5011699700-S2S0
DVP-1160070-01
Page 1: ...2010 06 15 5011699700 S2S0 DVP 1160070 01...
Page 2: ...tenance staff from operating the device e g key or specific tools are required to open the enclosure in case danger and damage on the device may occur a DO NOT connect input AC power supply to any of...
Page 3: ...Input Point Spec Items 24VDC 15 20 single common port input Input No X0 X3 X4 X7 Input type DC SINK or SOURCE Input Current 10 24VDC 5mA Input impedance 4 7k Max frequency 20kHz 10kHz Off On 15VDC Act...
Page 4: ...Wiring 1 Use 22 16AWG 1 5mm single or multiple core wire on I O wiring terminals See the figure in the right hand side for its specification PLC terminal screws should be tightened to 1 90 kg cm 1 65...
Page 5: ...ply circuit protection fuse 2A i DVPPS01 DVPPS02 j DC power supply output 24VDC 500mA k DVP PLC main processing unit l Digital I O module Input Point Wiring There are 2 types of DC inputs SINK and SOU...
Page 6: ...SB360 3A 60V Extends the life span of contact 1 Diode suppression of DC load Used when in smaller power Figure 10a 2 Diode Zener suppression of DC load Used when in larger power and frequent On Off F...
Page 7: ...igure 13b g Manually exclusive output For example Y3 and Y4 control the forward running and reverse running of the motor forming an interlock for the external circuit together with the PLC internal pr...