English-3
For use on a flat surface of a Type 4X "Indoor Use Only" enclosure or equivalent.
The allowable thickness of the panel for mounting should be less than 5 mm.
Installation Method:
Step 1:
Ensure to put waterproof gasket into HMI and
then insert the HMI into the panel cutout.
Step 2:
Ensure to insert fasteners into the HMI’s insertion
slots and turn the screw till screws touch panel
cutout.
Step 3:
Turn the screw with less than torque 0.7N.M to
avoid damage to plastic box.
Torque: 6.17lb-inch (0.7N-M)
Step 4:
Keep at least 60mm distance from rear of HMI
product to the wall, installation surface or the other
controllers for heat dissipation.
The size of the fastener.
16
16.
3
20.
4
Wiring
Recommended wiring is in the table below:
Type
Wire Gauge (AWG)
Stripped length
Torque
Solid
28 ~ 12
7 ~ 8 mm
5 kg-cm
(
4.3 lb-in)
Stranded
30 ~ 12
7 ~ 8 mm
5 kg-cm (4.3 lb-in)
Units: mm
Units: mm
Summary of Contents for Network Device DOP-B
Page 1: ...5011665702 2008 12 30 HB02...
Page 17: ...2 10 20 C to 60 C 4 F to 140 F 10 90 Type 4X 5mm...
Page 23: ...8 DOP B07S200 DOP B07S201 DOP B07E205 A F1 F2 F3 F4 Y Z SYS B C D C B A D...
Page 24: ...9 DOP B07S211 DOP B07E215 A F1 F2 F3 F4 Y Z SYS B C D C B A D...
Page 31: ...2 10 20 C to 60 C 4 F to 140 F 10 90 Type 4X 5mm...
Page 37: ...8 DOP B07S200 DOP B07S201 DOP B07E205 A F1 F2 F3 F4 Y Z SYS B C D C B A D...
Page 38: ...9 DOP B07S211 DOP B07E215 A F1 F2 F3 F4 Y Z SYS B C D C B A D...