41
P0428
Voltage limit of
voltage controller
100
130
%
110
Percentage of motor
rated voltage
P0459 Kp of current loop
15
P0460 Ki of current loop
522
P0886
Bandwidth of current
loop decouple filter
0
65535
0.01Hz
1000
P0887
Adjustment
coefficient of current
loop decouple
0
100
%
100
Table 4-20 Encoder configuration
ID
Parameter
Min
Max
Unit
Default
Description
P0545 Encoder resolution
0
65535
PPR
5000
P0546
Counting period of
encoder M method
0
65535
us
2500
P0547
Counting clock
frequency of
encoder T method
0
65535
MHz
8
P0548
Switching speed of
encoder MT
rpm
339
P0549
Maximum error of
encoder speed
detection
0.01
rpm
120
P0550
Bandwidth of
encoder speed filter
10
1000
Hz
100
4-3 Protection parameters
Table 4-21 Input over current(software)
ID
Parameter
Min
Max
Unit
Default
Description
P1073
Threshold of input
over current
0
1000
%
200
While both of MCB and switch of startup cabinet are close, if the RMS value of three
phase input current is higher than threshold of input over current(P1073), input over
current(software) fault is generated.
Table 4-22 Input phase loss
ID
Parameter
Min
Max
Unit
Default
Description
P0489
Voltage threshold of
input phase loss
0
100
%
20
P1251
Fault duration time:
Input Phase Loss
0
65535
ms
80
If the unbalanced degree of input voltage is higher than voltage threshold of input phase
loss(P4089) in a duration time of P1251, input phase loss fault is generated.
Summary of Contents for MVF2000 Series
Page 2: ......