5011668000-RU00

2007-08-13

 

 

Warning

 

 

Please read this instruction sheet carefully before use.

 

 

Switch off the power before wiring.

 

 

RTU-485 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, 
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the 
device (e.g. key or specific tools are required to open the enclosure) in case danger and damages on the 
device may occur.

 

 

DO NOT touch the internal circult in one minute after the power is switched off.

 

 

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. 
Check all the wiring again before switching on the power and DO NOT touch any terminal when the power is 
switched on. Make sure the ground terminal 

  is correctly grounded in order to prevent electromagnetic 

interference. 

 

 

Introduction 

Thank you for choosing Delta RTU-485 communication module. RTU-485 is a Modbus remote I/O 
communication module for Delta's PLC to remote-control Slim series DI/DO and AI/AO extension units. 
As a standard Modbus slave, RTU-485 is compatible with other master station complying with Modbus 
protocol. 
 

Product Profile & Outline 

S

G

D

-

D

+

ST O P

R UN

R

T

U

-4

8

5

R UN

A LA RM

PO W ER

R S- 4 85

1

2

3

5

6

9

8

7

4

10

11

12

13

14

15

16

 

Unit: mm 

1. POWER indicator 

9. Mounting hole for extension unit 

2. RUN indicator 

10. Nameplate 

3. ALARM indicator 

11. Extension port for extension unit 

4. RUN/STOP switch 

12. DIN rail slot (35mm) 

5. Communication indicator 

13. Fastening hole for extension unit 

6. Address setup DIP switch 

14. DIN rail clip 

7. Communication mode setup DIP switch 

15. Mounting rail for extension unit 

8. RS-485 communication port 

16. Power input 

 
 
 
 

ENGLISH 

 

Specifications 

 RTU-485 Connector 

Type 

Removable  3-pin  connector 

Transmission 
method 

RS-485 

Transmission  cable 

2 twisted  isolation  cables 

Electrical  isolation 

500V DC 

 Communication 

Valid  communication 
address 

1 ~ F0 (decimal: 1 ~ 240) 

Series  transmission 
speed 

1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps (bits  per  second) 

Communication 
mode 

7,E,1-ASCII / 7,O,1-ASCII / 7,E,2-ASCII / 7,O,2-ASCII / 7,N,2-ASCII / 8,E,1-ASCII / 
8,O,1-ASCII / 8,N,1-ASCII / 8,N,2-ASCII / 8,E,1-RTU / 8,O,1-RTU / 8,N,1-RTU/ 
8,N,2-RTU 

 Electrical Specification 

Power voltage 

24V DC (-15% ~ 20%) (with DC  input polarity reverse  protection)   

 Environment 

Noise  immunity 

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge, 4KV  Contact  Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Li4ne: 2KV, Digital I/O: 1KV 
Analog & Communication I/O: 1KV 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz , 1.4GHz ~ 2.0GHz , 10V/m 

Operation/storage 

Operation: 0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity),  pollution  degree 2 
Storage: -25ºC ~ 70ºC (temperature), 5 ~ 95% (humidity) 

Shock/vibration 
immunity 

International  standards: IEC61131-2

IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 

(TEST Ea) 

Standards 

IEC 61131-2, UL508 

 

Components 

 RUN/STOP Switch

 

Status 

Explanation 

1. RUN indicator on RTU-485 is On. 

   

2. AI/AO extension  unit  in RUN status. 

1. AI/AO extension  unit  switches  from RUN to STOP status. 

RUN 

 STOP 

2. Y points on DI/DO extension  unit are  all Off. 

1. RUN indicator on RTU-485 is Off. 

2. AI/AO extension  unit  in  STOP  status. 

3. Communication control  is  not allowed in AI/AO extension  unit. 

STOP 

4. Communication control  is  not allowed in DI/DO extension  unit. 

1. RTU-485 re-detects the number of points in DI/DO unit and the 

number of  AI/AO units. 

 

ST OP

RUN

 

STOP 

 RUN 

2. AI/AO extension unit switches from STOP to RUN status. 

 

 Address Setup DIP Switch

 

DIP Switch  Setting

 

Explanation

 

H’01 ~ H’F0

 

For valid RTU-485 address, the definition of ID0 ~ ID7 
are: 2

0

, 2

1

, 2

, … 2

, 2

.

 

H’00, H’F1 ~ H’FF

 

In the Modbus protocol, H’00 is defined as broadcast 
mode. H’F1 ~ H’FF are  incorrect RTU-485  addresses.

 

 

 

 Communication Mode Setup DIP Switch

 

The communication setup switch is a set of 8-bit DIP switches. PA0 ~ PA3 are for setting up RTU-485 
communication mode, DR0 ~ DR2 are for setting up the series transmission speed, and A/R is for setting 
up ASCII/RTU mode. There are 13 communication modes and 8 series transmission speeds available.

 

PA3 

PA2 

PA1 

PA0 

A/R 

Communication  mode 

OFF 

OFF 

OFF 

OFF 

ON 

7,E,1-ASCII 

OFF 

OFF 

OFF 

ON 

ON 

7,O,1-ASCII 

OFF 

OFF 

ON 

OFF 

ON 

7,E,2-ASCII 

OFF 

OFF 

ON 

ON 

ON 

7,O,2-ASCII 

OFF 

ON 

OFF 

OFF 

ON 

7,N,2-ASCII 

OFF 

ON 

OFF 

ON 

ON 

8,E,1-ASCII 

OFF 

ON 

ON 

OFF 

ON 

8,O,1-ASCII 

OFF 

ON 

ON 

ON 

ON 

8,N,1-ASCII 

ON 

OFF 

OFF 

OFF 

ON 

8,N,2-ASCII 

OFF 

ON 

OFF 

ON 

OFF 

8,E,1-RTU 

OFF 

ON 

ON 

OFF 

OFF 

8,O,1-RTU 

OFF 

ON 

ON 

ON 

OFF 

8,N,1-RTU 

ON 

OFF 

OFF 

OFF 

OFF 

8,N,2-RTU 

Other settings  of PA3, PA2, PA1, PA0 and A/R will be regarded as invalid 
communication modes 

 

 

DR2 

DR1 

DR0 

Series Transmission  speed 

OFF 

OFF 

OFF 

1,200 bit/s 

OFF 

OFF 

ON 

2,400 bit/s 

OFF 

ON 

OFF 

4,800 bit/s 

OFF 

ON 

ON 

9,600 bit/s 

ON 

OFF 

OFF 

19,200 bit/s 

ON 

OFF 

ON 

38,400 bit/s 

ON 

ON 

OFF 

57,600 bit/s 

ON 

ON 

ON 

115,200  bit/s 

 Function Codes Supported by RTU-485

 

RTU-485 complies with the standard Modbus protocol, supporting the 7 function codes, H’01, H’02, H’03, 
H’05, H’06, H’0F, and H’10. Please refer to the standard Modbus protocol for the specific data format of 
each function code. 

Function  code 

Function 

Data type 

Applicable  address 

H’01 

Read the output status of bit 
device 

bit 

DO area: H’0500 ~ H’057F 

H’02 

Read the input status of bit 
device. 

bit 

DI area: H’0400 ~ H’047F 

Special function  area: H’0000 ~ H’001F 

CR of the 1

st

 AI/AO unit: H’1600 ~ H’1630 

CR of the 2

nd

 AI/AO unit: H’1640 ~ H’1670 

CR of the 3

rd

 AI/AO unit: H’1680 ~ H’16B0 

CR of the 4

th 

AI/AO unit: H’16C0 ~ H’16F0 

CR of the 5

th

 AI/AO unit: H’1700 ~ H’1730 

CR of the 6

th

 AI/AO unit: H’1740 ~ H’1770 

CR of the 7

th

 AI/AO unit: H’1780 ~ H’17B0 

H’03 

Read  register 

word 

CR of the 8

th

 AI/AO unit: H’17C0 ~ H’17F0 

H’05 

Write single datum into  bit 
device 

bit 

DO area: H’0500 ~ H’057F 

RUN/STOP RTU module: H’0003 

H’06 

Write  single datum  into  register 

word 

Applicable to CR with write attribute in the 1

st

 

~ 8

th

 AI/AO  extension  unit. 

H’0F 

Write many data into bit device 

bit 

DO area: H’0500 ~ H’057F 

RUN/STOP RTU module: H’0003 

H’10 

Write many data into register 

word 

Applicable to CR with write attribute in the 1

st

 

~ 8

th

 AI/AO  extension  unit. 

Example:

 Use function code 03 to read CR0 and CR1 in the 1

st

 AI/AO extension unit: (ASCII mode) 

The request message sent from master PLC to RTU-485 is “: 01 03 16 00 00 02 E4 CR LF” 
The responding message sent from RTU-485 to the master PLC is “: 01 03 04 00 88 00 00 70 CR LF” 

Note: 

1. RTU-485 can only read and write one AI/AO extension unit at the same time.   
2. RTU-485 is able to read/write maximum 16 words at a time in the communication control.   

 

 

 

 

 

LED Indicators

 

 POWER Indicator 

LED status 

Indication 

How to deal with it 

Off 

No power 

Check if the power and connection of 
RTU-485 work normally. If both  work 
normally, your RTU-485  malfunctions. 
Please change to a new RTU-485.

 

Constantly On  in green 

RTU-485 module  is  powered 

 RUN Indicator

 

LED status 

Indication 

How to deal with it 

Off 

RTU-485 and the connected AI/AO 
extension unit  are  in  STOP status.   

-

 

Constantly On  in green 

RTU-485 and the connected AI/AO 
extension  unit  are  in RUN status. 

 ALARM Indicator 

LED status 

Indication 

How to deal with it 

Red  light flashes 

Low power voltage 

Adjust the voltage supplied to RTU-485 to 
normal  voltage.

 

Incorrect  communication  format 

Reset to the communication format 
supported  by RTU-485 and re-power the 
module after  the setup. 

Incorrect  station  No. 

Check if the station No. is within H’01 ~ 
H’F0. 

Constantly On  in red 

1. No  extension  unit  connected 

2. More than 8 extension  unit 

connected 

3. More then 128 I/O points in the 

extension  unit. 

1. Make sure  the extension unit  is correctly 

connected. 

2. Make sure the number of connected 

extension units is  less than  8. 

3. Make sure the number of I/O points is 

less  than128. 

 RS-485 Indicator 

LED status 

Indication 

How to deal with it 

Red  light  flashes  during 
communication 

The LED will flash once when RTU-485 
and the master completes  the 
communication  of 1  message. 

-

 

 

 

 

注意事項

 

  請在使用之前,詳細閱讀本使用說明書。

 

 

實施配線,務必關閉電源。

 

 

本機為開放型(

OPEN TYPE

)機殼,因此使用者使用本機時,必須安裝於具防塵、防潮及免於電擊

/衝擊意外的外殼配線箱內。另必須具備保護措施(如:特殊的工具或鑰匙才可打開),防止非維護

人員操作或意外衝擊本體,造成危險及損壞。

 

 

輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。

 

 

交流輸入電源不可連接於輸入/輸出信號端,否則可能造成嚴重損壞。請在上電前再次確認電源配線,

且請勿在上電時觸摸任何端子。本體上的接地端子 務必正確的接地,以提高產品抗雜訊能力。

 

 

產品簡介

 

感謝您使用台達

RTU-485

通訊模組,

RTU-485

Modbus

遠端

I/O

通訊模組,可實現台達可程式控制器對

Slim

系列

DI/DO

AI/AO

擴充模組的遠端控制

 

。此外,

RTU-485

做為標準的

Modbus

從站設備,也可以相

容其他遵循

Modbus

協定的主控設備。

 

 

產品外觀及各部介紹

產品外觀及各部介紹

產品外觀及各部介紹

產品外觀及各部介紹

 

S

G

D

-

D

+

ST O P

R UN

R

T

U

-4

8

5

R UN

A LA RM

PO W ER

R S- 4 85

1

2

3

5

6

9

8

7

4

10

11

12

13

14

15

16

 

尺寸單位:

mm 

1. POWER

指示燈

 

9. 

擴充機定位孔

 

2. RUN

指示燈

 

10. 

銘牌說明

 

3. ALARM

指示燈

 

11. 

擴充機連介面

 

4. RUN/STOP

開關

 

12. DIN

軌槽

  (35mm) 

5. Communication

指示燈

 

13. 

擴充機固定扣

 

6. 

站號設置開關

 

14. DIN

固定扣

 

7. 

通訊模式設置開關

 

15. 

擴充機固定槽

 

8. RS-485

通訊口

 

16. 

電源輸入口

 

 

繁體中文

繁體中文

繁體中文

繁體中文    

 

功能規格

 

 

RTU-485 

連接器

連接器

連接器

連接器

 

接頭

 

可插拔式

3Pin

連接器

 

傳輸方式

 

RS-485 

傳輸電纜

 

2

絞線式隔離線

 

電氣隔離

 

500V DC 

 

通訊

通訊

通訊

通訊

 

有效通訊位址

 

1 ~ F0

(十進位為

1 ~ 240

 

串列傳輸速率

 

支援

1,200

2,400

4,800

9,600

19,200

38,400

57,600

115,200 bps

(位元

/

秒)

 

通訊模式

 

支援

7,E,1-ASCII

7,O,1-ASCII

7,E,2-ASCII

7,O,2-ASCII

7,N,2-ASCII

8,E,1-ASCII

8,O,1-ASCII

8,N,1-ASCII

8,N,2-ASCII

8,E,1-RTU

8,O,1-RTU

8,N,1-RTU

8,N,2-RTU 

 

電氣規格

電氣規格

電氣規格

電氣規格

 

電源電壓

 

24V DC (-15% ~ 20%)

(具直流輸入電源極性反接保護)

 

 

環境規格

環境規格

環境規格

環境規格

 

雜訊免疫力

 

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge

4KV Contact Discharge 

EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV 
Analog & Communication I/O: 1KV 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz~1000MHz ,  1.4GHz~2.0GHz , 10V/m 

操作

/

儲存環境

 

操作:

0ºC ~ 55ºC

(溫度)、

50 ~ 95%

(濕度)、污染等級

  2 

儲存:

-25ºC ~ 70ºC

(溫度)、

5 ~ 95%

(濕度)

 

耐震動

/

衝擊

 

國際標準規範

  IEC61131-2

IEC 68-2-6  (TEST  Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

 

標準

 

IEC 61131-2

UL508 

標準

 

 

各部元件介紹

 

 

RUN/STOP

開關

開關

開關

開關

 

 

 

 

 

1. RTU-485

模組的

RUN

燈亮

 

RUN 

2. AI/AO

擴充模組處於

RUN

狀態

 

1. AI/AO

擴充模組由

RUN

切換到

STOP

狀態

 

RUN 

 STOP 

2. DI/DO

Y

點全部變為

OFF

狀態

 

1. RTU-485

模組的

RUN

燈熄滅

 

2. AI/AO

擴充模組處於

STOP

狀態

 

3. AI/AO

擴充模組不可通訊控制

 

STOP 

4. DI/DO

擴充機不可通訊控制

 

1. RTU-485

模組重新偵測擴充機

DI/DO

點數和

AI/AO

台數

 

S TOP

R U N

 

STOP 

 RUN 

2. AI/AO

擴充模組由

STOP

切換到

RUN

狀態

 

Reviews: