background image

 

 

 

Warning 

 

Please read this instruction sheet carefully before use. 

 

DVPAETB series is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, 

humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the 

device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may 

occur. 

 

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur.. Check 

all the wiring again before switching on the power, and DO NOT touch any terminal when the power is switched 

on. 

 Introduction

 

DVPAETB-ID32A/OR16A extension  drive  board  is  designed  for connecting  to DVP32SM11N and 

DVP32SN11TN, the I/O module with multiple points. 

 Product Profile & Outline 

DVPAETB-ID32A 

 

Unit: mm 

 

 

1. 40-pin  header  connector 

4. Bottom  fastening  lock 

2. 36-pin input terminal 

5. 40-pin IDC connection  cable*1 

3. DIN rail clip 

6. DIN rail 

*1: You  can select  Delta’s  standard  accessory DVPACAB7A10 (IDC 40P-40P 1m) 
 

 

DVPAETB-OR16A 

 

Unit: mm 

 

ENGLISH 

1. 2-PIN power input terminal 

7. DIN rail clip 

2.  Power  indicator 

8. Bottom fastening lock 

3. 20-pin  header  connector 

9. 20-pin IDC connection  cable*2 

4. Output indicator 

10. DIN rail 

5. Output relay 

11. Output point  action indicator 

6. 9-pin+11-pin output terminal 

 

*2: You  can  select  Delta  standard  accessory DVPACAB7B10 (IDC 40P-20Px2 1m) 

 Model Explanation 

Input Unit 

Output  Unit 

Model Name 

Power 

Points 

Type 

Points 

Type 

DVPAETB-ID32A 

N/A 

32 

DC Type 

Sink/Source 

N/A 

DVPAETB-OR16A 

24V DC 

N/A 

16 

Relay 250V AC/30V DC 

2A/1 point, 5A/COM. 

 Connection Cable 

Model  Name 

Length 

Pins 

Connector 

Applicable  PLC  (accessory) 

DVPACAB7A10 

1m 

40P-40P 

IDC connector  on 

both  sides 

DVP32SM11N  (DVPAETB-ID32A) 

DVPACAB7B10 

1m 

40P-20Px2 

IDC connector  on 

both  sides 

DVP32SN11TN  (DVPAETB-OR16A) 

 Specifications

 

 Electrical Specifications 

 

  Model 

  Item 

DVPAETB-ID32A 

DVPAETB-OR16A 

Insulation  resistance 

> 5M

 (all I/O point-to-ground: 500V  DC) 

Operation/storage 

environment 

Operation: 0 ~ 55°C (temperature), 50 ~ 95% (humidity),  pollution  degree 2 

Storage: -25 ~ 70°C (temperature), 5 ~ 95% (humidity) 

Weight (g) 

166g 

216g 

 Input Point 

Type 

DC (There is no actual input device. Please refer to spec. of DVP32SM11N.) 

Input format 

DC (SINK or SOURCE) 

Input  voltage/current 

24V DC 5mA 

Off 

 On more  than 16V DC 

Action  level 

On 

 Off less  than 14.4V DC 

Response  time 

Approx. 10ms 

Circuit isolation/operation 

instruction 

By  internal  photocoupler /  LED  indicators 

 Output Point 

Type 

Relay-R 

Current  specification 

2A/1point (5A/COM) 

Voltage  specification 

< 250V AC, 30V DC 

75VA (inductive) 

Maximum load 

90W (resistive) 

Response  time 

Approx. 10ms 

 Installation & Wiring

 

 Terminals of Digital I/O Extension Unit 

ID32A 

X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36

X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37

S/S S/S

S/S S/S

 

OR16A

 

Y1 Y2 Y3 C1 Y4 Y5 Y6 Y7 C2 Y10 Y11 Y12 Y13 C3 Y14 Y15

C0 Y0

Y14 Y15

+24V

GND

Y1 Y2 Y3

Y4 Y5 Y6 Y7

Y10 Y11 Y12 Y13

Y14 Y15

Y0

Y14 Y15

 

 Installation 

How  to  install DIN rail: 

 

Fix  one side  first. 

Next, insert the drive board into the DIN rail and 

check if  the board is tightly knitted to the rail.   

To uninstall the board, push up the board and pull it 

out. Follow the steps as  indicated in the figure. 

Configuration of output points in the connection of DVP32SN11TN and DVPAETB-OR16A: 

 

Environment  Notice: 

 

 

DO NOT

 install the board in the environment with dust, smoke, metallic debris, corrosive or 

flammable  gas 

 

DO  NO

 install the board in the premise of high temperature, humidity, direct  shock and  vibration 

 

DO NOT

 place the I/O signal wires and power supply wires in the same wiring duct or use cables 

of multiple cores. 

 Wiring of I/O Points 

Wiring of input points: 

There are two types of DC inputs, SINK and SOURCE. 
 

Wiring  Loop 

DC 

(DC Signal IN) 

SINK Mode 

S/S

X37

X36

X35

X0

+24V GND

POWER SUPPLY

SINK Mode

 

DVPAETB-ID32A

 

Wiring  Loop 

DC 

(DC Signal IN) 

SOURCE Mode 

S/S

X37

X36

X35

X0

+24V GND

POWER SUPPLY

SOURCE Mode

 

 

DVPAETB-ID32A

   

Wiring of output points: 

Relay output circuit wiring 

MC2

MC1

9

10

C0

Y0

Y4

Y2

C2

Y3

Y5

Y1

5

2

3

7

8

1

6

7

2

5

4

MC2

MC1

Y6

Y7

8

DVPAETB-OR16A

 

 

1. Other  output  points 

6. Varistor*3 

2. Fuse 

7. Inductive  load 

3. Reverse  current  protection  diode*1 

8. Incandescent  light  (resistive  load) 

4. Manual  exclusive  output*2 

9. DC  power  supply 

5. Emergency  stop:  Uses  external  switch 

10. AC power  supply 

*1: There is no intermal protection circuit inside the output relay of DVPAETB-OR16A. Therefore, when 

activating  a DC inductive  load, please  parallelly  connect it to a  reverse  current  protection  diode  to  extend 

the  life of the  contact. The  reverse current protection  diode shall comply  with the  following specifications:   

 

a. Able to endure maximum 5 ~ 10 times the amount of the load voltage. 

b. Its forward current has to be bigger than the load current. 

*2:  The  manual  exclusive  output  uses  external  circuit  and  forms  an  interlock,  together  with  the  program 

inside the PLC,  to ensure safety protection in case  of any unexpected  errors. 

*3: There is no  internal protection circuit inside the  output relay of DVPAETB-OR16A. Therefore, when 

activating an AC inductive  load, please parallelly connect it to a varistor (0.1uF + “100ohm to 120ohm”) to 

reduce the interference  in the AC load and extend the life of the contact. 

Note:

 Please select proper safety wires. If the wires are not sufficient in long-time operation, overheating and 

sparking may occur.

 

 

注意事項 

 

請在使用之前,詳細閱讀本使用說明書。

 

 

本機為開放型

  (OPEN TYPE) 

機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊

/

擊意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或
意外衝擊本體,造成危險及損壞。

 

 

交流輸入電源不可連接於直流類型之輸入

/

出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確

認電源配線。請勿在上電時觸摸任何端子。

 

 

產品簡介

 

 

  DVPAETB-ID32A/OR16A

擴充驅動板,主要用於與高密度

I/O

模組

DVP32SM11N

DVP32SN11TN

連接使用。

 

 

產品外觀及各部介紹

 

DVPAETB-ID32A 

 

單位:

mm 

 

 

1. 40PIN

牛角座

 

4. 

底座固定鎖

 

2. 36PIN

輸入端子

 

5. 40PIN IDC

連接線

*1 

3. DIN

軌固定槽

 

6. DIN

 

*1: 

可使用台達標準配件

DVPACAB7A10 (IDC 40P-40P 1m) 

 

 

DVPAETB-OR16A 

 

單位:

mm

 

 

 

繁體中文 

1. 2PIN

電源輸入端子

 

7. DIN

軌固定槽

 

2. 

電源指示燈

 

8. 

底座固定鎖

 

3. 20PIN

牛角座

 

9. 20PIN IDC

連接線

*2 

4. 

輸出指示燈

 

10. DIN

 

5. 

輸出繼電器

 

11. 

輸出點動作指示燈

 

6. 9PIN+11PIN 

輸出端子座

 

 

*2: 

可使用台達標準配件

DVPACAB7B10 (IDC 40P-20Px2 1m) 

 

配件型號

 

輸入單元

 

輸出單元

 

配件名稱

 

電源

 

點數

 

形式

 

點數

 

形式

 

DVPAETB-ID32A 

N/A 

32 

DC Type 

Sink/Source 

 

DVPAETB-OR16A 

24V DC 

 

16 

繼電器

Relay 250V AC/30V DC   

2A/1

點,

5A/COM

 

 

連接線型號

 

線材名稱

 

線長

 

PIN

 

線材接頭種類

 

適用機種(配件)

 

DVPACAB7A10 

1m 

40P-40P 

二側

IDC

接頭

 

DVP32SM11N (DVPAETB-ID32A) 

DVPACAB7B10 

1m 

40P-20Px2 

二側

IDC

接頭

 

DVP32SN11TN (DVPAETB-OR16A) 

 

規格

 

 

電氣規格

 

 

 

 

 

 

 

DVPAETB-ID32A 

DVPAETB-OR16A 

絕緣阻抗

 

5 M

以上(所有輸出/入點對地之間

  500V DC

 

操作/儲存環境

 

操作:

0 ~ 55°C

(溫度),

  50 ~ 95%

(濕度),

 

污染等級

儲存:

-25 ~ 70°C

(溫度),

5 ~ 95%

(濕度)

 

重量(約)

(g) 

166g 

216g 

 

輸入點規格

 

輸入點形式

 

直流(無實際輸入元件,以下輸入規格參考於

DVP32SM11N

。)

 

輸入形式

 

直流(

SINK

SOURCE

 

輸入電壓電流

 

24V DC 5mA 

Off 

 On 16V DC

以上

 

動作位準

 

On 

 Off 14.4V DC

以下

 

反應時間

 

10ms   

電路隔離

/

操作指示

 

內部之光耦合器

/

內部之

LED

顯示燈

 

Reviews: