background image

 

 

Specification and Manual 

 

 

Customer :   

 

 

Description :   

Air Conditioner for Equipment (Through Wall Mounting)

 

Customer Part No. :                                                                              Rev.:   

Delta Model No. :           

HEC1200PB

                                            Rev :   

02 

Sample Date Code:   

Sample Issue Date :    SEP.15 2020 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DELTA ELECTRONICS, INC. 

252, SHANG YING ROAD, KUEI SAN 

TEL : 886-(0)3-3591968 

TAOYUAN CITY 333, TAIWAN 

  FAX : 886-(0)3-3591991 

 

 

Please send one copy of this specification back after you 

signed approval for production pre-arrangement   

Approved by : 

Date : 

 

Summary of Contents for HEC1200PB

Page 1: ...ev Delta Model No HEC1200PB Rev 02 Sample Date Code Sample Issue Date SEP 15 2020 DELTA ELECTRONICS INC 252 SHANG YING ROAD KUEI SAN TEL 886 0 3 3591968 TAOYUAN CITY 333 TAIWAN FAX 886 0 3 3591991 Please send one copy of this specification back after you signed approval for production pre arrangement Approved by Date ...

Page 2: ...ance 12 1 6 Thermal and Airflow 13 2 Electrical Specification 14 2 1 Indicator Connector 14 2 1 1 Power Supply Alarm Connector 14 2 1 2 Protection 15 3 Environmental Condition 17 3 1 Operating Temperature 17 3 2 Storage Temperature 17 3 3 Operation Humidity 17 3 4 Ingress Protection Rating 17 4 Reliability Table 17 5 Safety Certification 17 6 Accessory 18 7 Parameters Table 18 7 1 System Setup 18 ...

Page 3: ...Part no Delta model no HEC1200PB Page 3 9 Reclaim 21 10 Versions 21 ...

Page 4: ... objects on it Please pay attention to the following icons on the package If air conditioner is toppled over slanted or dropped unfortunately please follow below steps a stand for 12 hours to ensure refrigerant pressure stability b power on and execute self test to make sure no alarm happened c air conditioner keeps 1 hour operating and make sure there is no abnormal acoustic noise Safety Notes Pl...

Page 5: ...ling into wall or ceiling do not damage electrical wiring or hidden utilities 8 Be sure to use only the specified accessories and parts for installation work 9 Protective earth connection The enclosure must be earthed at the protective earth terminal Use 2 5 mm2 14 AWG wire and use spring washer to avoid loosening 10 The air conditioner shall be not accessible to the general public 11 The installa...

Page 6: ...conditioner while moving or storage 8 The hole in the bottom of the air conditioner should be connected to a sealed container through a drainpipe 9 The appliance is not to be used by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction 10 Children being supervised not to play with ...

Page 7: ...on for Approval Customer Description Air conditioner for Equipment with 1500 W Rated Cooling Capacity Through Wall Mounting Customer P N Rev Delta model no HEC1200PB Rev 02 Sample revision Date Code Sample issue date Quantity one sets INTERNAL EXTERNAL ...

Page 8: ... method Dimension H x W x D without flange mm inch 700 x 500 x 200 27 7 x 19 8 x 7 9 Application Outdoor Weight Kg lbs 28 0 61 7 Mounting Method Door Side Color optional RAL7035 Environmental Protection Performance Operating Temperature Range C F 10 to 55 14 to 131 Operating Humidity External 0 100 RH Internal 0 80 RH Storage Temperature C F 40 to 70 40 to 158 Storage Relative Humidity RH 5 95 Ref...

Page 9: ...no HEC1200PB Page 9 Power Range Input Voltage VDC 48 Max Operating DC Current A 14 3 Alarm N A Dry Contact Output Key Components Controller Built in Smart Controller Fans Delta High Efficiency Blowers Compressor Rotary DC ...

Page 10: ...Part no Delta model no HEC1200PB Page 10 1 3 Dimension mm inch 1 Material Case SGCC Sheet 2 Finish Powder coating 75 120 uM Color RAL 7035 3 Dimensional Tolerance 1 mm ...

Page 11: ...Part no Delta model no HEC1200PB Page 11 1 4 Mounting Panel Cutout Inside Outside Gasket ...

Page 12: ...can clean the condenser with water directly The external side fan blade can also be cleaned with normal pressure water if there is dust accumulation Please do not use strong water jet to impact the center of fan and the surface of condenser The bottom hole of the air conditioner should be connected to a sealed container through a drainpipe please clear drain holes when the maintenance Please also ...

Page 13: ...l protecting cover is sealed with silicon for IP55 requirement Please do not dismantle the sealed cover or will lose the quality assurance of the compressor 1 6 Thermal and Airflow The internal and external air flow circulation is shown as the figure Through separated mechanism design internal and external air flow won t be mixed since the waste heat can be dissipated from the cabinet to the ambie...

Page 14: ... 3 N A N A 4 N A N A 5 N A N A Pin Description 3 Alarm 4 Alarm System alarm default setup Note Customers can setup the N O or N C by themselves when any alarm happen through display board d1 6 Dry contact Setup Specification Contact rating 60 Vdc 100mA Normal PIN 3 and PIN 4 dry contact output close Any alarms happening PIN 3 and PIN 4 dry contact output open Case Grounding Pin 1 Pin 5 48V DC ...

Page 15: ...ormally and the LED will light in green If the system gets into self test mode and the LED will flash in green Fan In When the inner fan is running normally and the LED will light in green Fan Out When the outer fan is running normally and the LED will light in green C Press Buttons UP or increase DOWN or decrease SET Parametric setup ON OFF ESC Power on off or back 2 1 2 Protection Over current p...

Page 16: ...0PB Page 16 Allow reverse voltage 42 58 VDC Short Ckt If compressor UVW short for any both phase the compressor will not operate Compressor H T protection Tcomp 105 oC Eva L T protection TEVA 0 oC Power on delay for fans compressor ...

Page 17: ...rotection Rating IP55 IEC60529 on external side GR487 on external side 4 Reliability Table Test item Condition High temperature IEC 60068 2 2 Low temperature IEC 60068 2 1 High temp High humidity IEC 60068 2 3 Temperature cycle IEC 60068 2 14 test Nb Vibration ETSI 300 019 1 4 CLASS 4 1 Ingress protection external side IEC 60529 IP55 GR487 Salt fog test external side IEC 60068 2 11 severity 4 6cyc...

Page 18: ...s Table 7 1 System Setup Item System Parameter Default Range d1 1 System Version 2 5 N A d1 2 Alarm Logs 0 0 N A d1 3 Inside over temp Setup 60 oC 40 oC 70 oC d1 4 Auto Self Test Function Enable Enable Disable d1 5 Recovery Default N A N A d1 6 Photo Coupler Normal Status Close Close Open d1 7 Password 000 000 999 d1 8 System Re lock N A N A d2 1 Target temperature 30 oC 25 oC 40 oC ...

Page 19: ...tection 2 2 PWB Temperature Protection 2 3 IPM Temperature Protection 2 4 Amb Temperature Protection 2 5 3 Temperature Sensor Fault Amb Temperature Sensor 3 1 Eva Temperature Sensor 3 2 Cond Temperature Sensor 3 3 Comp Out Temperature Sensor 3 4 PWB Temperature Sensor 3 5 IPM Temperature Sensor 3 6 4 Fan Fault Indoor Fan 4 1 Outdoor Fan 4 2 5 Controller Fault EEPROM 5 1 Current Sensor 5 2 DC Bus V...

Page 20: ...conditioner is running but the cabinet temperature is still high no obvious cooling effect 1 The air conditioner capacity is not match the load of the system 2 The ambient temperature is too high 3 Low efficiency of the condenser 4 Other system failure 1 Check the heating load of the system 2 Ensure the air conditioner operates in correct temperature range 3 Clean the condenser 4 Please contact th...

Page 21: ... of as urban waste It must be taken to a special local authority differentiated waste collection center or to a dealer providing this service 10 Versions REV Description Owner Date 00 Issue SPEC VIC 2017 06 01 01 Modify TUV CE ICON REX LYU 2020 08 13 02 Modify Caution REX LYU 2020 09 15 Recommended a keeps 1 0 meter at least Space tight causes air re0circulation Reduce cooling performance potentia...