ADP485-01 is an OPEN-TYPE. Please place the module in an enclosure away from airborne dust or high 

humidity and prevent electric shock or sudden shock on ADP485-01. Also, it is equipped with protective 

method such as some special tool or key to open the enclosure, so as to avoid the hazard to users or any 

damage to the module. Do NOT touch terminals when power on. 

 

When many devices are connecting in serial, their Baud rate and communication format setting should be 

the same. Also, each device must have individual Unit Address. 

 

I/O terminal screw should be tightened between 1.95kg-cm (1.7 in-lbs). Use copper conductor only, 

60/75°C. 

 

Introduction 

ADP485-01 is mainly designed to connect Delta product by RS-485 interface. It is equipped with surge 

absorber and limited current protection to ensure safe connection of different devices. Also, 120

 

terminating resistance selection is available. This module enables Delta products to connect one 

another by RS-485 interface with much concern of safety and wide application. 

ADP485-01  offers  four  different  connectors  to  enable  the  network  connection  for  Delta’s  PLC  DVP 

series, HMI DOP series, AC Motor Drive VFD series and Servo drive ASD series. 

 

Product Profile 

32

6

60

3

1

0

6

,8

9

0

6

8

7

3,4

1
2
3
4
5

 

Unit: mm 

1

 

Mounting  plate 

5

 

ON/OFF of terminating resistor (default setting: OFF) 

2

 

COM1 (DB9 female) 

6

 

DIN rail (35mm) 

3

 

COM2 (DB9 male) 

7

 

RS-485 port 

4

 

Nameplate 

8

 

RJ12 

 

Optional Connecting Cable 

  ADPCAB03A: ADP485-01 

 ASD-A connecting cable/30cm 

  ADPCAB03B: ADP485-01 

 ASD-B connecting  cable/30cm 

 

 

ENGLISH 

 

RS-485 Network Connection with Delta Products

 

ADP485-01 

 VFD (AC Motor Drive) 

RS-485 network

RJ12

 

ADP485-01 

 DOP (HMI) 

RS-485 network

F1

F3

F2

HMI DOP Series

COM1 COM2

one by one wiring 

DB9 male connector

DB9 male connector

 

connect to COM 1

 

 

ADP485-01 

 ASD-A (Servo Drive) 

RS-485  network

Connecting cable (ADPCAB03A)

 

ADP485-01 

 ASD-B (Servo Drive) 

RS-485 network

Connecting cable (ADPCAB03B)

 

 Environmental Specification 

Environment 

Operation

 

0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollutant degree 2 

Storage

 

-25°C ~ 70°C (temperature), 5 ~ 95% (humidity) 

Vibration/Shock 

resistance

 

International  Standard:  IEC 61131-2, IEC  68-2-6  (TEST  Fc)/IEC 61131-2  & IEC 

68-2-27 (TEST Ea) 

 COM1, COM2, and RJ12 PIN Explanation 

COM1-DB9 female 

RJ12-VFD 

1
2
3
4
5

6
7
8
9

 

 

PIN 

Definition 

PIN 

Definition 

RS485- 

+15V 

RS485+ 

GND 

RS485+ 

SG- 

RS485- 

SG+ 

5, 6, 7, 8, 9: NC 

 

5, 6: Reserved 

 

COM2-DB9 male 

RJ12-ADP485-01 

5

2
1

4
3

6

7

8

9

 

 

PIN 

Definition 

PIN 

Definition 

3, 6 

RS485- 

RS-485+ 

RS485+ 

RS-485- 

5, 9 

GND 

GND 

1, 2, 4, 7: NC 

 

1, 2, 6: NC 

 

Use of Terminating Resistance

 

In all RS-485 installations, the cable must be correctly terminated with two sets of resistors, one set at 

each end of the network (4,000 feet maximum total cable length). This applies even if you are only 

using  one slave node connected to one master device. The terminating resistors prevent  reflection 

problems that can interfere with data transmission. The resistance value of the terminating resistors 

should match the characteristic impedance of the cable. A typical value is 120 ohms. The terminating 

resistors must be placed at the two farthest ends of the RS-485 network, regardless of where the 

master device is. In some cases master device RS-485 ports have built in or optional terminating 

resistors. Beware of your network (whether it has one node or 32 nodes) having only two sets of 

terminating resistors. 

Termination Resistor Switch

 

 Cable Connection 

ADPCAB03A 

 

DB9 male

1394 male

1
2
3
4
5
6
7
8
9

1

5
6

3

2
4

RS485 -

RS485 +

GND

 

ADPCAB03B 

 

DB9 male

Mini DIN

1
2
3
4
5
6
7
8
9

8
1

3
6

RS485 -

RS485 +

GND

 

 

注意事項 

 

本機為開放型

  (Open Type) 

機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電

擊或衝擊意外之外殼配線箱內。另必須具備保護措施

  (

特殊之工具或鑰匙才可打開

防止非維護

人員操作或意外衝擊本體,造成危險及損壞。請勿在上電時觸摸任何端子。

 

 

在串聯通訊各個節點所連接之裝置,其通訊速率

  (Baud rate) 

及通訊格式

  (Format) 

必須設定相同以

及每個節點必須有獨立之站號位址

  (Unit address)

 

 

/

入配線端子鏍絲扭力為

1.95kg-cm (1.7 in-lbs)

,只能使用

60°C/75°C

之銅導線。

 

 

產品簡介 

本產品為一轉接器,主要用於台達機電產品

  RS-485

串聯通訊連接之用,本轉接器內建有突波吸收及限

流保護裝置,對於連接於

ADP485-01

的裝置,供了更好的保護。另外並提供終端電阻

  (120

選擇開關,

不需外加。因此本產品提供台達機電產品在

RS-485

連線、保護及應用非常方便的介面轉接器。

 

ADP485-01

提供四種不同型式之插座以搭配台達機電產品

  PLC DVP

系列、人機介面

  DOP

系列、變頻器

 

VFD

系列、伺服驅動器

ASD

系列使用,提供相互間

  RS485

通訊連線使用。

 

  產品外觀 

32

6

60

3

1

0

6

,8

9

0

6

8

7

3,4

1
2
3
4
5

 

尺寸單位:

mm 

1

 

固定板

 

5

 

終端電阻選擇開關(出廠設定值為

OFF

 

2

 

COM1 (DB9

母座

)

 

6

 

DIN

軌糟

  (35mm)

 

3

 

COM2 (DB9

公座

)

 

7

 

RS-485

連接口

 

4

 

銘牌

 

8

 

RJ12

連接口(連接變頻器)

 

  選購連接線 

ADPCAB03A

ADP485-01 

 

台達伺服驅動器

ASD-A

連接線

/30

公分

 

ADPCAB03B

ADP485-01 

 

台達伺服驅動器

ASD-B

連接線

/30

公分

 

 

 

 

繁體中文 

 

台達機電產品

RS-485

網路連接圖

 

ADP485-01 

 VFD

變頻器

 

RS-485

網路

RJ12

VFD  Series

 

ADP485-01 

 DOP

人機介面

 

RS-485

網路

F1

F3

F2

人機介面 

DOP

COM1 COM2

 1

接線

DB9

公頭

DB9

公頭

 

連接於 

COM 1

 

Reviews: