avoid the hazard to users or any damage to the module. DO NOT touch terminals when power 

on.

 

 

Introduction 

 Functions

 

  Cyclical data exchange process 

  Support the SYNC and FREEZE for data synchronization between master and slaves 

  Support Auto Baud rate detection 

  Support 12MHz baud rate in DP network 

  Cyclical data size is fixed to 4 bytes input and 4 bytes output 

  Support GSD file configures by using configuration tools 

 Product Profile 

3

5

4

1

2

4

8

6

7

6

D

V

P

-P

F

0

1

x16

x16

 

 Model  name 

 Extension  port 

 Power/NET LED 

 Extension hole for mounting unit or module 

 DIN rail clip 

 Extension clip 

 Address switch 

 

 Profibus connector 

 

 Specifications 

 DP Connection 

Interface 

DB9 pin connector 

Transfer method 

High speed RS-485 

Transfer cable 

2-wire twisted shielded cable 

Electrical  isolation 

500V DC 

ENGLISH 

 Communication 

Message types 

DPV0, cyclical data exchange process 

Device ID 

09B9 HEX 

GSD file 

EATN09B9.GSD 

Model name 

DVPPF01-S 

9.6kbps, 19.2kbps, 93.75kbps, 187.5kbps, 500kbps 

Baud rates 

(auto  detected) 

1.5Mbps, 3Mbps, 6Mbps, 12Mbps 

 Environmental Specification 

Noise immunity 

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 

EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV 

Analog & Communication I/O: 1KV 

Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 

RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m 

Environment 

Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2 
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity) 

Vibration/shock 
resistance 

Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)   

IEC 61131-2 & IEC 68-2-27 (TEST Ea) 

Approvals 

 

   

 

Installation & Configuration    

 Dimensions 

 

   

 

D

V

P

-P

F

0

1

x16

x16

NET

POWER

1

0

 

Dimensions are in millimeter and [inch]

 

 Installing the DVPPF01-S with the PLC Controller 

Open the extension cover with a screwdriver. 

Use a screwdriver to lift and unfasten the fixing clip. 

 

 

Connect the DVPPF01-S to extension port of PLC 
controller and fasten the fixing clip. 

Plug the Profibus connector to the socket of 
DVPPF01-S, and tighten screw to secure the 
connector. 

0

1

STO P

D

V

P

-1

2

S

A

RUN

RUN

BAT.LOW

ERROR

POWER

R

S

-2

3

2

R

S

-4

8

5

POWER

C0

X7

Y0

C1

Y1

Y2

Y3

C2

D

V

P

-P

F

0

1

s

X1

X2

X0

X5

X4

X3

X6

s

NET

x16

x16

1

0

 

 

 Cable Length and Baud Rate 

The Maximum cable length in a segment depends on the transmission speed. Profibus-DP communicates at 
speeds from 9.6kbps to 12Mbps over distances from 100 to 1,200 meters. 

Baud rate (bps) 

9.6k 

19.2k 

93.75k 

187.5k 

500k 

1.5M 

3M 

6M 

12M 

Length (m) 

1,200 

1,200 

1,200 

1,000 

400 

200 

100 

100 

100 

Check the extension I/O by WPL software: 

Connect to PLC MPU 

 

 

Once connection is successful, software will check if 32 
inputs/outputs is detected 

 

 PIN Definition of DP Connector 

PIN 

Definition 

Content 

PIN 

Definition 

Content 

-- 

N/C 

VP 

Positive  voltage 

-- 

N/C 

-- 

N/C 

RxD/TxD-P 

Data  receiving/sending 

P (B) 

RxD/TxD-N 

Data  receiving/sending 

N (A) 

-- 

N/C 

-- 

N/C 

DGND 

Data  reference 

potential  (C) 

 

 

 

1

5

9

6

 MAC ID Setting 

Address 

Content 

1…0x7D 

Valid Profibus address 

0 or   

0x7E…0xFF 

Invalid Profibus address. NET LED will rapidly blink with RED when 

node address is at 0, 0x7E…0xFF 

'

x16

'

x16

 

 Setting of DVPPF01-S Connect to Profibus-DP 

Connection example: 

DVP-PF01

Profibus network

DVP-PS01

DVP-12SA

D

V

P

-P

F

0

1

Y3

D

V

P

-1

2

S

A

0

1

R

S

-2

3

2

R

S

-4

8

5

X4

R UN

STO P

C1

Y1

C 2

Y2

X5

X6

Y0

C0

X7

RUN

POWER

BAT .LOW

ERROR

X2

X 1

X0

s

s

X3

x16

x16

N ET

P OWER

PC Master

1

0

 

DVPPF01-S provides fixed 4 bytes input data and 4 bytes output data to user in Profibus-DP system. 4 bytes 

input data are transmitted from DVPPF01-S module to Profibus-DP Master, it are mapping to Y20-Y57 in PLC 

controller when DVPPF01-S is the first extension unit of PLC. 4 bytes output data are transmitted from 

Profibus-DP Master, and it are also mapping to X20-X57 in PLC controller. 

 

 Data Mapping 

 

Following is a ladder program example:

 

M1000

MOV

K4X20

D10

MOV

MOV

MOV

K4X40

D20

D21

K4Y40

K4Y20

D11

 

This program example copies the 4 bytes data from X20-X57 that transmitted by DP master to D10 and D11 

registers in PLC controller. And, PLC controller will write 4 bytes data in D20 and D21 registers to Y20-Y57, 

these 4 bytes data will send to DVPPF01-S, and DVPPF01-S will send these data to DP master. 

 

Troubleshooting

 

 NET LED 

LED status 

Indication 

Corrective actions 

OFF 

No power supply 

Verify DVPPF01-S is powered on 

Red blinking 
(rapidly) 

Invalid Profibus address setting 
via switch 

Check whether the switch setting is valid 

 

Setting range of slave: 1-125 
Set the valid value and re-power 

Red blinking 

Communication link to 
PROFIBUS, and no cyclical 
data  exchanged 

-- 

Red ON 

No connection to Profibus 

Verify that DP network installation is OK 

Verify that PLC is working 

Verify that switch address setting match with configuration in 
DP master 

Green 
blinking 

Reserved 

-- 

Green ON 

Cyclic data exchange in 
progress and OK 

-- 

 Power LED 

LED status 

Indication 

Corrective actions 

Green ON 

Power on 

-- 

OFF 

No power 

Verify that PLC controller is powered on 

 

注意事項 

 

此安裝手冊只提供電氣規格、一般規格、安裝及配線等。

 

 

本機為開放型

  (Open Type) 

機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊

/

衝擊意

外之外殼配線箱內。另必須具備保護措施

  (

如:特殊之工具或鑰匙才可打開

防止非維護人員操作或意外衝擊

本體,造成危險及損壞。請勿在上電時觸摸任何端子。

 

 

產品簡介 

     功能說明    

 

循環資料處理

 

 

支援

SYNC

FREEZE

主站和從站間資料同步化

 

 

支援自動偵測鮑率

 

 

DP

網路中可使用

12MHz

鮑率

 

 

循環資料處理固定為

4 bytes

4 bytes

輸出

 

 

可使用設定工具設定

GSD file 

 

各部介紹

 

3

5

4

1

2

4

8

6

7

6

D

V

P

-P

F

0

1

x16

x16

 

 

機種名稱

 

 

擴充機

/

擴充模組連接口

 

 

電源、

NET

指示燈

 

 

擴充機

/

擴充模組定位孔

 

 

DIN

軌固定扣

 

 

擴充機

/

擴充模組固定扣

 

 

位址旋鈕

 

 

 

Profibus

連接口

 

 

 

規格

 

DP

連線

 

介面

 

DB9

接頭

 

傳輸方式

 

高速的

RS-485 

傳輸線

 

2

絞線式隔離線

 

電氣隔離

 

500V DC 

 

 

繁體中文 

通訊

 

訊息類型

 

DPV0, 

循環式處理資料交換

 

裝置

ID 

09B9 HEX 

GSD

檔案

 

DELT09B9.GSD 

模組名稱

 

DVP-PF01 

9.6kbps, 19.2kbps, 93.75kbps, 187.5kbps, 500kbps 

鮑率(自動偵測)

 

1.5Mbps, 3Mbps, 6Mbps, 12Mbps 

環境規格

 

雜訊免疫力

 

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 

EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV 

Analog & Communication I/O: 1KV 

Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 

RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m 

操作

/

儲存環境

 

操作:

0°C ~ 55°C

(溫度),

50 ~ 95%

(濕度),污染等級

  2 

儲存:

-25°C ~ 70°C

(溫度),

5 ~ 95%

(濕度)

 

耐振動

/

衝擊

 

國際標準規範

  IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea) 

標準

 

IEC 61131-2, UL 508 

標準

 

 

安裝與設定

 

 

外觀圖

 

 

 

 

D

V

P

-P

F

0

1

x16

x16

NET

POWER

1

0

 

單位

: mm [inches]

 

 

Reviews: