Warning
This instruction sheet only provides descriptions for electrical specifications, general specifications, installation and
wiring.
This is an OPEN TYPE Controller. The DVPPF01-S should be kept in an enclosure away from airborne dust, humidity,
electric shock risk and vibration. Also, it is equipped with protective methods such as some special tool or key to open
the enclosure, so as to avoid the hazard to users or any damage to the module. DO NOT touch terminals when power
on.
Introduction
Functions
•
Cyclical data exchange process
•
Support the SYNC and FREEZE for data synchronization between master and slaves
•
Support Auto Baud rate detection
•
Support 12MHz baud rate in DP network
•
Cyclical data size is fixed to 4 bytes input and 4 bytes output
•
Support GSD file configures by using configuration tools
Product Profile
3
5
4
1
2
4
8
6
7
6
D
V
P
-P
F
0
1
x16
x16
Model name
Extension port
Power/NET LED
Extension hole for mounting unit or module
DIN rail clip
Extension clip
Address switch
Profibus connector
Specifications
DP Connection
Interface
DB9 pin connector
Transfer method
High speed RS-485
Transfer cable
2-wire twisted shielded cable
Electrical isolation
500V DC
ENGLISH
Communication
Message types
DPV0, cyclical data exchange process
Device ID
09B9 HEX
GSD file
EATN09B9.GSD
Model name
DVPPF01-S
9.6kbps, 19.2kbps, 93.75kbps, 187.5kbps, 500kbps
Baud rates
(auto detected)
1.5Mbps, 3Mbps, 6Mbps, 12Mbps
Environmental Specification
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Environment
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)
Vibration/shock
resistance
Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)
IEC 61131-2 & IEC 68-2-27 (TEST Ea)
Approvals
Installation & Configuration
Dimensions
D
V
P
-P
F
0
1
x16
x16
NET
POWER
1
0
Dimensions are in millimeter and [inch]
Installing the DVPPF01-S with the PLC Controller
Open the extension cover with a screwdriver.
Use a screwdriver to lift and unfasten the fixing clip.
Connect the DVPPF01-S to extension port of PLC
controller and fasten the fixing clip.
Plug the Profibus connector to the socket of
DVPPF01-S, and tighten screw to secure the
connector.
0
1
STO P
D
V
P
-1
2
S
A
RUN
RUN
BAT.LOW
ERROR
POWER
R
S
-2
3
2
R
S
-4
8
5
POWER
C0
X7
Y0
C1
Y1
Y2
Y3
C2
D
V
P
-P
F
0
1
s
X1
X2
X0
X5
X4
X3
X6
s
NET
x16
x16
1
0
Cable Length and Baud Rate
The Maximum cable length in a segment depends on the transmission speed. Profibus-DP communicates at
speeds from 9.6kbps to 12Mbps over distances from 100 to 1,200 meters.
Baud rate (bps)
9.6k
19.2k
93.75k
187.5k
500k
1.5M
3M
6M
12M
Length (m)
1,200
1,200
1,200
1,000
400
200
100
100
100
Check the extension I/O by WPL software:
Connect to PLC MPU
Once connection is successful, software will check if 32
inputs/outputs is detected
PIN Definition of DP Connector
PIN
Definition
Content
PIN
Definition
Content
1
--
N/C
6
VP
Positive voltage
2
--
N/C
7
--
N/C
3
RxD/TxD-P
Data receiving/sending
P (B)
8
RxD/TxD-N
Data receiving/sending
N (A)
4
--
N/C
9
--
N/C
5
DGND
Data reference
potential (C)
1
5
9
6
MAC ID Setting
Address
Content
1…0x7D
Valid Profibus address
0 or
0x7E…0xFF
Invalid Profibus address. NET LED will rapidly blink with RED when
node address is at 0, 0x7E…0xFF
'
x16
'
x16
Setting of DVPPF01-S Connect to Profibus-DP
Connection example:
DVP-PF01
Profibus network
DVP-PS01
DVP-12SA
D
V
P
-P
F
0
1
Y3
D
V
P
-1
2
S
A
0
1
R
S
-2
3
2
R
S
-4
8
5
X4
R UN
STO P
C1
Y1
C 2
Y2
X5
X6
Y0
C0
X7
RUN
POWER
BAT .LOW
ERROR
X2
X 1
X0
s
s
X3
x16
x16
N ET
P OWER
PC Master
1
0
DVPPF01-S provides fixed 4 bytes input data and 4 bytes output data to user in Profibus-DP system. 4 bytes
input data are transmitted from DVPPF01-S module to Profibus-DP Master, it are mapping to Y20-Y57 in PLC
controller when DVPPF01-S is the first extension unit of PLC. 4 bytes output data are transmitted from
Profibus-DP Master, and it are also mapping to X20-X57 in PLC controller.
Data Mapping
Following is a ladder program example:
M1000
MOV
K4X20
D10
MOV
MOV
MOV
K4X40
D20
D21
K4Y40
K4Y20
D11
This program example copies the 4 bytes data from X20-X57 that transmitted by DP master to D10 and D11
registers in PLC controller. And, PLC controller will write 4 bytes data in D20 and D21 registers to Y20-Y57,
these 4 bytes data will send to DVPPF01-S, and DVPPF01-S will send these data to DP master.
Troubleshooting
NET LED
LED status
Indication
Corrective actions
OFF
No power supply
Verify DVPPF01-S is powered on
Red blinking
(rapidly)
Invalid Profibus address setting
via switch
Check whether the switch setting is valid
Setting range of slave: 1-125
Set the valid value and re-power
Red blinking
Communication link to
PROFIBUS, and no cyclical
data exchanged
--
Red ON
No connection to Profibus
Verify that DP network installation is OK
Verify that PLC is working
Verify that switch address setting match with configuration in
DP master
Green
blinking
Reserved
--
Green ON
Cyclic data exchange in
progress and OK
--
Power LED
LED status
Indication
Corrective actions
Green ON
Power on
--
OFF
No power
Verify that PLC controller is powered on
注意事項
此安裝手冊只提供電氣規格、一般規格、安裝及配線等。
本機為開放型
(Open Type)
機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊
/
衝擊意
外之外殼配線箱內。另必須具備保護措施
(
如:特殊之工具或鑰匙才可打開
)
防止非維護人員操作或意外衝擊
本體,造成危險及損壞。請勿在上電時觸摸任何端子。
產品簡介
功能說明
•
循環資料處理
•
支援
SYNC
及
FREEZE
主站和從站間資料同步化
•
支援自動偵測鮑率
•
在
DP
網路中可使用
12MHz
鮑率
•
循環資料處理固定為
4 bytes
和
4 bytes
輸出
•
可使用設定工具設定
GSD file
各部介紹
3
5
4
1
2
4
8
6
7
6
D
V
P
-P
F
0
1
x16
x16
機種名稱
擴充機
/
擴充模組連接口
電源、
NET
指示燈
擴充機
/
擴充模組定位孔
DIN
軌固定扣
擴充機
/
擴充模組固定扣
位址旋鈕
Profibus
連接口
規格
DP
連線
介面
DB9
接頭
傳輸方式
高速的
RS-485
傳輸線
2
絞線式隔離線
電氣隔離
500V DC
繁體中文
通訊
訊息類型
DPV0,
循環式處理資料交換
裝置
ID
09B9 HEX
GSD
檔案
DELT09B9.GSD
模組名稱
DVP-PF01
9.6kbps, 19.2kbps, 93.75kbps, 187.5kbps, 500kbps
鮑率(自動偵測)
1.5Mbps, 3Mbps, 6Mbps, 12Mbps
環境規格
雜訊免疫力
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
操作
/
儲存環境
操作:
0°C ~ 55°C
(溫度),
50 ~ 95%
(濕度),污染等級
2
儲存:
-25°C ~ 70°C
(溫度),
5 ~ 95%
(濕度)
耐振動
/
衝擊
國際標準規範
IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea)
標準
IEC 61131-2, UL 508
標準
安裝與設定
外觀圖
D
V
P
-P
F
0
1
x16
x16
NET
POWER
1
0
單位
: mm [inches]